68
Enter the “Unit” segment when on the “Main Menu”.
6 Main menu
2/5
6 Unit
1/6
Enter password
>
Inlet/ Outlet
>
Unit
>
Operation Modes
>
System Items
>
Time Program
>
Overview to Communication
>
Setting Points
>
Manufacturer’s Information
>
Operation Time
>
Alarm List
>
Enter the “Setting Points” when on “Unit”.
6 Unit
4/6
6 Setting Points
1/6
Inlet/ Outlet
>
Temperature Setting Points
>
Operation Modes
>
AHU Setting Points
>
Time Program
>
Stage 1 Setting Points
>
Setting Points
>
Stage 2 Setting Points
>
Operation Time
>
DX Stages
>
Alarm List
>
HP Stages
>
Enter “Temperature Setting Points” segment when on “Setting Points”. You may change the setting
points defined with “>” on the opened screen.
6 Temperature Setting Points
1/12
6 Temperature Setting Points
1/12
Eco. Cooling Temp. Setting Point 28 oC>
Blow Temperature Lower Limit
11 oC
Conf. Cooling Temp. Setting
Point
24 oC>
Cooling Blow Temperature
11 oC
Conf. Heating Temp. Setting
Point
20 oC>
Heating Blow Temperature
11 oC