VG-6627 Digital Somke Detector 

Installation and Operation Manual V1.04

 

Address setting 

1. VG-6537 Digital Programmer is used to write an address of the Detector.Connecting Progarmmer with loop

terminals:1,2 of the Detector before it installation . 

2.Set address, Pressing Write key, the address will be shown on the numeric display if successful. It is fail if there

is no address. Please refer to VG-6537 Digital Programmer Manual for details. 

3.Address range should be within 0

255. The address is unique in a loop.

Mode setting 

Sensitivity Mode 

dB/m 

Application Environment 

0.109 

Clean Room 

0.116 

Hotel Room,Small Flat; 

0.126 

Office,Long Corridor 

0.136 

Ware House,Car Park 

Factory Setting

Sensitivity Mode 1

The  VG-6627  sensitivity  mode  can  be  set  by  Control  Panel,please  refer  to  the  corresponding  Manual  for

details.

Testing 

Warning

Power is switched off before all devices are installed completely. 

The detector must be tested after installation or regular maintenance. 

Registration:

 The fire alarm control panel  will registers the detector on line to check if the  address of the

detectors mounted is the same address as that registered in the control panel.

Fire condition:

 After registration, make detector under fire conditions by using Smoke generator to test

whether the detector alarms normally and control panel displays its registered address.

Reset

After testing, reset the detector through control panel.

Fault Finding 

Detector Fault on 
Control Panel 

Check wiring of Common base, no water no short-circuit and open circuit. 

Chenk the connection between detector and common base. 

Nuisance alarm 

The detector alarm frequently but there is no Fire and other unusual, then check whether 

the chamber in the detector is too dirty and needs to be cleaned 

Otherwise, the circuit may be broken. 

Address Fault 

Address is set incorrectly,Reset by VG-6537 Digital Programmer. 