V2 CITY2+ Скачать руководство пользователя страница 18

ENGLISH

- 38 -

PARAMETER

VALUE

DESCRIPTION

DEFAULT

MEMO

t.ASE

Lock advance time

1.0”

0.0”- 1’00

While the electric lock is energized, the gate will stay standstill for 

t.ASE 

time, to make its release easier.
In case 

t.ASE

 is lower than 

t.SEr

, the lock energizing will go on while 

the doors will start moving.

m

 WARNING: in case the gate has no electric lock, set the value 

0.0”

t.inv

Backlash time

no

0.5” - 1’00

It could be useful to give a closing command to motors, to help the 
electric lock release. The control unit controls the motors in reduced power 
in closing direction for the setup time

no

Function deactivated

t.PrE

Pre-blinking time

1.0”

0.5” - 1’00

Before any gate movement, blinker will be activated for 

t.PrE

 time, to 

warn about the incoming motion

no

Function deactivated

Pot1

Motor 1 power

80

30 - 100

The displayed value is the percentage of max. motor power

Pot2

Motor 2 power

80

30 - 100

The displayed value is the percentage of max. motor power

Po.r1

Power motor 1 during slow-down phase

50

0 - 70

The displayed value is the percentage of max. motor power

Po.r2

Power motor 2 during slow-down phase

50

0 - 70

The displayed value is the percentage of max. motor power

P.bAt

Maximum motor power during battery operation

During battery operation, the controller is powered with a lower voltage 
compared to mains power. For this reason, the power of the motors is 
reduced compared to normal operation and may not be sufficient to move 
the gate panels effectively. 
This menu allows you to activate the motors at their maximum power 
during battery operation.

Si

Si

Function activated

no

Function deactivated

SPUn

Start off 

When the gate is standstill and it begins moving, the initial inertia must be 
faced, therefore, if your gate is quite heavy, its doors could not move.
In case the 

SPUn

 (pickup) function is activated, for the first 2 seconds of 

motion of each door, the control unit will ignore both 

Pot1

 and 

Pot2

 

values and it will give motors the maximum power command in order to 
overcome the gate inertia.

Si

Si

Function activated

no

Function deactivated

rAM

Starting ramp 

4

0 - 10

In order not to stress too much the motor, when the motion starts the 
power is gradually increased, until reached the set value or 100% if the 
take-off is enabled. 
Higher is the set value, longer the length of time of the ramp, that is the 
time necessary to reach the value of nominal power. 

Содержание CITY2+

Страница 1: ...TALE PER CANCELLI AD ANTA E SCORREVOLI DIGITAL CONTROL UNIT 24V FOR LEAF SWING AND SLIDING GATES ARMOIRE DE COMMANDE NUM RIQUE 24V POUR PORTAILS VANTAILS ET COULISSANTS CUADRO DE MANIOBRAS DIGITAL 24V...

Страница 2: ......

Страница 3: ...SHING LIGHT 5 9 LOCK 5 10 LIMIT SWITCH AND ENCODER 5 11 EXTERNAL AERIAL 5 12 PLUG IN RECEIVER 5 13 ADI INTERFACE 5 14 ELECTRIC CONNECTIONS 6 CONTROL PANEL 6 1 USE OF THE DOWN MENU AND UP KEYS FOR PROG...

Страница 4: ...e plastic case has an IP55 insulation to connect flexible or rigid pipes use pipefittings having the same insulation level Installation requires mechanical and electrical skills therefore it shall be...

Страница 5: ...can be used for a signal light or a 24 V flashing light Auxiliary relay with programmable logic for courtesy light flashing light or other use ENERGY SAVING FUNCTION 5 INSTALLATION Installation of co...

Страница 6: ...d receiver output of photocells 2 between terminals L8 PHOTO2 and L11 COM of the control unit Use outputs having normally closed contact mWARNING if several couples of same kind photocells are mounted...

Страница 7: ...mmediately The direction of the gate at next command of START or PEDESTRIAN START depends upon the parameter STOP it inverts or continues the motion If the input STOP is disabled the command makes the...

Страница 8: ...and K5 COM Connect the close limit switch to motor 2 using terminals K4 FCC2 and K5 COM Installation of encoders Connect the negative feeds BLACK cable for both encoders to terminal K5 COM Connect the...

Страница 9: ...al Devices Interface interface of the control unit CITY2 allows the connection to V2 optional modules Refer to V2 catalogue or to the technical sheets to see which optional modules with ADI interface...

Страница 10: ...1 OPENING Z4 Motor 1 CLOSING Z5 Motor 2 OPENING Z6 Motor 2 CLOSING B1 B2 230VAC courtesy light or flashing light POW 24V power supply POW Power supply BAT pole of the optional battery pack code 161212...

Страница 11: ...ENGLISH 31 F1 L N L N F1 MAINS MAINS CITY2 CITY2 L CITY2 CITY2 L CITY2 BC OVERLOAD DOWN MENU UP BAT POW POW BAT RECEIVER...

Страница 12: ...as been caused by a safety device border or obstacle detector The central arrow shows that the gate is on pause If it blinks it means that the time countdown for the automatic closing has been activat...

Страница 13: ...utomation work properly and if necessary modify the configuration of the desired parameters 8 LOADING OF DEFAULT PARAMETERS If necessary it is possible to restore all the parameters to their standard...

Страница 14: ...anel is jammed A START command is given This position is memorized as the close point for gate panel 2 4 3 Gate panel 1 is closed until one of the conditions listed in point 4 2 occur this position is...

Страница 15: ...you can alternate the display of thousands or units Area 2 is the reading of the number of cycles before the next request for service its value is rounded down to the hundreds Area 3 is the setup of...

Страница 16: ...t NOTE By holding down the UP or DOWN keys configuration menu items will scroll fast until item FinE is viewed In this way you can quickly reach either the top or bottom of the list PARAMETER VALUE DE...

Страница 17: ...e to be setup is t Ch1 NOTE To avoid that the door does not close completely we recommend to setup a longer time than t APP opening time t C2P Leaf 2 closing time during pedestrian cycle no 0 5 5 0 Du...

Страница 18: ...slow down phase 50 0 70 The displayed value is the percentage of max motor power P bAt Maximum motor power during battery operation During battery operation the controller is powered with a lower vol...

Страница 19: ...e last closing stretch t CvE Fast closing time after slowing down 0 0 0 0 3 0 If a slowing time other than 0 is set up it could be likely that the gate speed is not enough for the lock to fasten durin...

Страница 20: ...s generally used no no Function deactivated The gate closes after the time set for the function Ch AU 0 5 20 0 The gate closes after the setup time PA tr Pause after transit Per rendere minimo il temp...

Страница 21: ...nput STOP stops the gate pressing the command START the gate continues the motion invE The command STOP stops the gate at the next START the gate starts moving in the opposite direction Fot1 Photocell...

Страница 22: ...led for optical safety edges rESi Test enabled for conductive rubber safety edges FC En End of Stroke Inputs no no End of stroke inputs are disabled L SW End of stroke equipped with a normally close s...

Страница 23: ...ing on the control unit disconnect through the disconnecting switch on the power line and remove the power supply terminal 2 Be sure that there is no voltage break upstream the control unit 3 Check wh...

Страница 24: ...nected even if they are not enabled for a few instants after movement of a gate panel This means that the connection to the encoder for that gate panel is reversed Exchange terminal K1 with K2 or K3 w...

Страница 25: ...V2 S p A Corso Principi di Piemonte 65 67 12035 RACCONIGI CN ITALY Tel 39 0172 812411 Fax 39 0172 84050 info v2home com www v2home com...

Отзывы: