![Uponor Combi Port XS Скачать руководство пользователя страница 15](http://html1.mh-extra.com/html/uponor/combi-port-xs/combi-port-xs_installation-and-operation-manual_1060960015.webp)
7.3 Setting log heat interface units
Date:
Setting log heat interface units
Site:
Type:
Serial no:
Component
Description
Setting
range
Factory
setting
Set
on
site
Set zone valve for
the flow rate
Setting value 1
2
3
4
5
6
7
8
9
1-9
continous
7
Kv value /
2 K P
deviation
0,05
0,09
0,14
0,20
0,26
0,32
0,49
0,57
0,67
TWB
The thermostatic hot water temperature limiter, infinitely adjustable downwards
35-70 °C
(limited to
60 °C)
6
Scale value 35-70 °C 1
2
3
4
5
6
7
8
Hot water
temperature
35 °C
40 °C
45 °C
50 °C
55 °C
60 °C
65 °C
70 °C
TTV
Thermostatic lead module (TTV), capillary 6 mm, Kvs 1,55
35-60 °C
45 °C
DRG
Differential pressure regulator the heating circuit
50-150 mbar 100 mbar
Other components/devices
Component
Description
Type
Comment
Heat exchanger
GBS 220H-16 Plates
GKE 228H-24 Plates
GKE 228H-40 Plates
Installer, signature:
Installer, in capital letters:
Service partner:
Combi Port XS
|
Installation and operation manual
|
15