OPERATION DEFECTS 

This paragraph shows some possible operation defects along
with their causes and solutions.

MAINS led does not switch on

It means that there is no voltage on 

City5

control unit card.

1.

Make sure that there is no power outage above the control 
unit

2.

Before working on the control unit, disconnect through the 
disconnecting switch placed on the power line and take off 
the power supply terminal

3.

Check whether the fuse F1 is burnt-out; if so replace it with 
one of the same value.

OVERLOAD led is on

It means that there is an overload on the power supply of the
accessories

1.

Remove the extractable part containing terminals 1 to 12. 
OVERLOAD led will switch off.

2.

Remove the overload cause.

3.

Reinsert the terminal board extractable part and check that

this led is not on again.

The repeating leds switch on properly, but the lamps of the
lights do not switch on

It means that there is no voltage on the power supply of the
lamps

1.

Make sure that there is no power outage above the control 
unit

2.

Before working on the control unit, disconnect the circuit of 
power supply of the lamps and take off the extractable green 
terminal 

W1 - W2

.

3.

Check whether the fuse F2 is burnt-out; if so replace it with 
one of the same value.

Error 1

The following writing appears on display when you exit from
programming:

It means that changed data could not be stored.
This kind of defect has no remedy and the control unit has to
be sent to V2 Elettronica for repairs. 

  

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Содержание City5

Страница 1: ...uesto caso a riposo il semaforo verde in entrata e rosso in uscita I veicoli in entrata possono transitare senza dover avviare il ciclo Per transitare in uscita occorre premere il pulsante o usare un...

Страница 2: ...Nel passaggio dal verde in una direzione al verde nell altra direzione viene dato un avvertimento di 2 secondi con verde lampeggiante e un tempo di 5 secondi con rosso in entrambe le direzioni per po...

Страница 3: ...ROL UNIT POWER SUPPLY 22 LAMPS OF THE LIGHTS 22 INTERFACE WITH THE CONTROL UNIT OF THE GATE 22 PRESENCE AND CONTROL DEVICES 22 PLUG IN RECEIVER 24 OUTDOOR ANTENNA 24 ADI INTERFACE 24 CONTROL PANEL 24...

Страница 4: ...accidental detachment of a conducting wire dangerous voltage parts will not come into contact with safety low voltage ones The plastic case has an IP55 insulation to connect flexible or rigid pipes us...

Страница 5: ...ther vehicles once reached a predetermined threshold parking capacity Function of reservation while approaching in case of green light on the opposite direction with possibility of setting the priorit...

Страница 6: ...the gate control unit to give the opening control and synchronize the switch on of the lamps with the gate motion This connection requires the terminal board G mWARNING The synchronization of the lam...

Страница 7: ...ing a diode with the cathode on terminal M1 and the anode on terminal M2 for the outer side and with the cathode on terminal M4 and the anode on terminal M5 for the inner side provided that the device...

Страница 8: ...up of an incoming phase CHANNEL 2 rt Starting up of an outgoing phase CHANNEL 3 rt break of the phase at rest CHANNEL 4 rt Start to the control unit of the gate without starting up of the phase mWARN...

Страница 9: ...the storage of the changes made and to revert to the normal working of the control unit In order not to loose the own configuration it is compulsory exiting through this menu item mWARNING If no oper...

Страница 10: ...o phases are active neither incoming nor outgoing SPEn outer lights off vErd green light on fixed roSS red light on fixed Light on at rest on the inner side Through this menu it is possible to set the...

Страница 11: ...or of presence placed on the arrival side is cleared Polarity of the sensor of presence Thanks to this menu it is possible to use the control unit with sensors of presence of any kind Set the item n C...

Страница 12: ...de while the phase is started up in the opposite direction If set no green is given immediately when possible otherwise the red fixed light is on Time of green The green fixed light is on during the t...

Страница 13: ...e relay sending the start signal to the control unit of the gate When the control is active the terminal G3 N O is short circuited with the terminal G4 while the terminal G5 N C is open Mon a control...

Страница 14: ...e the number of vehicles inside the car park is displayed for 2 seconds Cont the number of vehicles inside the car park is constantly displayed Number of vehicles inside the car park By this menu it i...

Страница 15: ...ining terminals 1 to 12 OVERLOAD led will switch off 2 Remove the overload cause 3 Reinsert the terminal board extractable part and check that this led is not on again The repeating leds switch on pro...

Страница 16: ...9 5 Minimum time of the red 2 0 i SCA Si no Enabling of the warning light of open gate Si C CEn Mode to send the start control on the control unit of the gate Mon Mon a control pulse is given each tim...

Страница 17: ...or the power supply of the accessories C U Power Power supply from network 230V 120V W1 W2 Power supply for the lamps of the lights Z1 GREEN inner traffic light Z2 COMMON inner traffic light Z3 RED in...

Страница 18: ...e of the red light has to be set in order to coincide with the opening time of the gate Once started up the phase the succession green flashing green and minimum time of red have a fixed length indepe...

Страница 19: ...riving the gate In this case at rest the traffic light is green incoming and red outgoing The incoming vehicles can pass without starting up the phase To go out it is necessary to press the button or...

Отзывы: