NivoRadar
®
Continuous level measurement
Series NR 4000
Technical information / Instruction manual
Technical data
page 14
Adjustment
Adjustment elements
3 x keys for menu adjustment
Smartphone/Tablet
Adjustment app
Voltage supply
Operating voltage U
B
Ʋ
at 4 mA
12 … 35 V DC
Ʋ
at 20 mA
9 … 35 V DC
Reverse voltage protection
Integrated
Permissible residual ripple
Ʋ
for 12 V < U
B
< 18 V
≤ 0.7 V
eff
(16 … 400 Hz)
Ʋ
for 18 V < U
B
< 35 V
≤ 1 V
eff
(16 … 400 Hz)
Load resistor
Ʋ
Calculation
(U
B
- U
min
)/0.022 A
Ʋ
Example - with U
B
= 24 V DC
(24 V - 12 V)/0.022 A = 545 Ω
Overvoltage protection
Dielectric strength against metallic
mounting parts
> 10 kV
Overvoltage resistance (test impulse
voltages 1.2/50 µs at 42 Ω)
> 1000 V
Additional overvoltage arrester
Due to the floating structure of the electronics and
comprehensive insulation measures generally not
necessary.
Electrical protective measures
Potential separation
Electronics potential free up to 500 V AC
Protection rating
IP66/IP68 (3 bar, 24 h) acc. to IEC 60529,
Type 6P acc. to UL 50
Altitude above sea level
5000 m (16404 ft)
Protection class
III
Pollution degree
4