DS1058-007A
19
DIP switch A5 = OFF
Outputs OUT1÷OUT8
Free from potential
Positive polarisation
Negative polarisation
at rest
Closed contact
12 V
0 V
in alarm condition
Open contact
-
-
DIP switch A5 = ON
Outputs OUT1÷OUT8
Free from potential
Positive polarisation
Negative polarisation
at rest
Open contact
-
-
in alarm condition
Closed contact
12 V
0 V
Operating modes of output relays OUT1 ÷ OUT8
Relay operation mode
Subordinated to radio
module status
Operating mode
Enabled
(DIP switch B1 = OFF)
When radio module 1058/010 is armed, the output
follows associated detection device.
Detection device 1 open -> relay 1 armed
Detection device 1 closed -> relay 1 disarmed
Bistable
(DIP switch A4 = OFF)
Disabled
(DIP switch B1 = ON)
The output always follows associated detection
device.
Detection device 1 open -> relay 1 armed
Detection device 1 closed -> relay 1 disarmed
Enabled
(DIP switch B1 = OFF)
When radio module 1058/010 is armed, the output is
armed and remains armed for about 1 second at
every opening operation on associated detection
device.
Monostable
(DIP switch A4 = ON)
Disabled
(DIP switch B1 = ON)
The output is armed and remains armed for about 1
second at every opening operation on associated
detection device.
Tamper 1058/010 connection
Pins TMP are a support to radio module 1058/010 tamper connection and must be taken back to wired
anti-intrusion control panel.