background image

05/16 

 

 

 

 

Unitronics 

 

Add-on modules- 

 

Available by separate order for 
communication and cloning. 

Integral USB Port  

This may be used for 
programming purposes. 

Note:

 the USB port and an Add-on module cannot be physically connected at the same time. 

Add-on: during installation 

Add-on: after installation 

USB Port 

Installing an Add-on module requires sufficient clearance space 

 

72 mm (2.835")

 

27.5 mm
(1.083")

3

8

 m

m

(1

.4

9

6

")

3

5

.8

 m

m

(1

.4

0

9

")

 

 

  

DIN-rail mounting 

Snap PLC onto the DIN rail

 

Panel mounting 

Cut-out: 117 x 89mm 
(WxH)

(4.606”x 3.504”) 

 

 

 

Notes

: Removing the unit requires clearance space. Recommendation: 

approximately 40mm (1.58”) 

  For UL listed module, in order to meet the UL508 standard, panel-mount this device on  
  the flat surface of a Type 1 enclosure. 

Wiring 

 

  This equipment is designed to operate only in SELV/PELV/Class 2/Limited Power 

environments. 

  All power supplies in the system must include double insulation. Power supply outputs 

must be rated as SELV/PELV/Class 2/Limited Power. 

 

Do not connect either the ‘Neutral or ‘Line’ signal of the 110/220VAC to device’s 0V pin. 

  Do not touch live wires. 

 

  All wiring activities should be performed while power is OFF. 

  Install an external circuit breaker. Guard against short-circuiting in external wiring. 

  Use appropriate circuit protection devices. 

  Unused pins should not be connected.  Ignoring this directive may damage the device. 

  Double-check all wiring before turning on the power supply. 

Caution

 

  To avoid damaging the wire, use a maximum torque of 0.5 N·m (5 kgf·cm). 

  Do not use tin, solder, or any substance on stripped wire that might cause the wire 

strand to break. 

  Install at maximum distance from high-voltage cables and power equipment. 

       

       

       

Содержание Jazz JZ20-J-UN20

Страница 1: ...ations Only qualified service personnel should open this device or carry out repairs Failure to comply with appropriate safety guidelines can cause severe injury or property damage Do not attempt to use this device with parameters that exceed permissible levels To avoid damaging the system do not connect disconnect the device when power is on Environmental Considerations Do not install in areas wi...

Страница 2: ...ure Wiring This equipment is designed to operate only in SELV PELV Class 2 Limited Power environments All power supplies in the system must include double insulation Power supply outputs must be rated as SELV PELV Class 2 Limited Power Do not connect either the Neutral or Line signal of the 110 220VAC to device s 0V pin Do not touch live wires All wiring activities should be performed while power ...

Страница 3: ...and noise interference with input lines used over an extended distance Use wire that is properly sized for the load Earthing the product To maximize system performance avoid electromagnetic interference as follows Use a metal cabinet Connect the 0V terminal directly to the earth ground of the system Use the shortest less than 1m 3 3 ft and thickest 2 08mm 14AWG min wires possible Inputs This model...

Страница 4: ...In either case the npn pnp pins must be connected Input wiring npn sink Input wiring pnp source Input wiring I0 I8 pnp source I9 I10 npn sink Analog Inputs Note Shields should be connected at the signal source Analog Input wiring current 2 wire AN1 Analog Input wiring current 3 wire AN1 Analog Input wiring current 4 wire AN1 Analog Input wiring voltage AN2 and AN3 ...

Страница 5: ...C 328 to 1400 F White Red Yellow Blue K 200 to 1250 C 328 to 2282 F Yellow Red Brown Blue N 200 to 1300 C 328 to 3214 F Orange Red Orange Blue R 0 to 1768 C 32 to 3214 F Black Red White Blue S 0 to 1768 C 32 to 3214 F Black Red White Blue T 200 to 400 C 328 to 752 F Blue Red White Blue Thermocouple 0 use T Input as negative input and T as positive RTD PT100 Sensor 0 use both inputs related to CM s...

Страница 6: ...arily withdraw any of the forgoing from the market All information in this document is provided as is without warranty of any kind either expressed or implied including but not limited to any implied warranties of merchantability fitness for a particular purpose or non infringement Unitronics assumes no responsibility for errors or omissions in the information presented in this document In no even...

Отзывы: