User interfaces
vacon • 63
Local contacts: https://www.danfoss.com/en/contact-us/contacts-list/
5.3.3
Parameters
Through this submenu, you can reach the application parameter groups and parameters. More in-
formation on parameters in chapter 7.
5.3.4
Diagnostics
Under this menu, you can find
Counters
5.3.4.1
Active faults
5.3.4.2
Reset faults
5.3.4.3
Fault history
5.3.4.4
Total counters
Table 22.
Menu
Function
Note
Active faults
When a fault/faults appear(s), the
display with the name of the fault
starts to blink. Press OK to return
to the Diagnostics menu. The
submenu shows the
number of faults. Select the fault
and push OK to see the fault-time
data.
The fault remains active until it is
cleared with the Reset button (push
for 2 s) or with a reset signal from the
I/O terminal or fieldbus or by choos-
ing
(see below).
The memory of active faults can
store the maximum of 10 faults in
the order of appearance.
Table 23.
Menu
Function
Note
Reset faults
In this menu you can reset faults.
For closer instructions, see chap-
ter 8.
CAUTION!
Remove external Control
signal before resetting the fault to
prevent unintentional restart of the
drive.
Table 24.
Menu
Function
Note
Fault history
40 latest faults are stored in the
Fault history.
Entering the Fault history and click-
ing OK on the selected fault shows
the fault time data (details).
Table 25. Diagnostics menu, Total counters parameters
Code
Parameter
Min
Max
Unit
Default
ID
Description
V4.4.1
Energy counter
Varies
2291
Amount of energy taken from
supply network. No reset.
NOTE FOR TEXT KEYPAD:
The highest energy unit
shown on the standard key-
pad is
MW
. Should the
counted energy exceed 999.9
MW, no unit is shown on the
keypad.
V4.4.3
Operating time
(graphical keypad)
a d hh:min
2298 Control unit operating time