Uponor Smatrix Base PRO Controller X-147 Modbus RTU interface l Installation manual l 27
Display name
Register
address
(decimal)
Function code
(Hex)
Type
Analogue/
Binary
Coding
Room floor max limit temperature
channel 9
40053
0x06
Write
Analogue
Signed 16 bit integer.
Range: min temperature or 20 - 35,
default: 26 °C (78.8 °F).
0x10
Write multiple
Room floor min limit temperature
channel 9
40054
0x06
Write
Analogue
Signed 16 bit integer.
Range: 10 - 30 or max temperature,
default: 20 °C (68 °F).
0x10
Write multiple
Room floor max limit temperature
channel 10
40055
0x06
Write
Analogue
Signed 16 bit integer.
Range: min temperature or 20 - 35,
default: 26 °C (78.8 °F).
0x10
Write multiple
Room floor min limit temperature
channel 10
40056
0x06
Write
Analogue
Signed 16 bit integer.
Range: 10 - 30 or max temperature,
default: 20 °C (68 °F).
0x10
Write multiple
Room floor max limit temperature
channel 11
40057
0x06
Write
Analogue
Signed 16 bit integer.
Range: min temperature or 20 - 35,
default: 26 °C (78.8 °F).
0x10
Write multiple
Room floor min limit temperature
channel 11
40058
0x06
Write
Analogue
Signed 16 bit integer.
Range: 10 - 30 or max temperature,
default: 20 °C (68 °F).
0x10
Write multiple
Room floor max limit temperature
channel 12
40059
0x06
Write
Analogue
Signed 16 bit integer.
Range: min temperature or 20 - 35,
default: 26 °C (78.8 °F).
0x10
Write multiple
Room floor min limit temperature
channel 12
40060
0x06
Write
Analogue
Signed 16 bit integer.
Range: 10 - 30 or max temperature,
default: 20 °C (68 °F).
0x10
Write multiple
Comfort setting channel 1
40061
0x03
Read
Analogue
Signed 16 bit integer.
Range: 0 = off, 5 - 12 = 5 - 12 %
default: 0.
0x06
Write
0x10
Write multiple
Comfort setting channel 2
40062
0x03
Read
Analogue
Signed 16 bit integer.
Range: 0 = off, 5 - 12 = 5 - 12 %
default: 0.
0x06
Write
0x10
Write multiple
Comfort setting channel 3
40063
0x03
Read
Analogue
Signed 16 bit integer.
Range: 0 = off, 5 - 12 = 5 - 12 %
default: 0.
0x06
Write
0x10
Write multiple
Comfort setting channel 4
40064
0x03
Read
Analogue
Signed 16 bit integer.
Range: 0 = off, 5 - 12 = 5 - 12 %
default: 0.
0x06
Write
0x10
Write multiple
Comfort setting channel 5
40065
0x03
Read
Analogue
Signed 16 bit integer.
Range: 0 = off, 5 - 12 = 5 - 12 %
default: 0.
0x06
Write
0x10
Write multiple
Comfort setting channel 6
40066
0x03
Read
Analogue
Signed 16 bit integer.
Range: 0 = off, 5 - 12 = 5 - 12 %
default: 0.
0x06
Write
0x10
Write multiple
Comfort setting channel 7
40067
0x03
Read
Analogue
Signed 16 bit integer.
Range: 0 = off, 5 - 12 = 5 - 12 %
default: 0.
0x06
Write
0x10
Write multiple
Comfort setting channel 8
40068
0x03
Read
Analogue
Signed 16 bit integer.
Range: 0 = off, 5 - 12 = 5 - 12 %
default: 0.
0x06
Write
0x10
Write multiple
Comfort setting channel 9
40069
0x03
Read
Analogue
Signed 16 bit integer.
Range: 0 = off, 5 - 12 = 5 - 12 %
default: 0.
0x06
Write
0x10
Write multiple
Comfort setting channel 10
40070
0x03
Read
Analogue
Signed 16 bit integer.
Range: 0 = off, 5 - 12 = 5 - 12 %
default: 0.
0x06
Write
0x10
Write multiple