36
36
36
Pedestrian Start during the partial opening phase
This menu allows fixing the control unit conduct in case it receives a
Pedestrian Start command during the partial opening phase.
PAUS
The gate stops and goes to pause
ChiU
the gate immediately starts closing
no
the gate goes on with the opening phase (command is ignored)
WARNING:
a Start command in any phase of partial opening will
cause the total opening; the Start Pedestrian command is always igno-
red during a total opening.
Automatic closing
During the automatic operation, the control unit will automatically
close the gate when a set-up time expires.
The Start command, if enabled by
St.PA
menu, allows closing the gate
before the set up time expires.
In semi-automatic operation, that is to say, if the automatic closing
function is disabled by setting the value to zero ('
no
' will be displayed),
the gate can be closed through the start command only: in this case,
St.PA
menu setup will be ignored.
If the control unit receives a Stop command when the gate is in
pause, it will automatically pass to the semi-automatic operation.
Closing after transit
During the automatic operation, the pause count down starts from the
set up value each time a photocell operates during the pause.
If the photocell operates during the opening time, this time will be
immediately stored as pause time.
This function allows having a fast closing as soon as transit through
the gate is completed, therefore, a time shorter than
CH.AU
is
generally used.
Ch.AU
will be used when ‘
no
’ is set up.
As for semi-automatic operation, this function is not active.
Blinker during pause time
Blinker usually operates during the gate motion only; however, if this
function is enabled, blinker will be on during the pause time too.
Содержание GOLD230V-DM
Страница 2: ...ISTRUZIONI 1 INSTRUCTIONS 23 NOTICES 45 INSTRUCCIONES 67 I GB F E...
Страница 24: ...22 22 22...
Страница 46: ...44 44 44...
Страница 68: ...66 66 66...
Страница 90: ...88 88 88...
Страница 91: ......