B-00125 USBS (1
st
Gen) Operation Manual
11
The BREAK-SAFE
®
when in the “OPEN POSITION” does not constitute being
rated insulation nor does it provide a visible gap. This is why the use of the
Utility Solutions “Jumper-T” (USJT-001) or equivalent as a parking stand is
suggested.
WARNING
!
!
9.
Insert the Safety Locking Pin into the hole labeled “LOCK CLOSED” and verify
the Safety Locking Pin secures the tool in the fully closed position. The Safety
Locking Pin secures the tool in the closed position and prevents an accidental
loadbreak operation.
10.
Following standard safety practices and procedures the permanent circuit
can now be cut and both ends isolated and insulated.
11.
Prior to performing the loadbreak operation remove the Safety Locking Pin
from the “LOCK CLOSED” position.
12.
With one steady motion, pull down firmly on the Load Break Ring using an
approved insulated hot stick until the tool locks in the open position. Do not
stop or hesitate while pulling.
13.
Insert the Safety Locking Pin into the hole labeled “LOCK OPEN” and verify
the Safety Locking Pin secures the tool in the fully open position.
The Safety Locking Pin secures the tool in the open position and prevents an
accidental load pickup operation.
If the Safety Locking Pin cannot be inserted into the “LOCK OPEN” hole it
alerts the operator the tool has not been fully extended in the open position.
If necessary pull down on the Black Pull Strap Assembly with enough force so
the Safety Locking Pin fully seats in a smooth and easy manner.
14.
Verify there is NO VOLTAGE AND/OR NO AMPERAGE present on the “LOAD
SIDE” prior to removing the jumper cable end attached to the “LOAD SIDE”
line.
15.
Place the unattached “LOAD SIDE” jumper cable end on an insulated Utility
Solutions “Jumper-T” (USJT-001) or equivalent device (FIGURE 2). This
separation constitutes a visible gap for safety.
16.
Following standard safety practices and procedures, work can be performed
on the de-energized line.