ÜKYP/YP Automatic Fuel Loading, Central System Heating Boiler Usage and Maintenance Manual 

INTRODUCTION 

 

Thank you for choosing ÜNMAK ÜKYP/YP series central system, pellet fuel central 

system  central  heating  boiler.  ÜNMAK  UKYP/YP  series  boilers  are  designed  to 

burn wood pellets. 

Please  read  the  user  manual  carefully  before  installing  and  operating  your 

product  and  keep  it  for  the  duration  of  the  product's  use.  Do  not  touch  or 

interfere with any part of the product other than the places allowed in the user 

manual. 

The installation, maintenance and service of the boiler requires an expert technical team. 

This user manual and regulations should be taken into consideration for the installation of the boiler, 

the  selection  of  the  appropriate  place  for  the  installation,  the  installation  of  the  boiler  water 

installation and the design of the chimney. 

These boilers are only used for heating installations, they are not suitable for direct domestic water 

heating. However, it can produce domestic hot water with the help of a boiler or heat exchanger. The 

energy required for the domestic water will be taken from the boiler energy. 

ÜKYP/YP heating boilers convert the chemical energy of the pellet into heat energy by combustion and 

load  it  onto  the  water,  which  is  the  heating  fluid.  Excessive  fuel  accumulation  in  the  combustion 

chamber by entering more numbers than necessary for the feeding setting in the combustion pot will 

cause energy loss and it will take longer for the fuel to burn. 

Combustion circuit is performed by fan, feeding screw and system pump control are performed by the 

electronic control panel supplied with the boiler. 

UKYP/YP heating boilers can only burn pellet fuels. Since the powdered fuels will fly in the combustion 

chamber with the system fan, there will be no efficient combustion. Since powdered fuel will collect 

more moisture, it will even cause auger blockage in the feed auger. Depending on the calorific values 

of the fuels, the heat transferred from the boiler to the water may exceed the declared values. 

 

 

 

 

Your user manual should be read carefully and it should be kept for the life of the boiler 
along with the accompanying warranty certificate.
 
 

 

Содержание UKYP/YP 130

Страница 1: ...LET FIRING CENTRAL HEATING BOILER USER MANUAL NL SOY Yap Malzemeleri Sanayi ve Ticaret Ltd ti Pancar Organize Sanayi B lgesi 2 Etap No 2 Torbal IZMIR TURKEY Tel 90 444 35 32 Fax 90 232 469 2412 www un...

Страница 2: ...SITE 4 SAFETY WARNINGS 6 ELECTRICAL INSTALLATION INSTRUCTIONS 8 INFORMATION ABOUT COMBUSTION 10 BOILER FEATURES 12 RULES FOR HEATING INSTALLATION 14 CONTROL PANEL AND USER INTERFACE 18 START UP 20 FUE...

Страница 3: ...omestic hot water with the help of a boiler or heat exchanger The energy required for the domestic water will be taken from the boiler energy KYP YP heating boilers convert the chemical energy of the...

Страница 4: ...tands on its chassis care should be taken that the carrying rope does not damage the painted thin sheets of the boiler and the reducer fan group under the bunker It is convenient to lift the boiler fr...

Страница 5: ...ble solution The boiler room door must not open directly to the escape staircase or general use stairs and must necessarily open to a common hall or corridor It is recommended to have a threshold of a...

Страница 6: ...stones facilitates cleaning It is inconvenient to keep flammable combustible and easily flammable materials in the boiler room Installation site dimensions The boiler room should be in dimensions to...

Страница 7: ...ed Under no circumstances should more than one boiler be connected to the same chimney Cylindrical chimney can be passed through the chimney in the figure Smoke chimneys should not be placed on the ou...

Страница 8: ...water should not be added directly to the overheated boiler for cooling purposes This can cause noise in the installation excessively high thermal stresses in the boiler and thus permanent damage The...

Страница 9: ...ot dipped or c It should be done with solid copper rod electrodes Copper rod electrodes must be at least 1 5 m tall with a diameter of 16 mm or a length of at least 1 25 m with a diameter of 20 mm and...

Страница 10: ...P a g e 9 KYP YP Automatic Fuel Loading Central System Heating Boiler Usage and Maintenance Manual Electrical Wiring Diagram...

Страница 11: ...onstruction and connection of the chimneys are important in terms of high combustion efficiency low heating cost and protecting the environment In order for the combustion to be good the chimney must...

Страница 12: ...west level of the chimney there should be a cleaning cover made of all kinds of sealed steel The length of the flue gas pipe between the chimney and the boiler should not exceed one quarter of the chi...

Страница 13: ...tion Pot It is the place where the fuel mixes with the air and returns to the flame Fuel comes from inside the double walled structure and air comes from outside Ignition takes place from the ignition...

Страница 14: ...600x600 FUEL CAPACITY kg 200 280 330 WATER VOLUME lt 320 400 480 560 640 890 925 1240 1195 1505 1570 BOILER WEIGHT kg 805 920 1080 1155 1300 1755 1900 2130 2200 2505 2750 NECESSARY DRAFT mbar 0 30 0 3...

Страница 15: ...volume increases by 3 55 of its initial volume Expansion tanks are used to take this expansion depending on the temperature in the water Expansion tanks also fulfill the safety of the system that is...

Страница 16: ...umber of floors applied The floor numbers given in the table are accepted as the boiler and expansion tank in the basement BOILER POWER SAFETY VALVE DIAMETER NUMBER OF FLOOR kW inch 1 2 3 4 5 6 7 8 9...

Страница 17: ...tallation from rising above the atmospheric pressure The air in the system is evacuated by opening the vent pipes to the atmosphere from the expansion tank It is recommended to use separate expansion...

Страница 18: ...d be checked daily and when it falls below the minimum value water should be added to the installation Open expansion tank volumes that should be according to nmak boiler capacities are given in the t...

Страница 19: ...to turn the control panel on and off button It is used to enter a new value to the device It is used to increase or decrease the Fan Adjustment Temperature Adjustment Fuel Supply Fuel Standby values E...

Страница 20: ...s activated and deactivated with this button Fan On Off The fan of the boiler is activated and deactivated with this button Manual Fuel Supply It is used to manually manually load fuel into the boiler...

Страница 21: ...is not seen because the Gearbox On Off and Fan On Off buttons are not pressed and the boiler is operating Belli bir s re Red kt r On Off ve Fan On Off butonlar na bas lmazsa nce ate leme ve besleme ya...

Страница 22: ...should be according to the boiler capacity and fuel type Press the Fuel Feed button to adjust the amount of fuel to be given into the boiler After setting the required feed setting from the buttons p...

Страница 23: ...second figure As soon as you press the ENTER button the fan setting you have set will be memorized and the image on the screen will be as in the third figure Ignite the auxiliary materials you put in...

Страница 24: ...capacities will vary according to values such as the degree of insulation in the environment heated by the boiler chimney draft thermal comfort demand of the space fuel diameter lower heating value Pr...

Страница 25: ...If there is fuel dust or ashes collected between the fins of the fan it is necessary to clean it by blowing it without disturbing the fin structure of the fan or by holding a dryer Cleaning the boile...

Страница 26: ...ing of plastic derived fuels in the boiler Chimney not heated Increase the temperature setting from the control panel Never throw plastic derived waste into the boiler or fuel tank bunker Check that t...

Страница 27: ...f the control panel Activate the limit thermostat by pressing the red pin that comes out For boilers between KYP YP 130 250 as follows It is inside the control panel in boilers between 300 600 Fuel ex...