Connecting Expansion Modules 

An adapter provides the interface between the OPLC and an expansion module. To connect the I/O module to 
the adapter or to another module: 
1. 

Push the module-to-module connector into the port located on the right side of the device. 

Note that there is a protective cap provided with the adapter.  This cap covers the port of the 

final 

 I/O module in the system. 

 

 

To avoid damaging the system, do not connect or disconnect the device when the  
power is on. 

 

Component identification 

1 Module-to-module 

connector 

2 Protective 

cap 

 

 

1

2

 

 

Wiring 

 

 

 

Do not touch live wires. 

 

 

Unused pins should not be connected.  Ignoring this directive may damage the device. 

 

Do not connect the ‘Neutral or ‘Line’ signal of the 110/220VAC to the device’s COM pins. 

 

Double-check all wiring before turning on the power supply. 

 

Wiring Procedures 

Use crimp terminals for wiring; use 26-12 AWG wire (0.13 mm 

2

–3.31 mm

2

) for all wiring purposes. 

1. 

Strip the wire to a length of 7±0.5mm (0.250–0.300 inches).  

2. 

Unscrew the terminal to its widest position before inserting a wire.  

3. 

Insert the wire completely into the terminal to ensure that a proper connection can be made. 

4. 

Tighten enough to keep the wire from pulling free.  

 

To avoid damaging the wire, do not exceed a maximum torque of 0.5 N·m (5 kgf·m). 

 

Do not use tin, solder, or any other substance on stripped wire that might cause the wire strand to break. 

 

Install at maximum distance from high-voltage cables and power equipment. 

I/O Wiring—General 

 

Input or output cables should not be run through the same multi-core cable or share the same wire. 

 

Allow for voltage drop and noise interference with input lines used over an extended distance.  Use wire 
that is properly sized for the load.  

 

Unitronics Industrial Automation 

 

Содержание IO-ATC8

Страница 1: ...d on these examples Please dispose of this product in accordance with local and national standards and regulations Only qualified service personnel should open this device or carry out repairs User safety and equipment protection guidelines This document is intended to aid trained and competent personnel in the installation of this equipment as defined by the European directives for machinery low ...

Страница 2: ...gas moisture or rain excessive heat regular impact shocks or excessive vibration Leave a minimum of 10mm space for ventilation between the top and bottom edges of the device and the enclosure walls Do not place in water or let water leak onto the unit Do not allow debris to fall inside the unit during installation Mounting the Module DIN rail mounting Snap the device onto the DIN rail as shown bel...

Страница 3: ...ng The figure below is not drawn to scale It may be used as a guide for screw mounting the module Mounting screw type either M3 or NC6 32 4mm 5 8mm 0 228 85mm 3 346 80mm 3 15 68 4mm 2 693 93mm 3 66 4mm x2 0 16 0 16 Unitronics Industrial Automation 3 ...

Страница 4: ...le check all wiring before turning on the power supply Wiring Procedures Use crimp terminals for wiring use 26 12 AWG wire 0 13 mm 2 3 31 mm 2 for all wiring purposes 1 Strip the wire to a length of 7 0 5mm 0 250 0 300 inches 2 Unscrew the terminal to its widest position before inserting a wire 3 Insert the wire completely into the terminal to ensure that a proper connection can be made 4 Tighten ...

Страница 5: ...se the appropriate wiring as shown below Open the device and set the jumpers according to the instructions beginning on page 6 The adapter and the COM signals of the analog inputs must be connected to the same 0V signal The COM signals of each channel are internally shorted When set to current voltage each 2 inputs share a common COM signal Unitronics Industrial Automation 5 ...

Страница 6: ...f a specific input first open the device by prying off its back using the blade of a flat bladed screwdriver The insertion points for the screwdriver are located on both sides of the module 1 Open the first side of the device by inserting the blade between the 2 plastic moldings as shown below then gently pushing up 2 Taking care not to damage the cable open the other side of the device by inserti...

Страница 7: ...pansion Module 3 Gently remove the top of the device as shown 4 The jumpers are shown at right Change the jumper settings as required in accordance with the tables shown on the next page Unitronics Industrial Automation 7 ...

Страница 8: ... instructions beginning on page 6 Caution Incompatible jumper settings and wiring may severely damage the device Jumper Thermocouple Voltage Current 1 B A A Input 0 2 B A B 3 B A A Input 1 4 B A B 5 B A A Input 2 6 B A B 7 B A A Input 3 8 B A B 9 B A A Input 4 10 B A B 11 B A A Input 5 12 B A B 13 B A A Input 6 14 B A B 15 B A A Input 7 16 B A B Default factory setting 8 Unitronics Industrial Auto...

Страница 9: ...tomatic Cold junction compensation error 1 5ºC 2 7ºF maximum Absolute maximum rating 0 6VDC Linearity error 0 04 maximum of full scale Error limit 0 4 of input value Warm up time Typically hour 1ºC 1 8ºF repeatability Status indicators OUT OF RANGE Red LEDs Lit when the corresponding input measures an analog value in excess of the input range See Note 4 Thermocouple input ranges Type Temperature r...

Страница 10: ... Relative Humidity RH 5 to 95 non condensing Dimensions WxHxD 80mm x 93mm x 60mm 3 15 x 3 66 x 2 362 Weight 150g 5 3 oz Mounting Either onto a 35mm DIN rail or screw mounted Notes 1 Each input may be set as either thermocouple voltage 0 10V or current 0 20mA 4 20mA via wiring jumper and software settings 2 The device can also measure voltage within the range of 5 to 56mV at a resolution of 0 01mV ...

Страница 11: ...ormula below is used to assign addresses for I O modules used in conjunction with the OPLC X is the number representing a specific module s location 0 7 Y is the number of the input or output on that specific module 0 15 The number that represents the I O s location is equal to 32 x 16 y Examples Input 3 located on expansion module 2 in the system will be addressed as I 67 67 32 2 16 3 Output 4 lo...

Страница 12: ...in this document including but not limited to 0implied warranties of merchantability and or fitness for a particular use or purpose Unitronics assumes no responsibility for the results direct and or indirect of any misuse of the information appearing in this document nor for any use of the Unitronics products referred to herein in any manner deviating from the recommendations made in this document...

Отзывы: