Uponor Combi Port XS Скачать руководство пользователя страница 25

Cold water warming 45 K (10-55 °C)

40

35

30

25

20

15

10

5

0

5

10

15

20

25

W

Y

1200

1100

1000

900

800

700

600

500

400

300

200

100

0

5

10

15

20

25

DI0000161

V

Z

Y

60°C

65°C

70°C

75°C

80°C

85°C

X

Item

Description

V

Primary heating demand in litres/hour (l/h)

W

Return temperature °C

X

Primary heating supply temperatures

Y

Tapping capacity in litres/minute (l/min)

Z

Max range

Cold water warming 50 K (10-60°C)

40

35

30

25

20

15

10

5

0

5

10

15

20

25

W

Y

1200

1100

1000

900

800

700

600

500

400

300

200

100

0

5

10

15

20

25

DI0000162

V

Z

Y

65°C

70°C

75°C

80°C 85°C

X

Item

Description

V

Primary heating demand in litres/hour (l/h)

W

Return temperature °C

X

Primary heating supply temperatures

Y

Tapping capacity in litres/minute (l/min)

Z

Max range

Combi Port XS

  |  

Installation and operation manual

  | 

25

Содержание Combi Port XS

Страница 1: ...Combi Port XS EN Installation and operation manual SD0000126...

Страница 2: ...shing 9 5 5 Tightness testing 10 5 6 Commissioning and hand over 10 6 Operation 11 6 1 Cold water throttle disc 11 6 2 Strainer 11 6 3 Thermostatic temperature lead module TTV 11 6 4 Circulation pump...

Страница 3: ...pecified by Uponor is not connected to or used with non Uponor products parts or components except for those approved or specified by Uponor and does not show evidence of tampering mishandling insuffi...

Страница 4: ...flammable vapours or gases Uponor cannot accept any responsibility for damage or breakdown that can result from ignoring these instructions 2 2 Standards and regulations Note The installation must be...

Страница 5: ...for details of where and how they can take this item for environmentally safe recycling Business users should contact their supplier and check the terms and conditions of the purchase contract This p...

Страница 6: ...alve is controlling the process As more hot water is required as more the valve is opening the flow of the heating water through the heat exchanger This ensures a constant hot water temperature If no...

Страница 7: ...essure regulator optional L Zone valve for limiting heating flow to apartment M Sensor pocket heat meter N Heat meter distance piece O Strainer 3 4 Accessories Depending on customer requirement the ba...

Страница 8: ...ort or installation Check the nuts to ensure that they are properly tightened before the connection to avoid property damages Before installing the heat interface unit ensure that the primary pipes ar...

Страница 9: ...entation SD0000106 Connect the primary supply lines with the corresponding ball valves at the HIU 5 3 Electrical installation Warning Required electrical connections and installations commissioning an...

Страница 10: ...iately Minimum 2 hours According to local standards and regulations 5 6 Commissioning and hand over Caution Improper commissioning can lead to property damage Complete commissioning by following these...

Страница 11: ...e capillary pipe 6 mm Note A too high value can cause the heating water return temperature to rise Note A too low maintenance temperature setting can lead to longer waiting times when preparing domest...

Страница 12: ...70 C 35 40 45 50 55 60 65 70 Change default settings Caution Make sure not to bend or break the capillary line SI0000286 2 3 4 The thermostat is equipped with a pin that limits the temperature to 60 C...

Страница 13: ...for assembly in the line and protects other control valves such as the proportional volume control from the excessive differential pressure that otherwise could cause the fitting to overflow Descript...

Страница 14: ...are filled and pressurised The cold water supply for the apartment is provided via the central house connection and distribution line The heat interface unit is equipped with a central shut off ball v...

Страница 15: ...iter infinitely adjustable downwards 35 70 C limited to 60 C 6 Scale value 35 70 C 1 2 3 4 5 6 7 8 Hot water temperature 35 C 40 C 45 C 50 C 55 C 60 C 65 C 70 C TTV Thermostatic lead module TTV capill...

Страница 16: ...rmostatic hot water temperature limiter if installed is working and correctly set Proportional volume control does not switch over Replace the proportional volume controller Waiting time for hot water...

Страница 17: ...rically Radiator thermostatic valves or return screw connections closed Check the thermostatic valves and return screw connections on the radiators No hot water and no heating Ball valves closed Open...

Страница 18: ...495 mm 200 mm 501 mm 350 mm 198 mm Connection measurents w l l1 l2 l3 l4 l5 h1 ZD0000062 w2 w1 w3 h l l1 l2 l3 l4 l5 495 mm 303 mm 60 mm 94 mm 93 mm 95 mm w w1 w2 w3 h h1 501 mm 361 mm 401 mm 406 mm...

Страница 19: ...tial pressure regulator M Cold water meter distance piece N Heat meter distance piece O Sensor pocket heat meter P Strainer Q Swivel nut R Ball valve 9 3 Technical specifications Combi Port XS Value M...

Страница 20: ...differential pressure regulator kvs 1 46 H HIU without strainer kvs 1 70 Pressure losses including ball valve Additional pressure losses e g heatmeter with Qn 1 5 of approximately 0 05 bar and other...

Страница 21: ...ture C X Primary heating supply temperatures Y Tapping capacity in litres minute l min Z Max range Cold water warming 40 K 10 50 C 55 50 45 40 35 30 25 20 15 10 5 10 15 20 25 W Y 1200 1100 1000 900 80...

Страница 22: ...ng supply temperatures Y Tapping capacity in litres minute l min Z Max range Cold water warming 50 K 10 60 C 55 50 45 40 35 30 25 20 15 10 5 10 15 20 25 W X 1200 1100 1000 900 800 700 600 500 400 300...

Страница 23: ...al pressure regulator kvs 1 46 H HIU without strainer kvs 1 70 Pressure losses including ball valve Additional pressure losses e g heatmeter with Qn 1 5 of approximately 0 05 bar and other internal ex...

Страница 24: ...ture C X Primary heating supply temperatures Y Tapping capacity in litres minute l min Z Max range Cold water warming 40 K 10 50 C 40 35 30 25 20 15 10 5 0 5 10 15 20 25 W Y 1200 1100 1000 900 800 700...

Страница 25: ...ng supply temperatures Y Tapping capacity in litres minute l min Z Max range Cold water warming 50 K 10 60 C 40 35 30 25 20 15 10 5 0 5 10 15 20 25 W Y 1200 1100 1000 900 800 700 600 500 400 300 200 1...

Страница 26: ...al pressure regulator kvs 1 46 H HIU without strainer kvs 1 70 Pressure losses including ball valve Additional pressure losses e g heatmeter with Qn 1 5 of approximately 0 05 bar and other internal ex...

Страница 27: ...X Primary heating supply temperatures Y Tapping capacity in litres minute l min Z Max range Cold water warming 40 K 10 50 C 40 35 30 25 20 15 10 5 0 5 10 15 20 25 W Y 1200 1100 1000 900 800 700 600 5...

Страница 28: ...ng supply temperatures Y Tapping capacity in litres minute l min Z Max range Cold water warming 50 K 10 60 C 40 35 30 25 20 15 10 5 0 5 10 15 20 25 W Y 1200 1100 1000 900 800 700 600 500 400 300 200 1...

Страница 29: ...ermany 1120090 v1_04_2021_EN Production Uponor DCO Uponor reserves the right to make changes without prior notification to the specification of incorporated components in line with its policy of conti...

Отзывы: