usi MCN108 Скачать руководство пользователя страница 13

Page 12

GAS

BLUE LED

AUDIBLE & VISUAL SIGNALS

POWER

GREEN LED

HORN

OPERATIONAL SUMMARY

CONDITION / RECOMMENDATION

Silent

Off

On and Blinks

Off approx

every 20

seconds

Off

Condition:

 AC power is present. DC power is present.

Recommendation:

 None

CO

RED LED

Silent

(alarmed

previously)

On and Blinks

Off approx

every 20

seconds

Off and Blinks

On approx.

every 5

seconds until 

reset

Silent

Off

Off and Blinks

On approx

every 40

seconds

Off

Condition:

 Alarm is powered by battery backup. AC Power is not  

present.

Recommendation:

 Check the breaker or fuse box for power. If the breaker 

or fuse box looks normal, call a licensed electrician for assistance.

4 Beeps,

5 second pause, 

1 beep

Blinks On in

sync with

the 1 beep

Turns off

when the

3 beeps start

Blinks On in sync 

with the cycle of

4 beeps and

turns off

Condition:

 The test/silence button has been pressed. The test sequence 

lasts for approx. 7 seconds.

Recommendation:

 None

Off

*See below

Off

Horn does not

sound when

other alarms

are active

or when 

interconnected

alarm’s

test/reset

button is

pressed

4 Beeps,

5 second pause, 

repeat

Off

Blinks On in

sync with

4 beeps

Condition:

 Originating CO Alarm.

Recommendation:

,IKD]DUGLVLGHQWL¿HGWDNHDOOSUHFDXWLRQVLIDQDODUP

sounds by calling an Emergency Service and getting out of the home.

4 Beeps,

5 second pause, 

repeat

Off

Turns off

when the

4 beeps start

Off

Condition:

1RQRULJLQDWLQJ&2$ODUP

Recommendation:

 An interconnected CO alarm has sensed CO, causing 

DOOLQWHUFRQQHFWHGXQLWVWRVRXQG,IKD]DUGLVLGHQWL¿HGWDNHDOOSUHFDXWLRQV

if an alarm sounds by calling an Emergency Service and getting out of 

the home.

Turns off

when the

4 beeps start

1 Beep,

2 second pause, 

repeat

Off

Blinks On

in sync

with the

1 beep

Condition:

 Originating GAS Alarm.

Recommendation:

,IKD]DUGLVLGHQWL¿HGWDNHDOOSUHFDXWLRQVLIDQDODUP

sounds by calling an Emergency Service and getting out of the home.

1 Beep,

2 second pause, 

repeat

Off

Turns off

when the

1 beeps starts

Off

Condition:

1RQRULJLQDWLQJ*$6$ODUP

Recommendation:

 An interconnected GAS alarm has sensed GAS, 

FDXVLQJDOOLQWHUFRQQHFWHGXQLWVWRVRXQG,IKD]DUGLVLGHQWL¿HGWDNHDOO

precautions if an alarm sounds by calling an Emergency Service and 

getting out of the home.

Turns off

when the

1 beeps starts

Off or Blinks

On in

sync with

the 1 beep

Condition:

 Nuisance Alarm.

Recommendation:

 If there is no hazard present, verify the alarm is 

mounted in the correct location (see User’s Manual). Reset alarm as 

instructed below.

Horn sounds

when no

hazard is

present

Off or Blinks

On in sync

with 4 beeps

Turns off

 when the

beeps start

4 Beeps,

5 second pause, 

repeat

Blinks

On in sync

with 4 beeps

Off

Turns off

 when the

4 beeps start

Condition:

 CO alarm when cause of alarm is known and poses no threat.

Recommendation:

 The CO alarm Silence Feature can be activated by pressing 

and releasing the Test/CO Silence button on the initiating alarm while in alarm 

condition. The alarm will remain silent for approx. 5 minutes (with the red LED 

blinking on approx. every 10 seconds), depending on the level of CO detected. 

If CO levels drop below alarm levels, the alarm will remain silent and return to 

normal operation. If CO levels remain constant or increase, this indicates a 

potentially dangerous situation and the horn will sound again. Ventilate area.

Off and

Blinks On

approx.

every 5

seconds

until reset

Condition:

 One or more alarms not responding to interconnected alarm.

Recommendation:

 Press and hold the alarm Test/Silence button for at least 

5 seconds. If still no alarm, turn off AC Power at the circuit breaker or fuse 

box and disconnect the alarm from the mounting bracket and make sure 

the connector plug is securely attached on units that did not alarm. If still no 

alarm, have a licensed electrician make sure the yellow wire is not mistakenly 

or accidentally connected to the white (neutral) wire.

Condition:

3UHYLRXVDODUPFRQGLWLRQDWXQLGHQWL¿HGVRXUFH

Recommendation:

48,&.),1'Š$ODUP2ULJLQDWLRQ,QDQLQWHUFRQQHFWHG

V\VWHPLWLVGLI¿FXOWWRGHWHUPLQHZKLFKDODUPLQLWLDWHGWKHDODUPVWRVRXQG

The QUICK FIND® feature will immediately allow you to locate the originating 

alarm (once the alarms have stopped sounding). To initiate QUICK FIND®,  

press and hold the test/silence button on any alarm until the test sequence 

RQWKLVDODUPEHJLQV5HOHDVHWKHWHVWEXWWRQ7KHVSHFL¿FKRUQSDWWHUQ

sequence is designated by the alarm type. Once this test sequence ends, 

the originating alarm continues to sound for approximately 60 seconds.

Page 13

GAS

BLUE LED

AUDIBLE & VISUAL SIGNALS

POWER

GREEN LED

HORN

OPERATIONAL SUMMARY

 (continued)

CONDITION / RECOMMENDATION

CO

RED LED

Silent

(alarmed

previously)

Off and Blinks

On approx

every 5

seconds

until reset

On and Blinks

Off approx

every 20

seconds

Off and Blinks

On approx

every 5

seconds

until reset

Condition:

 Alarm needs to be reset due to abnormal operation/previous 

alarms.

Recommendation:

 To reset the alarm, hold the Test/Silence button for 10 

seconds or until the blue LED turns on. This will clear the alarm origination 

and latching LEDs. Reset after each alarm event.

Horn has

stopped

sounding

Off

On and Blinks

Off approx

every 20

seconds

Condition:

 Latching CO LED indicator. The alarm has previously detected 

CO and had alarmed.

Recommendation:

 Follow the reset instructions to remove the latching 

LED.

Horn has

stopped

sounding

On and Blinks

Off approx

every 20

seconds

Off

Condition:

 Latching GAS LED indicator. The alarm has previously detected 

GAS and had alarmed.

Recommendation:

 Follow the reset instructions to remove the latching 

LED.

1 Chirp

approx.

every 40

seconds

Off

On and Blinks

Off approx

every 20

seconds

Off

Condition:

 Low battery.

Recommendation:

 Check to make sure a battery is present in the drawer, 

the battery activation pull tab has been completely removed, battery polarity 

is correct and the battery terminals are making contact with the smoke alarm 

contacts in the battery drawer. If chirp continues, replace the 9V battery (see 

User’s Manual for recommended battery types).

3 Chirps

approx.

every 20

seconds

Off

On and Blinks

Off approx

every 20

seconds

Off

Condition:

6HQVRU7URXEOH6HQVRU(QGRI/LIH$ODUP

Recommendation:

 Reset the alarm. If this does not clear the problem, 

replace alarm.

2 Chirps

approx.

every 20

seconds

Off

On and Blinks

Off approx

every 20

seconds

Off

Condition:

3URGXFW(QGRI6HUYLFH/LIH1RWL¿FDWLRQ

Recommendation:

 5HSODFH WKH DODUP LPPHGLDWHO\7KH SURGXFW HQGRI

VHUYLFHOLIHQRWL¿FDWLRQFDQEHWHPSRUDULO\VLOHQFHGIRUDKRXUSHULRGIRU

up to 20 days. After 20 days, the warning cannot be silenced. The alarm 

should be replaced immediately.

*  During 120 volt operation On and Blinks Off approx. every 20 seconds.

   During 9 volt (DC backup) operation, blinks On approx. every 40 seconds.

Off and Blinks

On approx

every 5

seconds

until reset

Off and Blinks

On approx

every 5

seconds

until reset

RESET INSTRUCTIONS:

 Press the Test/Silence button for 10 seconds, or until the blue LED turns on, and then release. This will clear the alarm 

latching LED’s and clear the alarm origination. Be sure to RESET alarms after each alarm event.

QUICK FIND® Alarm Origination/Location Feature

: The QUICK FIND® feature will allow you to immediately locate the originating alarm (the alarm 

that triggered the other alarms), once the alarms have stopped sounding.
3UHVVDQGKROGWKHWHVWVLOHQFHEXWWRQRQDQ\DODUPXQWLOWKHWHVWVHTXHQFHRQWKLVDODUPEHJLQV5HOHDVHWKHWHVWEXWWRQ7KHVSHFL¿FKRUQSDWWHUQ

sequence is designated by the alarm type.

2. Once this test sequence ends, the originating alarm continues to sound for approximately 60 seconds, which provides ample time to locate the 

originating alarm.

3. Remember to 

reset

 the 

originating alarm

 in order to clear the QUICK FIND® and return the system to normal operation.

NOTE:

,I\RXKDYHDQ\DGGLWLRQDOTXHVWLRQVDERXWWKHRSHUDWLRQRI\RXUDODUPSOHDVHFRQWDFWRXU&XVWRPHU6HUYLFH'HSDUWPHQWDW

and we will gladly assist you.

288-3508-07

©

2012 UNIVERSAL SECURITY INSTRUMENTS, INC., Rev. 07/2016 CD

Printed in China

SEVEN-YEAR LIMITED WARRANTY

MODELS MCN

108 and 

MCN

108L

86,(OHFWULF,QF8QLYHUVDO6HFXULW\,QVWUXPHQWV,QF³86,´ZDUUDQWVWKLVSURGXFWWREHIUHHIURP
defects in material and workmanship for a period of seven (7) years from the date of purchase. 
This warranty shall not apply to any batteries used in the product or to any damage which may be 
caused by such batteries. This warranty applies only to the original consumer purchaser and only 
to products used in normal residential use and service. If this product is found to be defective, 
USI’s only obligation, and your exclusive remedy, is the repair or replacement of the product, at 
USI’s discretion, provided  the product has not been damaged through misuse, abuse, accident, 
PRGL¿FDWLRQVDOWHUDWLRQQHJOHFWRUPLVKDQGOLQJ7KLV:DUUDQW\VKDOOQRWDSSO\WRDQ\SURGXFWZKLFK
LVIRXQGWRKDYHEHHQLPSURSHUO\LQVWDOOHGVHWXSRUXVHGLQDQ\ZD\QRWLQDFFRUGDQFHZLWKWKH
instructions supplied with the product.

ALARM RETURNS

For replacement of this alarm under the terms of this Warranty, contact Customer Service at 
'HSDUWPHQWDWH[WHQVLRQWRREWDLQWKHFXUUHQWSRVWDJHDQGKDQGOLQJIHHV86,
GRHVQRWZDUUDQWDQGVSHFL¿FDOO\GLVFODLPVDQ\ZDUUDQW\ZKHWKHUH[SUHVVRULPSOLHGRI¿WQHVVIRU
a particular purpose, other than the warranty contained herein. No implied warranty on this product, 
created by state law, shall extend beyond the term of this warranty unless such law otherwise 
SURYLGHV86,VSHFL¿FDOO\GLVFODLPVDQ\OLDELOLW\DQGVKDOOQRWEHOLDEOHIRUDQ\FRQVHTXHQWLDORU
incidental loss or damage, including, but not limited to, damages to any equipment with which this 
product is used. Some states do not allow the exclusion or limitation of incidental or consequential 
damages, so the above limitations or exclusions may not apply to you. No agent, representative, 
dealer, or employee of the company has the authority to increase or alter the obligations or terms 
RIWKLV:DUUDQW\7KLV:DUUDQW\JLYHV\RXVSHFL¿FOHJDOULJKWVDQG\RXPD\DOVRKDYHRWKHUULJKWV
which vary from state to state. This Warranty is only valid for merchandise purchased from outlets 
LQWKH8QLWHG6WDWHVDQG&DQDGD7KLVZDUUDQW\H[SLUHVXSRQSURGXFWHQGRIVHUYLFHOLIHVLJQDOO

LITHIUM BATTERY LIMITED WARRANTY

7KH8OWUDOLIHEDWWHU\PRGHOV89/-DQG89/-3DUHZDUUDQWHGE\8OWUDOLIH&RUSRUDWLRQLQWKLV
alarm ONLY and are not warranted in any other device.  Submit your warranty claim through the 
8OWUDOLIHZHEVLWHZZZXOWUDOLIHFRUSFRPRUFDOO

11407 Cronhill Drive, Suite A

Owings Mills, Maryland 21117 USA

Visit Us on the Web! 

www.USI Electric.com 

Содержание MCN108

Страница 1: ...L GAS ALARM WITH SILENCE FEATURE THANK YOU for purchasing this combination alarm This manual includes important information regarding where to install the alarm how to operate maintenance testing and...

Страница 2: ...ATELY 7 YEARS OF OPERATION FROM INITIAL POWER UP NOTE MANUFACTURER RECOMMENDS REPLACEMENT OF THIS ALARM 7 YEARS AFTER DATE OF INSTALLATION WHAT YOU SHOULD KNOW ABOUT NATURAL GAS Natural gas is a fossi...

Страница 3: ...be centrally located outside of each separate sleeping area in the immediate vicinity of the bedrooms Where bedrooms are separated and audibility of the alarm to occupants within the bedroom area cou...

Страница 4: ...HFWO QH W WR D IXHO EXUQLQJ VRXUFH Ventilate these areas as much as possible If you must install the alarm near a cooking or heating appliance install at least 5 feet 1 5m from appliance HVV WKDQ LQFK...

Страница 5: ...nting bracket from the back of the alarm by holding the mounting bracket and WZLVWLQJ WKH DODUP LQ WKH GLUHFWLRQ LQGLFDWHG E WKH 7 67 72 5 029 DUURZ RQ WKH VLGH RI the alarm base OPTIONAL TAMPER RESIS...

Страница 6: ...n silent Interconnected combination CO and natural gas alarms will only respond if a natural gas event initiated the alarm All other alarms remain silent Natural gas detection is only present in model...

Страница 7: ...he battery backup will not work unless a good battery is properly installed When the alarm utilizes battery backup power the natural gas sensor will operate the alarm and will sample less frequently t...

Страница 8: ...all electronic circuitry and horn are working If no alarm sounds the alarm may have a power supply failure Test the alarm weekly to assure proper operation ALARM ORIGINATION Patented Quick Find Alarm...

Страница 9: ...n condition press and hold the TEST SILENCE button on any alarm for at least 10 seconds or until the blue LED turns on and then release Reset after each alarm The reset feature will reset all intercon...

Страница 10: ...controlled labatory environment can produce an explosion and death NEVER use a gas UDQJH RU DQ RSHQ DPH RI DQ NLQG WR WHVW WKLV DODUP RX PLJKW DFFLGHQWDOO GDPDJH or set UH WR WKH DODUP RU WR RXU KRPH...

Страница 11: ...DQHRXV RSHUDWLRQ RI VHYHUDO IXHO EXUQLQJ DSSOLDQFHV FRPSHWLQJ IRU OLPLWHG LQWHUQDO DLU Vent pipe connections vibrating loose from clothes dryers furnaces or water heaters Obstructions in or unconventi...

Страница 12: ...ice and getting out of the home Turns off when the 1 beeps starts Off or Blinks On in sync with the 1 beep Condition Nuisance Alarm Recommendation If there is no hazard present verify the alarm is mou...

Страница 13: ...als are making contact with the smoke alarm contacts in the battery drawer If chirp continues replace the 9V battery see User s Manual for recommended battery types 3 Chirps approx every 20 seconds Of...

Страница 14: ...t PRGL FDWLRQV DOWHUDWLRQ QHJOHFW RU PLVKDQGOLQJ 7KLV DUUDQW VKDOO QRW DSSO WR DQ SURGXFW ZKLFK LV IRXQG WR KDYH EHHQ LPSURSHUO LQVWDOOHG VHW XS RU XVHG LQ DQ ZD QRW LQ DFFRUGDQFH ZLWK WKH instruction...

Отзывы: