background image

01/16 

 

 

 

 

Unitronics 

 

Add-on modules- 

 

Available by separate order for 
communication and cloning. 

Integral USB Port  

This may be used for 
programming purposes. 

Note:

 the USB port and an Add-on module cannot be physically connected at the same time. 

Add-on: during installation 

Add-on: after installation 

USB Port 

Installing an Add-on module requires sufficient clearance space 

 

72 mm (2.835")

 

27.5 mm
(1.083")

3

8

 m

m

(1

.4

9

6

")

3

5

.8

 m

m

(1

.4

0

9

")

 

 

  

DIN-rail mounting 

Snap PLC onto the DIN rail

 

Panel mounting 

Cut-out: 117 x 89mm 
(WxH)

(4.606”x 3.504”) 

 

 

 

Notes

: Removing the unit requires clearance space. Recommendation: 

approximately 40mm (1.58”) 

  For UL listed module, in order to meet the UL508 standard, panel-mount this device on  
  the flat surface of a Type 1 enclosure. 

Wiring 

 

  This equipment is designed to operate only in SELV/PELV/Class 2/Limited Power 

environments. 

  All power supplies in the system must include double insulation. Power supply outputs 

must be rated as SELV/PELV/Class 2/Limited Power. 

  Do not 

connect either the ‘Neutral or ‘Line’ signal of the 110/220VAC to device’s 0V pin. 

  Do not touch live wires. 

 

  All wiring activities should be performed while power is OFF. 

  Install an external circuit breaker. Guard against short-circuiting in external wiring. 

  Use appropriate circuit protection devices. 

  Unused pins should not be connected.  Ignoring this directive may damage the device. 

  Double-check all wiring before turning on the power supply. 

Caution

 

  To avoid damaging the wire, use a maximum torque of 0.5 N·m (5 kgf·cm). 

  Do not use tin, solder, or any substance on stripped wire that might cause the wire 

strand to break. 

  Install at maximum distance from high-voltage cables and power equipment. 

       

       

       

Содержание Jazz JZ20-J-R16HS

Страница 1: ...ples Please dispose of this product according to local and national standards and regulations Only qualified service personnel should open this device or carry out repairs Failure to comply with appropriate safety guidelines can cause severe injury or property damage Do not attempt to use this device with parameters that exceed permissible levels To avoid damaging the system do not connect disconn...

Страница 2: ...ure Wiring This equipment is designed to operate only in SELV PELV Class 2 Limited Power environments All power supplies in the system must include double insulation Power supply outputs must be rated as SELV PELV Class 2 Limited Power Do not connect either the Neutral or Line signal of the 110 220VAC to device s 0V pin Do not touch live wires All wiring activities should be performed while power ...

Страница 3: ...est less than 1m 3 3 ft and thickest 2 08mm 14AWG min wires possible Inputs 1 All the products comprise I0 I5 these digital inputs are arranged in a single group Via wiring the entire group may be set to either pnp or npn 2 The following information concerns JZ20 R10 JZ20 J R10 and JZ20 R16 JZ20 J R16 I0 and I1 can function as high speed counters or as normal digital inputs 3 The following informa...

Страница 4: ...pnp or wire both groups as npn or as pnp In either case the n p pins must be connected Input wiring I0 I5 npn sink Input wiring I0 I5 pnp source Input wiring I6 I7 npn sink Input wiring I6 I7 pnp source JZ20 J R16HS Note The inputs are arranged in two groups You can wire one group as npn and the other as pnp or wire both groups as npn or as pnp In either case the n p pins must be connected Input w...

Страница 5: ... npn sink Input wiring I6 I7 pnp source HSC input wiring npn sink HSC input wiring pnp source Shaft encoder wiring npn sink Shaft encoder wiring pnp source Digital Outputs JZ20 R10 JZ20 J R10 JZ20 R16 JZ20 J R16 JZ20 J R16HS Output wiring ...

Страница 6: ...without notice to discontinue or change the features designs materials and other specifications of its products and to either permanently or temporarily withdraw any of the forgoing from the market All information in this document is provided as is without warranty of any kind either expressed or implied including but not limited to any implied warranties of merchantability fitness for a particula...

Отзывы: