PARAMETER
VALUE
DESCRIPTION
AntE SCor
MEMO
Ch.AU
Automatic closing
no
no
no
Function deactivated
0.5” - 20.0’
The gate closes after the setup time
StoP
Stop Input
no
no
no
The input STOP is not available
ProS
The input STOP stops the gate: pressing the command START the gate
continues the motion
invE
The command STOP stops the gate: at the next START the gate starts
moving in the opposite direction
Fot1
Photocell 1 input
This menu allows enabling the input for type 1 photocells, that is to
say, photocells active both during the opening and closing phase
no
no
no
Input disabled
APCh
Input enabled
Fot2
Photocell 2 input
This menu allows enabling the input for type 2 photocells, that is to
say, photocells non active during the opening phase
CFCh CFCh
CFCh
Input enabled even at standstill gate too
Ch
Input enabled for the closing phase only
m
WARNING: If the photocell is damaged the gate is opened
anyway.
Before closing the test of the photocell (if enabled) will detect
the fault and prevent the gate from closing.
no
Input disabled
CoS1
Safety edge 1 input
This menu allows enabling the input for type 1 safety edge, that is to
say, fixed edges
no
no
no
Input disabled
APCh
Input enabled in opening and closure
AP
Input enabled during the opening and disabled during the closure
CoS2
Safety edge 2 input
This menu allows enabling the input for type 2 safety edge, that is to
say mobile edges
no
no
no
Input disabled
APCh
Input enabled in opening and closure
Ch
Input enabled during the closing and disabled during the opening