manualshive.com logo in svg
background image

Lineman driven. Field proven.

U

TILITY

S

OLUTIONS

2

USJL-001 Manual Rev. 1.5 (3-6-14)

BEFORE Installing

Visually inspect the tool to verify that the protective cable is not cut or damaged.  

Prior to installation of the USJL-001 ensure that all four insulated handles 

are in the receiving position.  This means that the insulated handle has been 

unthreaded so that the copper attachment ferrule is just barely recessed inside 

the black insulated handle.  The ferrule should not protrude from the insulated 

handle. 

Also prior to installation ensure that the ferrule, when in the receiving position, 

has a wide enough attachment slot opening.  If necessary unthread the ferrule 

past the insulated handle and use a large flat head screwdriver to open the slot 

accordingly. 

Installation, Removal and Storage

1. 

Remove the Meter Enclosure Cover.

2. 

Push one end of a jumper lead ferrule over the load side bypass horn until 

fully seated. 

3. 

Turn the insulated handle clockwise until the jumper ferrule firmly clamps 

onto the bypass horn.

4. 

Push the corresponding jumper lead ferrule over the source side bypass 

horn until fully seated.  

5. 

Turn the insulated handle clockwise until the jumper ferrule firmly clamps 

onto the bypass horn.

6. 

Repeat the same process for the other side of the meter base 

with the remaining jumper lead.

7. 

Verify that the jumper leads are secure and will not interfere with 

the removal of the meter.

8. 

Remove the meter.

9. 

After the meter has been replaced remove the jumper leads 

one side at a time.  Unthread and remove the insulated handle 

attached to the load side first followed by the corresponding 

source side ferrule.  

10.  Repeat the same process for the other side of the meter base.    

Warranty

Utility Solutions, Inc. warrants the Electric Meter Jumper Lead Set for any defects in manufacturing 

for the period of one year. If the tool is returned within that time period, Utility Solutions, Inc. will 

replace the tool free of charge. 

!

!

DANGER

Contact with high voltage will cause death or 

grievous personal injury to the operator. Only 

use this device in conjunction with safe operating 

practices around energized lines and equipment.

!

!

WARNING

Only utilize this tool while wearing appropriate 

rated gloves and personal protective equipment.

Отзывы: