background image

19

•DRAWINGS FOR ILLUSTRATION PURPOSES ONLY•

CAUTION

GASES THAT ARE DRIVEN BY FRESH COAL MUST BE
BURNED OR THEY WILL ACCUMULATE AND EXPLODE.
NEVER SMOTHER A FIRE WHEN ADDING FRESH COAL.

CAUTION

DO NOT OPERATE WITH THE FEED AND/OR ASH DOOR
OPEN. THIS FURNACE IS DESIGNED FOR THERMO-
STATIC OPERATION. OPERATION WITH ANY OF THESE
DOORS OPEN WILL OVERHEAT AND DAMAGE THE
FURNACE.

CAUTION

NEVER USE GASOLINE, GASOLINE-TYPE LANTERN
FUEL, KEROSENE, CHARCOAL LIGHTER FLUID, OR
FLAMMABLE LIQUIDS TO START OR "FRESHEN UP" A
FIRE IN THE FURNACE.

CAUTION

NEVER STORE FLAMMABLE LIQUIDS, ESPECIALLY
GASOLINE, IN THE VICINITY OF THE FURNACE.

OPERATING INSTRUCTIONS

The temperature in the plenum of the warm air furnace at
which the blower turns on or turns off is controlled by the
setting of the pointers in the blower limit control. These
pointers may be adjusted through their entire range of
settings to achieve the desired warm air output from the
furnace. (See Fig. 15)

1.

2.

3.

Move both pointers towards the right (counter clock-
wise) - this increases the temperature setting at which
the blower will turn on and off.
Move both pointers towards the left (clockwise) - this
decreases the temperature setting at which the blower
will turn on and off.
Move pointers away or apart from each other- this
increases the time that the blower will run on each
warm cycle.

FIG. 15

ADJUSTING BLOWER LIMIT CONTROL SETTINGS

BLOWER LIMIT

POINTER AND STOP

BLOWER FAN

"ON" POINTER

BLOWER FAN

"OFF" POINTER

COAL FUEL
Egg size (1-3/16" or larger) bituminous coal for residential
furnaces, or any of the specially packed fireplace coals can be
used.  Coal with a low ash content (2% to 6%) is recommended.
WOOD FUEL
Hardwood, 18" to 26" should be split and air dried (seasoned) for
6 months.
LIGHTING
1.
2.

3.
4.

Open the draft controls to "HIGH" for maximum draft.
Open the feed door and place paper and kindling on the grate
for starting the fire.
Light the fire and close the feed door.
Add wood or about 15 lbs. of coal (depending on which
model) after fire is burning briskly.
Set draft control for desired temperature.

ADDING FUEL
When starting a fire, add small amounts of fuel instead of adding
large quantities of fuel.  This will give more complete combus-
tion and less build-up of tars or soot in the chimney.

Set draft control to HIGH before opening feed door.
Wood fire
Add wood to a convenient level.
Coal Fire
Never smother the fire when adding coal (See Caution).
Gas accumulation and a mild smoky explosion will occur.
Add fresh kindling if the bed of coals has cooled.
Add up to 20 lbs. of coal per loading.  Never add coal above
the bottom of feed door opening.
Stir the coal and watch the fire.  Be sure the new coal is
burning briskly before you close the doors and turn the lower
the drat control setting down.

1.
2.

3.

a.

b.

c.

Shake grates vigorously 1/2" left to right to spill
ashes into the ash pan.  Do this at least once every
12 hours of operation.  Empty ash pan regularly.
Do not allow ashes to build-up to grate as grate will
warp and burnout, and you might spill the ashes
when removing the pan.
Dispose of hot ashes properly (See note 12 on
page 4).
Rotation of the handle (5 o'clock to 7 o'clock)
position will agitate coals and spill ashes into ash
pan.
It is advisable for you to get familiar with the shaker
grate operation before firing.

d.

e.

f.

Содержание Ashley 22AF

Страница 1: ...E OR TRAILER 851533A FOR INSTALLATION AS A CENTRAL FURNACE CERTIFIED UNDER ANSI UL 391 CAN CSA B366 1 M91 C R US Model 22AF OWNER SMANUAL SOLID FUEL WARM AIR FURNACE UNITED STATES STOVE COMPANY 227 Industrial Park Road P O Box 151 South Pittsburg TN 37380 423 837 2100 Keeping North America W Keeping North America W Keeping North America W Keeping North America W Keeping North America Warm Since 18...

Страница 2: ... or Existing Masonry Chimney SEE Page 8 Electrical Wiring 6 Draft Regulator 1 2 Conduit ConduitConnectors FurnaceCement ManufacturerRecommends Rutland Black Code 78 or Equivalent Plenum and Duct Work as Required CONGRATULATIONS You ve purchased one of America s Finest Wood and Coal Burning Furnaces By heating with wood and coal you re helping to CONSERVE AMERICA S ENERGY Wood is our Renewable Ener...

Страница 3: ...operly installed a house fire may result For your safety follow the in stallation directions Contact local building or fire officials about restrictions and installation in spection requirements in your area SAFETY NOTICE DANGER RISK OF FIRE OR EXPLOSION DO NOT burn garbage gasoline drain oil or other flammable liquids WARNING FIRE HAZARD DO NOT operate with fire draft exceeding 06 inches W C DO N...

Страница 4: ... CRACKING BUILD ONLY SMALL FIRES ON FIRST USE To prevent injury do not allow anyone to use this furnace who is unfamiliar with the correct operation of the furnace For further information on using your furnace safely obtain a copy of the National Fire Protection Association NFPA publication Chimney s Fireplaces and Solid Fuel Burning Appliances NFPA 211 The address of the NFPA is Batterymarch Park...

Страница 5: ... fired forced air upflow type central furnace or it may be installed as a central furnace CARING FOR PAINTED PARTS This furnace has a painted outside jacket which is durable but it will not stand rough handling or abuse When installing you furnace use care in handling Clean with soap and warm water when furnace is not hot DO NOT use any acids or scouring soap as these wear and dull the finish DISC...

Страница 6: ...6 DRAWINGS FOR ILLUSTRATION PURPOSES ONLY MODEL 22AF DIMENSIONS FIG 1 ...

Страница 7: ...mm Unit to backwall 30 760 mm Chimney connector pipe to sidewall 18 530 mm Chimney connector pipe to backwall 18 460 mm Hot air ducts to combustibles 2 50 mm NOTE Install only on a noncombustible floor REFER TO FIG 2 3 Place the furnace on a noncombustible floor Check figures 2 and 3 Be sure you have the clearances shown from the furnace and the connector pipe to combustible surfaces If you have a...

Страница 8: ...he flue liner to be sure it is safe to use Make repairs before attaching the furnace See Page 4 item 5 Look at Fig 4 The connector pipe and fittings you will need to connect directly to a masonry chimney are shown The chimney connection should be as short as possible If the connector pipe must go through a combustible wall before entering the masonry chimney consult a qualified mason or chimney de...

Страница 9: ...tal screws at each chimney pipe joint to make the piping rigid Thechimneyconnectormayincludeasec tionforabarometricdraftregulatorbetween the furnace and the chimney Fig 4 5 6 7 The barometric draft regulator must be installed in the same room same pressure zone as the furnace Installthebarometricdraftregulatorstrictly in accordance with the instructions that are providedwiththebarometricdraftregul...

Страница 10: ...himney connector can be connected to a masonry chimney by passing through a combustible wall NFPA Standard 211 allows the following wall pass through systems FIGURE 8 CONNECTION OF CHIMNEY CONNECTOR TO A MA SONRY CHIMNEY THROUGH A COMBUSTIBLE WALL MASONRY CHIMNEY CONSTRUCTED TO NFPA 211 AIRTIGHT CLEANOUT DOOR FLOOR PROTECTOR COMBUSTIBLE WALL TO HEATER CHIMNEY CONNECTOR CEILING SEE PARTS A B C D AN...

Страница 11: ...mney connector by means of sheet steel support plates on both ends of the chimney section The opening in the combustible wall shall be covered and the chimney section supported on both sides with sheet steel supports which are at least 24 gauge 0 024 in thickness The sheet steel supports shall be securely fastened to wall surfaces on all sides and shall be sized to fit and hold the chimney section...

Страница 12: ...NFPA 211 SHEET STEEL SUPPORTS 24 GAUGE MIN THICKNESS CHIMNEY FLUE MINIMUM CHIMNEY CLEARANCES FROM MASONRY TO SHEET STEEL SUPPORTS AND COMBUSTIBLES 2 IN CONNECTION OF CHIMNEY CONNECTOR TO A MASONRY CHIMNEY WHEN CHIMNEY CONNECTOR DOES NOT PASS THROUGH A COMBUSTIBLE WALL PART E Figure 8 In addition to the methods shown by A B C and D of Figure 8 a listed factory built wall pass through system may be ...

Страница 13: ...t using two 2 10 x 1 2 Tek screws Then Mount the bracket to the rear of the furnace with four 4 10 x 1 2 Tek screws Also Attach the Conduit from the Limit Control to the Junction Box 4 Installthefive 5 ClipNutstothebackofthefurnace InstalltheBlower 3 andBlowerGasket 4 tothefurnace using the 1 4 20 x 3 4 bolts provided in the parts bag Attach the remaining piece of Conduit from the junction box to ...

Страница 14: ... LOAD LIMIT LINE BREAK OFF JUMPER FOR LOW VOLTAGE FAN OFF INDICATOR FAN ON INDICATOR LIMIT INDICATOR Honeywell LIMIT SWITCH R1 R2 G W 110 VAC 60 HZ GROUND G B W ELECTRICAL JUNCTION BOX M1 M2 BLOWER MOTOR B WIRE NUTS IMPORTANT POWER SUPPLY WIRING MUST NOT BE LESS THAN 90 CENTIGRADE Fig 10 WIRECOLORCODE G GREEN GROUND B BLACK POWER SUPPLY W WHITE POWER SUPPLY R1 WHITE FAN CONTROL R2 BLACK FAN CONTRO...

Страница 15: ...ing Furnace as close as practical to the existing central hot air heating system maintainingclearancesasstatedonthelabellocatedon the side of the furnace c Clearances from combustible materials must be complied with as stated on the label below the fuel door Theinstallationmustbemadeonlyonanoncombustible floor d Installthesmokepipeconnectortothechimney with 26 gauge pipe and elbows to be purchased...

Страница 16: ...CTIONS Operation after loss of power Remove filter if provided Do not expect to keep home at normal temperatures Do not load fuel above bottom of feed door Set Fuel door and Ash door spin draft maximum closed per the factory installed stops 1 2 3 4 U S ONLY FIG 11 ...

Страница 17: ...17 DRAWINGS FOR ILLUSTRATION PURPOSES ONLY CENTRAL INSTALLATION U S CANADA FIGURE 12 ADD ON INSTALLATION U S ONLY FIGURE 13 ...

Страница 18: ...COMBINATION CONTROL LIMIT FAN JUMPER IN H H POWER SUPPLY GAS OIL ELECTRIC POWER SUPPLY JUNCTION BOX CENTRAL FURNACE BLOWER MOTOR WOOD FURNACE BLOWER MOTOR CAUTION DO NOT CONNECT PLENUM FAN CONTROL SWITCH ACROSS FURNACE LIMIT CONTROL This unit is certified for parallel installation with exitsting forced air gas or oil fired furnace U S Only ...

Страница 19: ...or residential furnaces or any of the specially packed fireplace coals can be used Coalwithalowashcontent 2 to6 isrecommended WOODFUEL Hardwood 18 to26 shouldbesplitandairdried seasoned for 6 months LIGHTING 1 2 3 4 Open the draft controls to HIGH for maximum draft Openthefeeddoorandplacepaperandkindlingonthegrate for starting the fire Light the fire and close the feed door Add wood or about 15 lb...

Страница 20: ...of the chimney should be at least 3 feet above the roof and be at least 2 feet higher than any point of the roof within 10 feet Fig 5 See page 28 for list of trouble shooting tips 4 5 6 A DRAFT READING OF 05 TO 06 W C IS SUGGESTED FOR PROPER BURNING OF THIS UNIT WHEN USING WOOD SERVICE HINTS Creosote and Soot Formation and Need for Removal When wood is burned slowly it produces tar and other organ...

Страница 21: ...21 DRAWINGS FOR ILLUSTRATION PURPOSES ONLY MODEL 22AF PARTS ...

Страница 22: ...uit Assembly 1 24 80131 4 x 4 Junction Box 1 N S 80231 JunctionBoxCover 1 25 68232 Blower Connection Conduit Assembly 1 26 80230 Blower Motor 1 20 hp 1 27 40256 Grate Frame 1 28 40257 Shaker Grate 1 29 40260 Shaker Handle 1 69355 FeedDoorAssembly OrderONLYiftheentireAssemblyisneeded 1 30 25105B Feed Door Painted 1 N S 88066 5 8 Rope Gasket 4 58 ft 31 83872 Door Pin 2 32 89354 Feed Door Handle 1 33...

Страница 23: ...23 DRAWINGS FOR ILLUSTRATION PURPOSES ONLY APPENDIX INSTALLATIONA NOTE ANTI BACKDRAFT FLAPPERS OR BAFFLE ARE REQUIRED FOR THIS INSTALLATION ...

Страница 24: ...24 DRAWINGS FOR ILLUSTRATION PURPOSES ONLY APPENDIX INSTALLATIONB NOTE ANTI BACKDRAFT FLAPPERS OR BAFFLE ARE REQUIRED FOR THIS INSTALLATION ...

Страница 25: ...25 DRAWINGS FOR ILLUSTRATION PURPOSES ONLY APPENDIX INSTALLATIONC NOTE ANTI BACKDRAFT FLAPPERS OR BAFFLE ARE REQUIRED FOR THIS INSTALLATION ...

Страница 26: ...26 DRAWINGS FOR ILLUSTRATION PURPOSES ONLY APPENDIX INSTALLATION D U S ONLY INSTALLATION E U S ONLY ...

Страница 27: ...27 DRAWINGS FOR ILLUSTRATION PURPOSES ONLY APPENDIX INSTALLATION F INSTALLATION G ...

Страница 28: ... a Burning green wood not seasoned or dry b Thermostat setting too low for type fuel a Insufficient draft b Smothering fire when adding fresh fuel a Open spin dampers b Clean chimney c Add raincap to chimney a Allow wood to season in a dry well ventilated area for six months b Set blower control to higher temperature See Page 19 c Set flue draft See Page 9 a Wire unit properly b Replace blower con...

Страница 29: ...29 DRAWINGS FOR ILLUSTRATION PURPOSES ONLY NOTES ...

Страница 30: ...30 DRAWINGS FOR ILLUSTRATION PURPOSES ONLY NOTES ...

Страница 31: ...White Oak 48 4100 9 Fair 28 6 Red Oak 46 3900 8 Fair 27 4 Beech 45 3800 7 Hard 26 8 Sugar Maple 44 3700 6 Fair 26 2 Black Oak 43 3700 6 Fair 25 6 Ash 42 3600 5 Well 25 0 Yellow Birch 40 3400 4 Hard 23 8 Red Maple 38 3200 3 Fair 22 6 Paper Birch 37 3100 3 Easy 22 1 Elm Sycamore 34 2900 2 Very Difficult 20 1 Red Spruce 29 1800 1 Easy 16 1 HEATING WITH WOOD ...

Страница 32: ...VE THE FULL MODEL NUMBER WHICH IS ON THE NAMEPLATE ATTACHED TO THE HEATER WHEN ORDERING REPAIR PARTS ALWAYS GIVE THE FOLLOWING INFORMATION AS SHOWN IN THIS LIST 1 THE PART NUMBER 2 THE PART DESCRIPTION 3 THE MODEL NUMBER 22AF 4 THE SERIAL NUMBER ____________________ HOW TO ORDER REPAIR PARTS UNITED STATES STOVE COMPANY 227 INDUSTRIAL PARK ROAD P O BOX 151 SOUTH PITTSBURG TN 37380 423 837 2100 WWW ...

Отзывы: