RECOMMENDED LOCATION OF ALARMS

•  Locate the first smoke alarm in the immediate area of the bedrooms. Try to protect the escape 

route as the bedrooms are usually farthest from an exit. If more than one sleeping area exists, 

locate additional smoke alarms in each sleeping area. If a hall is more than 40 feet (12 meters) 

long, install a smoke alarm at each end.

•  Locate additional smoke alarms to protect any stairway as stairways act like chimneys for smoke 

and heat.

•  Locate at least one smoke alarm on every floor level.

•  Locate a smoke alarm in any area where a smoker sleeps or where electrical appliances are 

operated in sleeping areas.

•  Smoke, heat and other combustion products rise to the ceiling and spread horizontally. Mounting 

the smoke alarm on the ceiling in the center of the room places it closest to all points in the room. 

Ceiling mounting is preferred in ordinary residential construction. However, in mobile homes, 

wall mounting on an inside partition is preferred to avoid the thermal barrier that may form at the 

ceiling.

•  When mounting smoke alarm on the ceiling, locate it a minimum of 4" (10cm) from a side wall 

or corner (see Diagram A).

•  When mounting smoke alarm on a wall, if local codes allow, use an inside wall with the top edge 

of the smoke alarm a minimum of 4" (10cm) and a maximum of 6" (15.2cm) below the ceiling/

wall intersections (See Diagram A).

Page 3

Sloped Ceilings (Peaked Ceilings):

Smoke alarms or smoke detectors mounted on a peaked ceiling shall be located within 36 in. (914 mm) 

horizontally of the peak, but not closer than 4 in. (102 mm) vertically to the peak.
Sloped Ceilings (Shed Ceilings):

Smoke alarms or smoke detectors mounted on a sloped ceiling having a rise greater than 1 ft. in 8 ft. (1 

m in 8 m) horizontally shall be located within 36 in. (914 mm) of the high side of the ceiling, but not closer 

than 4 in. (102 mm) from the adjoining wall surface.
Tray-Shaped Ceilings:

Smoke Alarms or smoke detectors shall be installed on the highest portion of the ceiling or on the sloped 

portion of the ceiling within 12 in. (305 mm) vertically down from the highest point.
Mobile Home Installation:

For  minimum  protection,  smoke  alarms    should  be  installed  in  compliance  with  H.U.D.  Manufactured 

Home Construction Safety Standards, Title 24 CFR, Section 3280.208 and Section 3282. For additional 

protection, see Single Story Residence smoke alarm requirements/recommendations for Existing Homes 

and New Construction Homes.
Note: For mobile homes built before 1978, install smoke alarms on inside walls between 4” and 12” from 

the ceiling (older mobile homes have little or no insulation in the ceiling). This is especially important if 

the ceiling is unusually hot or cold.
Install a smoke alarm inside each bedroom and in the hallway outside each separate sleeping area.

Existing Homes:

The NFPA requires a smoke alarm on every level and outside each sleeping area in existing construction. 

An existing household with one level and one sleeping area is required to have one smoke alarm.
New Construction Homes and Manufactured Homes:

The NFPA requires AC-powered, interconnected smoke alarms to be installed inside each bedroom, outside 

each bedroom area, and on every level of the home. They also require a minimum of two AC-powered, 

interconnected smoke alarms in any new construction home.

Ceiling

Acceptable

Top of detector

acceptable here

Sidewall

12 in.

(300 mm)

maximum

Note: Measurements shown are to 

the closest edge of the detector.

DIAGRAM A 

Содержание MP316S

Страница 1: ...y 8 Warranty Back Cover READ ALL INSTRUCTIONS THANK YOU for purchasing this smoke and fire alarm This tamper proof alarm does not require battery changes It has a permanent power sealed battery which will last for approximately 10 years This manual includes important information regarding where to install the alarm how to operate maintenance testing and product features It also includes tips and i...

Страница 2: ...their lives and properties l SMOKE ALARMS CANNOT DETECT FIRES IF THE SMOKE DOES NOT REACH THEM Smoke from fires may not reach the sensing chamber and set off the alarm One alarm should be installed inside each bedroom or sleeping area Do not obstruct airflow around the smoke alarm or place in areas of obstructed airflow l BEAWARE OF VARIOUS SITUATIONSAGAINST WHICH THE SMOKEALARM MAY NOT BE EFFECTI...

Страница 3: ... or smoke detectors mounted on a sloped ceiling having a rise greater than 1 ft in 8 ft 1 m in 8 m horizontally shall be located within 36 in 914 mm of the high side of the ceiling but not closer than 4 in 102 mm from the adjoining wall surface Tray Shaped Ceilings Smoke Alarms or smoke detectors shall be installed on the highest portion of the ceiling or on the sloped portion of the ceiling withi...

Страница 4: ... If the battery is dead the alarm cannot operate The sealed battery cannot be replaced Failure to properly install and activate this alarm will prevent proper operation of this alarm and will prevent its response to fire hazards Test the alarm following installation and weekly thereafter The built in test switch accurately tests the alarm operation as required by ANSI UL217 Standards for Safety If...

Страница 5: ...t button should sound the alarm immediately after it is pressed There are special conditions that when you press the Test Silence button you will experience a delay of approx 10 15 seconds before the alarm sounds This delay occurs if the Test Silence button is pressed during a self diagnostic period This may occur after initial power up Retest after 10 15 seconds ALARM ORIGINATION The QUICK FIND f...

Страница 6: ...g properly Clean this alarm at least once a month to remove dust dirt insects and debris Using a soft brush or wand attachment to a vacuum cleaner vacuum all sides and cover of smoke alarm Be sure all the vents are free of debris DO NOT use spray cleaning chemicals or insect sprays directly on or near the alarm DO NOT paint the alarm Doing so may permanently damage the alarm and interfere with ala...

Страница 7: ...ly approximately 3 4 turn 6 This will discharge the alarm battery and stop the alarm chirping after approximately one minute The alarm is now safe for disposal 7 The deactivation key cannot be removed and the alarm cannot be attached to the bracket 8 Be sure to install a new alarm Once this alarm has been deactivated The alarm cannot be reactivated The alarm cannot be reattached to the bracket The...

Страница 8: ...veryone is there o Call the fire department from your neighbor s home not from yours o Don t return to your home until fire officials say that it is all right to do so NATIONAL FIRE PROTECTION ASSOCIATION REQUIRED INFORMATION For your information the National Fire Alarm Code NFPA 72 reads as follows 11 5 1 Required Detection Where required by applicable laws codes or standards for a specific type ...

Страница 9: ...nditions previous alarms Low Battery 2 chirps approx every 60 seconds Deactivate alarm see User s Manual ALARM DEACTIVATION section Replace alarm immediately Blinks On once approx every 2 minutes Silent 3 Beeps 2 second pause Repeat Blinks On in sync with Horn If hazard is identified please take all precautions if an alarm sounds by calling an Emergency Service and getting out of the home 3 Beeps ...

Страница 10: ...t at 800 390 4321 extension 238 to obtain the current postage and handling fees USI does not warrant and specifically disclaims any warranty whether express or implied of fitness for a particular purpose other than the warranty contained herein No implied warranty on this product created by state law shall extend beyond the term of this warranty unless such law otherwise provides USI specifically ...

Отзывы: