UC1122 User Guide
22
If you select a "Lockout Time" of 10s, a "Continue Time" of 5s, and choose
, the statement will be triggered as soon as the value of the
selected analog input goes above 10, and remains above 10 for 5s. It will then start checking the
value of the selected analog input again after 10s and be triggered once more if the value of the
selected analog input is above 10 for 5s.
If the "Lockout Time" is 0, the statement will only be triggered once (will be triggered again when
the trigger condition has changed and becomes true again).
Note:
The threshold setting range is associated with ADC settings. If you have set up ADC settings,
then threshold setting range would be Osh to Osl. If you haven’t setup ADC settings, the
threshold setting range would be 4 to 20.
4.6.1.5 IF the Device Restarts
A command containing this IF condition will be triggered once the device has finished restarting.
4.6.2 Supported THEN Actions
4.6.2.1 THEN Change Output
A command containing this action will change the selected output according to specified actions.
The user can choose from the following actions:
•
Will be activated
•
Will be deactivated
•
Will follow the input: When the triggering condition is the input changes state, you can then
select change state as the action.