5
C-00829 USJJ-005 Manual Rev. 6.5 (8-15-14)
Installation for 38 kV Cutout ONLY
1. Grasp the top perpendicular ring of the Jack Jumper™ Cutout Bypass Tool with the
shotgun stick.
2. Extend the shotgun stick as needed and per its instruction.
3. Attach the upper attachment hook on an arcing horn between the fuse door and the
insulator. This can be done on either side of the cutout (Figure A).
4. Be sure the Jack Jumper™ Cutout Bypass Tool is secure and will not interfere with
removal of the fuse.
5. Release the top ring.
6. Grasp the bottom in-line ring of the Jack Jumper™ Cutout Bypass Tool with the
shotgun stick.
7. Gently pull to expand the spring and hook the bottom attachment hook on the fuse
door hinge casting (Figure B). The Jack Jumper™ Cutout Bypass Tool is now in place;
release it from the shotgun stick.
8. Open the fuse door and replace as necessary.
Arcing Horns
Fuse Door
Upper Attachment Point
Figure A
Lower Attachment Point
Figure B
Fuse