background image

For example,Before selecting the mode, you can set it up ac cording to the local power grid, 

PV input mode and battery type

Power

 

grid

 

PV input mode

 

Battery parameters

 

   

Содержание VT-6605103

Страница 1: ... BUL L KARAVELOW 9B Thank you for selecting and buying V TAC Product V TAC will serve you the best Please read these instructions carefully keep this user manual handy for future reference If you have any another query please contact our dealer or local vendor from whom you have purchased the product They are trained and ready to serve you at the best INTRODUCTION Multi Language Manual QR CODE Ple...

Страница 2: ...ion Possible damage to health as a result of the effects of radiation Do not stay closer than 20 cm to inverter for any length of time Ensure input DC voltage Max DC voltage Over voltage may cause permanent damage to inverter or other losses which will not be included in warranty Authorized service personnel must disconnect both AC and DC power from inverter before attempting any maintenance or cl...

Страница 3: ...V supply has been disconnected Hazardous voltage will present for up to 5 minutes after disconnection from power supply CAUTION RISK of electric shock from energy stored in capacitor Never operate on the inverter couplers the MAINS cables Battery cables PV cables or the PV generator when power is applied After switching o ffthe PV battery and Mains always wait for 5minutes to let the intermediate ...

Страница 4: ...r to the loads as first priority if solar energy and battery are not sufficient to power all connected loads utility energy Main Grid will supply power to the loads with solar energy at the same time 2 When PV Grid is available without battery A Solar energy provides power to the loads as first priority if solar energy is sufficient the excess power will feed to grid B Solar energy provides power to the...

Страница 5: ...he grid 2 When Grid Battery is available PV is disconnected A On charge time grid will charge battery and supply power to the connected loads at the same time B On discharge time if load power is less than battery power battery will supply power to loads as first priority the excess power will be feed to grid C On discharge time if load power is more than battery power battery and grid will supply ...

Страница 6: ...EFINITION DIMENSION Object Description A B PV1 PV1 PV2 PV2 C WiFi port for external WiFi D USB port for upgrading E F DRM BMS G H CT CAN I J DRY IO NTC K EPS output L Grid M Battery Battery N PV switch O Battery switch ...

Страница 7: ...urrent to array 0 DC disconnection swtich AC output Norminal AC power VA 5000 Max apparent AC power VA 5000 Rated grid voltage range V 230 176 to 270 Rated grid frequency Hz 50 60 Norminal AC current A 21 7 Max AC current A 21 7 Displacement power factor 0 99 leading 0 99 lagging Total harmonic distortion THDI 2 Load control optional AC input Norminal AC power VA 5000 Rated grid voltage range V 23...

Страница 8: ...ncy 230VAC 50 60Hz EPS rated current A 21 7 Max EPS current A 21 7 Switch time s 500ms Total harmonic distortion THDv 2 Parallel operation Yes Compatible with the generator Yes signal provided only Battery parameter Ba ery type Lithium ba ery Lead ACID Ba ery voltage range V 40 58 Recommended ba ery voltage V 48 Cut Off Voltage V 40 Max charging Voltag V 58 Max Protective Voltage V 59 Max charge d...

Страница 9: ...75 Net weight kg 82 Gross weight kg 86 Installation console mode Operating temperature range C 25 60 derating at 45 Storage temperature C 25 60 Storage Operation relative humidity 4 100 Condensing Altitude m 2000 Ingress Protection IP20 for outdoor use Protective Class Ⅰ Night time consumption 3W Over Voltage Category lⅡ MAINS Ⅱ PV Ba ery Pollution Degree II Cooling Natural Noise level 40dB Invert...

Страница 10: ...tional I GPRS module optional J User manual K CT Installation tools crimping pliers for binding post and RJ 45 screwdriver manual wrench etc Step 1 Fixing the bottom with the battery box 1 using 8 M5 12 screws Step 2 The battery box 2 fixed Align the lower notch of battery box 2 with the upper guide of battery box 1 lower it and push it to the right Facilitate pushing to the right the coil can be r...

Страница 11: ...tery boxes are fixed open the battery box door and use 3 M5 12 screws to fix it upward Step 4 PCS is fixed the method is the same as step 2 step 3 To facilitate pushing to the right the coil can be removed before assembly Rail Coil ...

Страница 12: ...xed to the wall and the bottom is fixed to the ground using M6 Expansion screws Step 6 The battery fixing as shown in the figure push from the right and a total of 24 M5 12 screws are used Please pay attention to the direction when assembling the battery ...

Страница 13: ...e system communication line 6 All the above wiring and operations must be carried out after the whole machine is powered down and all of them need professional personnel to complete Battery output input CAN Link Port 1 Link Port 0 CAN Link Port 1 Link Port 0 CAN Link Port 1 Link Port 0 CAN Link Port 1 Link Port 0 CAN Link Port 1 Link Port 0 CAN Link Port 1 Link Port 0 CAN BMS Battery6 Battery5 Bat...

Страница 14: ...ith the requirement of the local public grid Micro breaker should be installed between inverter and grid any load should not be connected with inverter directly GRID CT N L PE Meter Grid side Main Breaker CT On Grid Breaker AC Breaker Home Load PV1 PV2 Loads Off Grid Breaker Table of cable and Micro breaker recommended Model VT 6605103 Cable 5 6mm Micro breaker 32A ...

Страница 15: ...rating voltage should be conformed to MPPT voltage range Step3 Connect the completed cable to the power grid and eps interface and tighten the screws Warning PV module voltage is very high which already achieve dangerous voltage range please comply with electric safety rules when connecting Please do not make PV positive or negative ground Connection Steps Step 1 Checking PV module ensure the PV a...

Страница 16: ...tion interface between inverter and meter is RS485 with a Rj45 connector DRM Connection DRM is provided to support several demand response modes by emitting control signals as below Note Only PIN6 DRM0 is available now and other PIN functions are being developed PIN 1 2 3 4 5 6 7 8 CAN Definition X X X BMS_CANH BMS_CANL X X X Rs485 Definition X X X X X GND BMS_485A BMS_485B Load 1 8 1 8 1 8 1 2 3 4 ...

Страница 17: ...terface is consistent with WIFI interface Please refer to the GPRS user manual for detailed connection steps WIFI GPRS PIN Definition Step1 Plug Wifi into WiFi port at the bottom of the inverter Step2 Build the connection between the inverter and router Step3 Create a user account online Please check the WiFi user manual for more details WIFI WIFI WIFI WIFI 1 2 3 4 5V RS485_A RS485_B GND ...

Страница 18: ...Inverter Warning E lit in red The inverter is in fault status Off The inverter has no errors F Esc Return from current interface or function G Up Move cursor to upside or increase value H Down Move cursor to downside or decrease value I Enter Confirm the selection A Display the information of the inverter Function Button Indicator LED A B C D E F G H I Grid EPS Alarm Fault Green Green Yellow Red Ini...

Страница 19: ...Instructions for the use of three modes ...

Страница 20: ...For example Before selecting the mode you can set it up ac cording to the local power grid PV input mode and battery type Power grid PV input mode Battery parameters ...

Страница 21: ...is voltage at BAT port of measuring inverter 1 The battery charge is too low 1 If the battery is too low charge it in time 2 The battery BMS sends an instruction to prohibit discharging 2 Check the battery communication protocol Bat low vol The battery voltage is lower than the normal working voltage value Charge the battery as soon as possible 1 The PV input voltage exceeds the MPPT voltage 1 Che...

Отзывы: