ENGLISH
- 42 -
9 - INSTALLATION MENÙ (SEt)
This menu allows you to perform the movements of the gate
needed during installation.
The automatic learning procedure enables to save run limits based
on data collected by the encoder.
The manual handling procedure allows to control the gate in hold
to run mode in special cases such as during installation /
maintenance or a malfunction of the photocells or edges.
m
ATTENTION: before proceeding, make sure to position
the mechanical stops and the limit sensors correctly.
1.
Press and hold the
OK
key until the display shows
-SEt
2.
Release the
OK
key: the display shows
ESC
(only press the
OK
key if it is desired to exit this menu)
3.
Use the keys
h
and
i
to select the menu
Mov
to activate
manual handling or
APPr
to start the automatic learning
procedure of the run limits
4.
Press
OK
to start the selected procedure
9.1 - AUTOMATIC LEARNING OF THE RUN
LIMITS
m
CAUTION: to perform the self-learning procedure it
is necessary to disable the ADI interface by means of the
menu
i.Adi
. If some safeties are controlled by means of the
ADI module, they will not be active during the self-learning
NOTE: during the self-learning the slowdown in the limit
switch area is not active.
To store the precise position of the range limit it is
recommended to activate the slow speed near to the limit.
The position at which the slow speed is activated is stored
as the starting point for slowing down.
5.
The display shows the control panel and the automatic learning
procedure of the run limits starts.
5.1
If the gate is not at the closed limit, the motor will
activate to close at the slow speed until it reaches the
range
limit.
5.2
Gate opening is activated until the opening limit switch is
reached.
NOTE:
To slow down the motor press the control unit
button
i
or activate the START P. command (wired or
wireless) when the gate comes close to the range limit.
5.3
Gate closing is activated until the closing limit switch is
reached.
NOTE:
To slow down the motor press the control unit
button
i
or activate the START P. command (wired or
wireless) when the gate comes close to the range limit.
6.
At the end of the automatic learning procedure, the control
unit automatically exits this menu and returns to normal
operation.
9.2 - MANUAL HANDLING
m
WARNING: when this procedure is activated the
safeties are not active.
5.
The display shows
MAn
6.
Press and hold the
h
key to open the gate or the
i
button to
close the gate
7.
Release the button to stop the gate
8.
To exit this menu, press
OK
NOTE: If the motor is inactive for more than one minute
the procedure terminates automatically.
APPr
ESC
Mov
MAn
-SEt