Control connection
39
04/2019 - V01
DS 400.2
Dig
ital o
ut
pu
ts
(o
pe
n e
m
itt
er
)
Analoge Eingang ±10 V
DSx-BAx-DPC/E-DS-400-Ana-1-2
Input
Connection
Basic function
Voltage
State
Parameter
AIN1+, AIN1-
X1:8, X1:9
Speed command value +/- 10 V
prog.
AIN2+, AIN2-
X1:15, X1:16 Current limit
+/- 10 V
prog.
Features
Differential input
AIN1+ / AIN1-
AIN2+ / AIN2-
Input resistance
70 k
Threshold voltage
± 12 V
Resolution
11Bit + sign
The direction of rotation of the motor can either be changed by swapping the ± connections at
the differential input, or by means of a logic input or by programming.
The analog inputs can be assigned to different functions.
With a digital command value (RS232, x-bus) the analog input AIN1 can be programmed as
external analog speed limit and the analog input AIN2 can be programmed as external analog
current limit.
Analog /- 10V
Output
Connection
Function
Voltage
State
Parameter
AOUT1
X2:20
measurement
±10 V
prog.
GND
X2:21
Signal zero
0 V
fixed
The analog input can be assigned to different functions.
Sollx
REF150
10k
100k
100k
100nF
15k
10k
100k
15k
IN+
IN-
DSxx/BAxx
1.5V +/- 1.36V
analog
inputs