20 l Uponor Smatrix Base PRO Controller X-147 Modbus RTU interface l Installation manual
Display name
Register
address
(decimal)
Function code
(Hex)
Type
Analogue/
Binary
Coding
Cooling not allowed channel 10
00013
0x01
Read
Binary
Unsigned.
0 = Cooling not allowed
1 = Cooling allowed (default)
0x05
Write
0x0F
Write multiple
Cooling not allowed channel 11
00014
0x01
Read
Binary
Unsigned.
0 = Cooling not allowed
1 = Cooling allowed (default)
0x05
Write
0x0F
Write multiple
Cooling not allowed channel 12
00015
0x01
Read
Binary
Unsigned.
0 = Cooling not allowed
1 = Cooling allowed (default)
0x05
Write
0x0F
Write multiple
Integrated heat pump defrost state*
00016
0x01
Read
Binary
Unsigned.
0 = Heat pump defrost off/stopped (default)
1 = Heat pump defrost started
0x05
Write
0x0F
Write multiple
* Requires
Heat Pump Integration via BMS to be activated in U_BMS.txt. It takes about 2 minutes for the actuators in the Base PRO system to be fully
opened.