AC-PRO-II
®
Instruction Manual www.utilityrelay.com
Page 50
Ethernet
Workstation
Workstation
SUBSTATION #3
SUBSTATION #2
SUBSTATION #1
RS-485
Converter
RS-485
Converter
RS-485
Converter
Up to 32 trip units
can be daisychained
together.
Figure 24.1: Ethernet configuration
Ethernet
Workstation
Workstation
LCI
LCI
LCI
SUBSTATION #3
SUBSTATION #2
SUBSTATION #1
Up to 32 trip units
can be daisychained
together.
Figure 24.2: LCI Ethernet Configuration
24.5
Trip Unit Programming
AC-PRO-II trip unit has several programmable settings
related to communications. See Section 11.26 for
communications settings.
REPLY DELAY
The REPLY DELAY set point is the minimum delay between
the trip unit’s receipt of a MODBUS packet and its reply.
Adjusting it enables the trip unit to operate properly with
other manufacturers’ MODBUS RS-485 connections.
The factory default of this set point is 5 milliseconds.
The reply delay can be changed using the InfoPro-AC
software application.
24.6
Modbus Registers
The AC-PRO-II Modbus Register Map is available for
download at the following location:
http://www.utilityrelay.com/PDFs/Product_Manuals/I-AC2-
COMM.pdf