USBS Field Inspection (12-17-18)

Copyright © 2018 Utility Solutions, Inc.

UNLOCKED

LOCK

CLOSE

LOCK

OPEN

CLOSE

OPEN

FIELD INSPECTION PROCEDURE 

BREAK-SAFE

®

 Load Break & Pick-up Tool

!

!

DANGER

The Safety Lock does not RESET the tool. Refer to Inspection Procedure on reverse side and 

the Operation Manual for complete instructions on properly resetting the BREAK-SAFE™.

LOCKED

Conductor 

Hook

Load Pick-up Trigger

(located under Lock)

Conductor Bar

Load Break Ring 

(should rotate freely)

Internal 

Yellow Tube

Yellow 

Safety 

Lock

Brass 

Contacts

Floating Head

Duckbill Head

!

!

WARNING

Always remove the BREAK-SAFE

®

 from the circuit, or remove the jumper attached to 

the conductor bar, after each load break operation. 

The BREAK-SAFE

®

 is not rated insulation nor is it considered a “visible gap”.  