background image

Uni-I/O™  

 

Unitronics 

 

 

Output LEDs 

Green / Red LEDs 

10 

Input LEDs 

Green / Red LEDs 

11 

Status LED 

Tricolor LED, Green/Red/Orange 

N

OTE

 

 

Refer to the module's specification sheet for LED indications. 

12 

Module door 

Shipped covered with protective tape to prevent the door from 

being scratched. Remove tape during installation. 

13 

Screw holes 

Enable panel-mounting; hole diameter: 4mm (0.15”). 

 

About the I/O Bus Connectors 

The I/O Bus connectors provide the physical and electrical connection points between 

modules. The connector is shipped covered by a protective cover, protecting the connector 

from debris, damage, and ESD. 
The I/O Bus - Left (#4 in diagram) can be connected to either a CPU-for-Panel, a  

Uni-COM™ Communication module, to another Uni-I/O™ module or to the End Unit of a 

Local Expansion Kit. 
The I/O Bus - Right (#6 in diagram) can be connected to another I/O module, or to the 

Base Unit of the Local Expansion Kit. 

Caution 

 

If the I/O module is located last in the configuration, and nothing is to be 

connected to it, do not remove its Bus Connector Cover. 

 

Installation 

 

 

 

 

Turn off system power before connecting or disconnecting any modules or devices. 

 

Use proper precautions to prevent Electro-Static Discharge (ESD). 

 

Installing a Uni-I/O™ Module onto a UniStream™ HMI Panel  

 

 

N

OTE

 

The DIN-rail type structure on the back of the panel provides the physical support for 

the Uni-I/O™ module. 

1.  Check the unit to which you will connect the Uni-I/O™ module to verify that its Bus 

Connector is not covered.  

If the Uni-I/O™ module is to be the last one in the configuration, do not remove the 

cover of its I/O Bus Connector - Right. 

2.  Open the door of the Uni-

I/O™ module and hold it as 

shown in the accompanying 

figure.  

3.  Use the upper and lower 

guide-tunnels (tongue & 

groove) to slide the Uni-

I/O™ module into place. 

4.  Verify that the DIN-rail clips 

located at the top and 

bottom of the Uni-I/O™ 

module have snapped onto 

the DIN-rail. 

 

 

 

  

Содержание Uni-I/O UIS-WCB1

Страница 1: ...ation for UIS WCB1 Uni I O module Technical specifications may be downloaded from the Unitronics website The UniStream platform comprises CPU controllers HMI panels and local I O modules that snap together to form an all in one Programmable Logic Controller PLC Install Uni I O modules Onto the back of any UniStream HMI Panel comprising a CPU for Panel Onto a DIN rail using a Local Expansion Kit Th...

Страница 2: ...dance with the standards and limitations given in the product s technical specification sheet Do not place in water or let water leak onto the unit Do not allow debris to fall inside the unit during installation Install at maximum distance from high voltage cables and power equipment Kit Contents 1 Uni I O module 4 I O terminal blocks 2 black and 2 gray Uni I O Diagram 1 DIN rail clips Provide phy...

Страница 3: ...O module or to the Base Unit of the Local Expansion Kit Caution If the I O module is located last in the configuration and nothing is to be connected to it do not remove its Bus Connector Cover Installation Turn off system power before connecting or disconnecting any modules or devices Use proper precautions to prevent Electro Static Discharge ESD Installing a Uni I O Module onto a UniStream HMI P...

Страница 4: ...i I O modules onto a DIN rail To mount modules onto a DIN rail follow steps 1 7 in Installing a Uni I O Module onto a UniStream HMI Panel on page 3 In order to connect the modules to a UniStream controller you must use a Local Expansion Kit These kits are available with and without power supplies and with cables of varying lengths For complete information please refer to the installation guide of ...

Страница 5: ...ce from high voltage cables and power equipment Wiring Procedure Use crimp terminals for wiring use 26 12 AWG wire 0 13 mm2 3 31 mm2 1 Strip the wire to a length of 7 0 5mm 0 250 0 300 inches 2 Unscrew the terminal to its widest position before inserting a wire 3 Insert the wire completely into the terminal to ensure a proper connection 4 Tighten enough to keep the wire from pulling free UIS WCB1 ...

Страница 6: ...rth of the system Earthing the cables shield Connect the cable shield to the earth of the system preferably to the metal cabinet chassis Note that the shield must be connected only at one end of the cable typically earthing the shield at the UIS WCB1 end performs better Keep shield connections as short as possible Ensure shield continuity when extending shielded cables NOTE For detailed informatio...

Страница 7: ...nected Note that in this configuration the direction pin cannot be used as normal input Input wiring sink Input wiring source High Speed Input wiring sink High Speed Input wiring source Wiring the Analog Inputs Both inputs share the common point CM0 NOTE Each input offers two modes voltage or current You can set each input independently The mode is determined both by wiring and by the hardware con...

Страница 8: ...UIS WCB1 Installation Guide 8 Unitronics Voltage Differential Single ended Current 2 wire 3 wire 4 wire ...

Страница 9: ...temperature inputs isolation may be bypassed when using an exposed junction non isolated thermocouple in conjunction with analog inputs or another exposed junction thermocouple which can lead to flow of unwanted currents through the thermocouple wires that might interfere with thermocouple voltage reading In order to maintain temperature inputs isolation when using one or more of the analog inputs...

Страница 10: ...current limiting device in series with the relay contacts All 8 relay outputs share the common point CM5 Increasing contact life span To increase the life span of the relay contacts and protect the module from potential damage by reverse EMF connect a clamping diode in parallel with each inductive DC load an RC snubber circuit in parallel with each inductive AC load DC Load AC Load ...

Страница 11: ...mage the module Normal Transistor Output High Speed PWM Output Wiring the Analog Outputs NOTE The outputs are not isolated Each output offers two modes voltage or current You can set each output independently The mode is determined both by wiring and by the hardware configuration within the software application Voltage and current modes use distinct points Connect only the point associated with th...

Страница 12: ...uding but not limited to any impliedwarranties of merchantability fitness for aparticular purpose or non infringement Unitronicsassumes no responsibility for errors or omissions in the information presented in this document In no event shallUnitronics be liable for any special incidental indirect orconsequential damages of anykind oranydamages whatsoever arising outof or in connection with theuse ...

Отзывы: