Function Change and Motion
En
:
This is one of the most common sensor mode. The sensor mode works by comparing the controller’s set temp with the temp sensed at the position of
the present sensor (see Table #1)
(Ex: Set Temp > Present Temp: Output ON , Set Temp <Present Temp: Output Off)
Roles
Display
Basic Set
Scope of Set
Description
Classification of function
tn
SEN
SEN , TIMER
SEN (Sensor Motion mode) , TIMER(Time Motion mode)
Min Temp Set
-L
0
℃
-9
℃
~ not exceeding Max
Temp
Set the lowest Temp in the range of Temp Set
Max Temp Set
-H
60
℃
Over Min Temp ~80
℃
Set the highest Temp in the range of Temp Set
Temp Deviation Set
IF
2
℃
0
℃
~5
℃
ON/OFF motion from the deviation between Set Temp and present Temp
Output Delay Time
Ly
20 sec
01 sec ~ 60 sec
After output ON, work later as long as the delay time
Overheating Temp Set
Ht
60
℃
Over Max Temp ~ 80
℃
Error occurs when overheating sensor sensing temp exceeds the set temp (OPTION)
Correction Temp Set
ES
00
℃
-9
℃
~ 10
℃
Scope for correcting the actual temp deviation
Table #1 (Sensor Mode)
TIMER Functions
* Must disconnect the temp sensor for using timer functions (see Table #2).
Push
∨
and
∧
keys simultaneously for 3 sec, ‘tn' displays. Push
∧
key once again, the ‘EN’ displays. ‘EN’ as the mode by sensor is same to the present
mode. Push
∧
key once again, then ‘In’ displays. At this time push
∨
and
∧
keys simultaneously, then the present cycle value displays. For setting cycle,
use
∨
or
∧
key. After setting the cycle value, push
∨
and
∧
keys simultaneously, then ‘AU’ flickers, the cycle value is saved, and the present intensity
displays.
How to set (serviceman) = push
∨
and
∧
keys simultaneously– ‘tn’ displays on the screen- select ‘tin’ - push
∨
and
∧
keys simultaneously–Cycle value
d splays(Cycle) – select Cycle (basic 3 min)
- Set cycle value - push
∨
and
∧
keys simultaneously - ‘AU’ flickers – saved
* It is recommended for the end-user not to set.
How to use by the end-user = select the intensity to be used with
∨
and/or
∧
key (basic single-step)