17
CONTROL PANEL - FACTORY MENU
In the configuration menu, the parame-
ters must be set for correct unit operation.
Compressors operation (only non-hydro-
nic version) summer mode: allows to
include / exclude compressors in summer
mode. Minute compressor delay: it inserts
a compressor ON delay time (only non
hydronic version).
Season change mode: defines the
season change mode according to the
modes shown in the image.
SetPoint Summer Air and SetPoint Winter
Air: s and the Season change mode is set
to 3 indicates the season change
temperature limits.
Probe offset: it allows to adjust the offset
of the probes: under the you
will have a positive correction of the
value of the probes, while under the
column - there will be a negative
correction of the value of the probes.
- Antifreeze set: set indicating the antifre-
eze value; below this value the machine
goes into antifreeze.
- Antifreeze differential: sets the value of
the antifreeze differential: if the value of
the probe is greater than the set +
antifreeze differential, the machine exits
the antifreeze state.
- Antifreeze Renewal Fan Reduction:
indicates the speed reduction of the
renewal fan in antifreeze (Value in
percent).
- Minutes Antifreeze speed reduction:
indicates the time limit in which the fan
speed will be reduced; if the antifreeze
condition does not return during this time
the machine will go into antifreeze off.
- Minutes Switch off Machine in antifree-
ze: time the machine remains in OFF from
antifreeze
- Time Dirty Filters: indicates the time limit
required to generate the alarm of dirty
filters (in tens of hours).
- Seconds Speed Change Delay: Indica-
tes the delay time in the speed change
of the intake fan when switching from
ventilation to dehumidification / integra-
tion.
Indicates the values of the 3 speeds in
fan mode of the intake fan. Values are in
percentage and can vary between 0
and 100%
Indicates the values of the 3 speeds in
fan mode of the intake fan. Values are in
percentage and can vary between 0
and 100%
Integration Speed Set: Indicates the
values of the 3 speeds in integration
mode of the intake fan. Values are in
percentage and can vary between 0
and 100%