Technical specifications
Operating voltage
24 VAC +/- 10% Class II
circuits only
Maximum load
1.3 Amps at 24VAC or equivalent
of 6 thermal valve actuators
Air display range
32
°
F to 95
°
F (0
°
C to 35
°
C)
Floor display range
32
°
F to 140
°
F (0
°
C to 60
°
C)
Air setting range
34
°
F to 86
°
F (1
°
C to 30
°
C)
68
°
F (20
°
C) default
Floor setting range
34
°
F to 95
°
F (1
°
C to 35
°
C)
68
°
F (20
°
C) default
Air maximum setting
Adjustable to 86
°
F (30
°
C)
Floor maximum setting
Adjustable to 95
°
F (35
°
C)
CAN ICES-3 (B)/NMB-3(B) compliance
This equipment has been tested and found to comply with the
limits for a Class B digital device, pursuant to Part 15 of the
FCC Rules. These limits are designed to provide reasonable
protection against harmful interference in a residential
installation. This equipment generates, uses, and can radiate
radio frequency energy and, if not installed in accordance
with the instructions, may cause harmful interference to
radio communications. However, there is no guarantee that
interference will not occur in a particular installation. If this
equipment does cause interference to radio or television
reception, which can be determined by turning the equipment
off and on, the user is encouraged to try and correct the
interference by one or more of the following measures:
• Reorient or relocate the receiving antenna
• Increase the separation between the equipment and receiver
• Connect the equipment to a different circuit from that to which
the receiver is connected
• Consult the dealer or an experienced radio/TVG technician
for help
Setpoint limits settings
Minimum range
38
°
F (3
°
C) to maximum limit setting
50
°
F (10
°
C) default
Maximum range
Minimum limit setting to 99
°
F (37
°
C)
86
°
F (30
°
C) default
Floor sensor
10K J curve, 250 ft. maximum with
18 AWG
Units
User-configurable Fahrenheit or Celsius
Memory
Permanent for all settings and modes
Resolution
1
°
F (0.5
°
C) displayed, 0.25
°
calculated
Temperature
ranges
Shipping and storage: 14
°
F to 158
°
F
(-10
°
C to 70
°
C)
Operation: 32
°
F to 104
°
F (0
°
C to 40
°
C)
Humidity
20 to 90% non-condensing
Size
5.39" (136.91mm) H x 3.22"
(81.79mm) W x 0.63" (16mm) D
Sensor temperature vs. resistance table
Temperature Resistance
°F
°C
Ω
-50
-46
490,813
-45
-43
405,710
-40
-40
336,606
-35
-37
280,279
-30
-34
234,196
-25
-32
196,358
-20
-29
165,180
-15
-26
139,402
-10
-23
118,018
-5
-21
100,221
0
-18
85,362
5
-15
72,918
10
-12
62,465
15
-9
53,658
20
-7
46,218
25
-4
39,913
30
-1
34,558
35
2
29,996
40
4
26,099
45
7
22,763
50
10
19,900
55
13
17,436
60
16
15,311
65
18
13,474
70
21
11,883
75
24
10,501
80
27
9,299
85
29
8,250
Temperature Resistance
°F
°C
Ω
90
32
7,334
95
35
6,532
100
38
5,828
105
41
5,210
110
43
4,665
115
46
4,184
120
49
3,760
125
52
3,383
130
54
3,050
135
57
2,754
140
60
2,490
145
63
2,255
150
66
2,045
155
68
1,857
160
71
1,689
165
74
1,538
170
77
1,403
175
79
1,281
180
82
1,172
185
85
1,073
190
88
983
195
91
903
200
93
829
205
96
763
210
99
703
215
102
648
220
104
598
225
107
553
Uponor, Inc.
5925 148th Street West
Apple Valley, MN 55124
USA
T 800.321.4739
F 952.891.2008
Uponor Ltd.
2000 Argentia Rd., Plaza 1, Ste. 200
Mississauga, ON L5N 1W1
CANADA
T 888.994.7726
F 800.638.9517
A3100101_heat-onlyTstatWtouchscreen_manual_0316, Copyright © 2016 Uponor. Printed in the United States. MKT10050-AA
uponorpro.com