UV-technik EVG UVT 2x 100-200 W Скачать руководство пользователя страница 14

General sales and delivery conditions of UV-Technik Speziallampen GmbH are valid

Provision of the manual is mandatory

page 14 of 17 

subject to change without notice

 

operating manual EVG UVT 200-480W 

9

 

Installation instructions 

Point of installation 

The EVG UVT must be installed and operated only in a dry, chemically and bioligically inactive environment. 
Installation  in  vibrating  parts  of  the  system  is  not  allowed.  Hints  regarding  IP  protection  have  to  be 
observed.  The  EVG  UVT  must  be  mounted  upright  at  a  grounded  mounting  base,  which  absorbs  and 
removes ideally the emitted heat partly. For the installation, suitable fixing screws have to be selected. It is 
necessary to ensure that a distance between the screw and the printed ciruit board of at least of 3 mm is 
kept. In no case, wide flat screw heads may be used, which protrude below the PCB (danger of short ciruit!). 
The EVG UVT and its cabeling should be mounted separatelly from other components of the installation if 
possible. That is especially important for control, signal or sensor cables with its low voltages/currents. 

Connection / cabling 

The  EVG  UVT  must  be  connected  according  the  terminal  diagram  and  the  front  sticker.  The  ballast  is 
equipped with spring tension terminals, suitable as well for stranded wires as for rigid cables. The possible 
wire gauges are spezified in the technical data. Length of the stripped insulation or ferrules must be chosen 
according  to  the  size  of  the  terminals.  The  connection  must  be  tight.  Otherwise  short  ciruits,  wrong  or 
loose connections could cause disfunctions and damages. 

Cabeling of lamps 

Each lamp must be connected to the EVG UVT with an individual cable. It is not allowed to bundle several 
lamp  cables  into  a  multi-core  cable.  Cable  connections  to  the  lamp  may  not  be  disconnected  during 
operation. By no means install additonal components into the lamp supply cable, such as relays, switches, 
ignitors  or  capacitors.  The  number  of  the  clamping  points  in  the  lamp  cable  should  be  reduced  to  a 
minimum, if possible any additional clamping should be avoided. Designated clamps and connectors must 
be  checked  carefully,  not  only  rearding  electrical  data  but  necessarily  also  relating  to  temperature  and 
environmental conditions. Clamp contacts must be protected against corrosion. Sparks at corroded clamps 
could cause disfunctions or breakdown of the EVG UVT and imply fire hazard. 

Because of the high frequency supply, lamp cables emitts disturbances. Hence never install mains supply 
cables or control cables parallel to lamp cables. To minimize EMC disturbances, lamp cables must be kept 
as short as possible. Do not exceed the maximal lenght or cable capacity specified in the technical data. It is 
allowed  to  use  shielded  cables  to  reduce  interferences.  But  note  thus  increases  the  cable  capacity. 
Installing lamp cables in parallel as well as at metallic surfaces or cable ducts  raise also the capacity. The 
sum of all parasitic capacities detune the oscillator circuit in the EVG UVT and can cause ignition problems 
and a deviant lamp current. 

Mains supply cabling 

The  mains  supply  cabling must  have  a  low  impedance  and  the  installation  of the  power  cable  has  to  be 
such that interferences by the emission of  lamp cables are minimized. Mains supply cables must be kept 
short  and  should  not  be  installed  parallel  to  the  lamp  cables  or  directly  along  the  ballast  housings. 
Intersections  with  lamp  cables  should  be  avoided  where  possible.  If  absolutely  necessary,  such  crossings 
shall be made in right angles and a certain distance. Unavoidable noise interferences must be filtered with 
appropriate measures. Basically, the interference avoidance is preferable to interference elimination. 

 

Содержание EVG UVT 2x 100-200 W

Страница 1: ...ik Speziallampen GmbH Gewerbegebiet Ost 6 98704 Wolfsberg Stand 07 07 2016 Operating Manual Electronic Power Supply EVG UVT 2x 100 200 W 1 2 2 1 A EVG UVT 2x 150 320 W 1 5 2 1 A EVG UVT 2x 150 320 W 1...

Страница 2: ...written permission of the UV Technik Speziallampen GmbH If any part of this user s manual is reproduced stored in a retrieval system or transmitted in any form or by any means without obtaining the p...

Страница 3: ...ty and liability 7 Organizational measures 7 Informal safety measures 8 Danger due to electricity 8 Service maintenance remedying faults 8 3 Transport storage delivery 9 4 Order data for equipment 9 E...

Страница 4: ...an immediately threatening danger If it is not avoided death or very severe injuries damage to health will result Damage to property is possible The signal word marks a danger with medium risk or dan...

Страница 5: ...e failure of one lamp do not provoke the breakdown of the second lamp The permanent operation with only one lamp must be avoided if the allowed minimal input power will be undercut The EVG UVT contain...

Страница 6: ...ons Appropriate use EVG UVT is a microprocessor based electronic power supply for UV low pressure lamps Any other use or use above and beyond these terms is defined as inappropriate and is thus danger...

Страница 7: ...ology The equipment may only be used under the following conditions it is used for the purpose for which it was constructed which the equipment complies with all safety technology requirements HAZARDO...

Страница 8: ...observed HAZARDOUS ELECTRICAL VOLTAGE There is a danger causes by direct or indirect contact with electricity The electrical components of the EVG UVT must be inspected regularly equipment components...

Страница 9: ...pment Order equipment from UV Technik Speziallampen GmbH Gewerbegebiet Ost 6 98704 Wolfsberg OT W mbach Tel 0049 36785 520 0 Fax 0049 36785 520 21 E Mail info uvtechnik com Equipment Description Artic...

Страница 10: ...normal operation on off on system lamp ballast ok start condition not fulfilled off steady blink steady blink ballast is waiting for start mains under or overvoltage start at over temperature no lamp...

Страница 11: ...ay contacts terminal 6 8 9 11 1 changer maximal load 5 A 250 V AC 5 A 24 V DC ohmic load recommended minimal load 12 V DC 10 mA remote input terminal 1 2 10 230 V AC DC galvanically isolated to be use...

Страница 12: ...igned for installation in electrical cabinets IP protection class IP20 size of housing w x d x h borehole spacing 240 mm 250 x 105 x 60 mm 2x 100 200W 250 x 150 x 60 mm 2x 150 320W mounting position v...

Страница 13: ...ndatory operating manual EVG UVT 200 480W subject to change without notice page 13 of 17 8 Technical documentation Terminal diagram Dimensional drawing depth EVG UVT 2x 100 200W 105 mm depth EVG UVT 2...

Страница 14: ...connections to the lamp may not be disconnected during operation By no means install additonal components into the lamp supply cable such as relays switches ignitors or capacitors The number of the cl...

Страница 15: ...omponent see chart We use only premium quality capacitors of the highest temperature stability In compliance with the installation instructions as well as the maximum housing temperature a lifetime of...

Страница 16: ...Besides the usual operation LEDs the EVG UVT are equipped with a potential free signal output per chanel lamp which notifies the proper function of the unit This output is a relay that switches once...

Страница 17: ...to check the complete system according to the relevant rules If several ballasts build in a unit generally additional measures can be necessary to eliminate interferences Beside the observance of the...

Отзывы: