IO-ATC8
I / O E x p a n s i o n M o d u l e
12/03
Analog Inputs
Number of inputs
8 (single-ended) See Note 1.
Input range
0-10V, 0-20mA, 4-20mA. See Note 1.
Input type
Either Normal or Fast mode, according to the filter type selected in software
settings
Conversion method
Voltage to frequency
Normal mode
Resolution at 0-10V,
0-20mA
14-bit (16384 units)
Resolution at 4-20mA
3277 to16383 (13107 units)
Conversion time
100mSec minimum per input
Fast mode
Resolution at 0-10V,
0-20mA
12-bit (4096 units)
Resolution at 4-20mA
819 to 4095 (3277 units)
Conversion time
25mSec minimum per input
Input impedance
>400K
Ω
—voltage
500
Ω
—current
Isolation None
Absolute maximum rating
±15V—voltage
±30mA—current
Linearity error
0.04% max of full scale
Error limits
0.4% of input value
Status indicators
(OUT OF RANGE)
Red LEDs—Lit when the corresponding input is receiving current or voltage in
excess of the input range. See Note 5.
Environmental
IP20/NEMA1
Operating temperature
0
°
to 50
°
C (32 to 122° F)
Storage temperature
-20
°
to 60
°
C (-4 to 140° F)
Relative Humidity (RH)
5% to 95% (non-condensing)
Dimensions (WxHxD)
80mm x 93mm x 60mm (3.15 x 3.66 x 2.362”)
Weight
150g (5.3 oz)
Mounting
Either onto a 35mm DIN-rail or screw- mounted.
Notes:
1.
Each input may be set as either thermocouple, voltage (0-10V), or current (0-20mA, 4-20mA)
via wiring, jumper and software settings.
2.
The device can also measure voltage within the range of -5 to 56mV, at a resolution of 0.01mV.
The device can also measure raw value frequency at a resolution of 14-bits(16384).
3.
The input analog value represents the measured value as shown in the following examples:
- Thermocouple: a value of 262 is represented as 26.2ºC.
- mV: value of 262 is represented as 2.62mV.
4.
The value of a thermocouple may also indicate when the sensor is not connected to the input, or
when the analog value exceeds the permissible range. If such is the case, the value will be 32767.
5.
The voltage or current value of analog inputs can also indicate faults, as shown in the table below.
Value: 12-bit
(Fast mode)
Value: 14-bit
(Normal mode)
Input Value
Deviates:
-1 -1
Slightly
below
the input range.
4096 16384 Slightly
above
the input range.
32767 32767
Greatly
above or below
the input range.
10
Unitronics Industrial Automation