Type
Max AC Current (A)
Rated current of AC breaker (A)
Single Phase Ongrid Inverter
VT-6607005
23
32
Safety & Symbols
02
Note:
The Inverter can be only connected to low-voltage grid.
(220/230Vac, 50/60Hz).
Surge Protector Recommendation
• AC side, nominal discharge current 20KA, second grade lightning protection,
protection voltage 2.5KV.
• DC side, nominal discharge current 20KA, second grade lightning protection,
protection voltage 3.2KV.
• The wiring distance between the inverter and the distribution box should be at
least 5 meters.
2. Safety & Symbols
2.1 Safety Precautions
1. All work on the inverter must be carried out by qualified electricians.
2. The device may only be operated with PV panels.
3. The PV panels and inverter must be connected to the ground.
4. Do not touch the inverter cover until 5 minutes after disconnecting both DC
and AC power supply.
Circuit Breaker Recommendation