Unitek DELTA 800 Скачать руководство пользователя страница 8

 

8

Abnormal Situation 

Cause 

Solution 

UPS shutdowns immediately, ON 
switch does not work and there is 
no alarm 

DIP Switch setting error. 

Set correct Voltage and frequency on the 
DIP Switch (2) 

ON button (3) switch was not 
pressed or pressed less than 3 
seconds.  

Press and hold the Main On switch for 
more than 3 seconds. 

Battery voltage is too low 

Recharge the battery for at least 4 hours. 

Battery is not connected 
properly. 

Check that battery connectors are fully 
engaged. 

UPS can not be turned on and 
LCD panel does not light. 

UPS is not connected to AC 
Power supply. 

Check that the power cable from the UPS 
to the utility power supply is securely 
connected. 

Faulty microprocessor 

Unplug power cord and all connected 
equipment from the UPS to let it shut 
down automatically. Replace PCB or 
microprocessor. 

ON button (3) switch on front panel 
doesn’t work. 

ON button (3) was damaged. 

Replace ON button 

UPS input circuit breaker tripped 

Overload 

Remove some load by unplugging non-
critical equipment and press the circuit 
breaker (6) to reset it. 

UPS starts up normally but there is 
no output. 

Output breaker or output relay is 
damaged. 

Check and Replace output breaker or 
output relay. 

Power cord is loose 

Re-plug the power cord firmly. 

Blown Input fuse (or breaker) / 
Line voltage is too high or too 
low / Line frequency is over 
range. 

Remove load and replace fuse (or 
resetting the input breaker) with the same 
rating and check input voltage and 
frequency. 

UPS is always at battery mode. 

Input relay damaged. 

Replace Input relay. 

UPS is normal but the computer 
can’t be turned on. 

Computer input power cord is 
loose or not connected. 

Reconnect computer input power cord 
correctly. 

Battery is not fully charged or 
battery is dead or weak. 

Recharge the battery for 4 hours and re-
test the backup time. If problem remains, 
Replace batteries 

Backup time is less than the rating. 

UPS is slightly overloaded. 

Remove the least critical load 

Communication function is not 
working. 

Wrong interface cable. 

Use the communication cable included in 
UPS box 

Battery is weak. 

Allow the battery to recharge for at least 4 
hours. Then, perform a self-test. If the 
problem persists after recharging, replace 
the battery. 

The replace battery icon (

) is lit. 

B

e

yR

e

p

a

ce

m

e

n

t co

n

n

e

cto

oco

n

n

e

cte

d

 p

ro

p

e

rly. 

Check that the battery connector is fully 
engaged. 

The overload icon (

) is lit and 

power output is normal, UPS emits 
continuous beep, and fault LED (2) 
is lit. 

UPS is overloaded. 

Remove some load by unplugging non-
critical equipment 

The fault icon (

) is lit and the 

alarm beeps continuously in backup 
mode. 

UPS Fault including overload, 
short circuit, or output voltage, 
and other abnormal conditions. 

1. Check output circuit 
2. Call for service 

 The site wiring fault icon (

) is lit. 

Site wiring problem. 

Call an electrician to check your wiring. 

Power cord plug is loose 

Check the power cord plug  

Input breaker on rear panel 
blown or Input Fuse blown 

Reset the input breaker or replace fuse 

UPS stays idle while AC is 
connected. 

Wall socket is damaged 

Check wall socket with a table lamp. 

Battery is not fully charged or 
battery is dead. 

Recharge the battery for 4 hours and re-
test the backup time. If problem remains, 
replace batteries 

During power failures, the UPS 
automatic turns off 

UPS is faulty. 

Call for service. 

 
 

Содержание DELTA 800

Страница 1: ...anuel de l utilisateur Manual del usuario User s manual DELTA 800 1100 1400 2200 3000 Onduleur Online System 800 3000 VA SAI Online System 800 3000 VA 800 3000 VA Online System UPS www unitek power co...

Страница 2: ...2...

Страница 3: ...nnect es n exc de pas les 3 5 mA Cet appareil g n re utilise et peut mettre des fr quences radio S il n est pas install conform ment aux instructions il peut provoquer des interf rences au niveau des...

Страница 4: ...eur trop faible corrig 11 Voltage secteur trop fort corrig 12 Sortie onduleur 13 Erreur de polarit ou de mise la terre 14 Surcharge 15 Taux de charge de l onduleur des batteries 16 Affichage taux de c...

Страница 5: ...batterie quand le voltage ou la fr quence du secteur sortent des plages de tol rance Des alertes visuelles et sonores sont alors d clench es L onduleur fournit alors un courant r gul gr ce ses batter...

Страница 6: ...t 2 6 Indicateurs visuels et sonores bips Etat Mode Normal secteur normal Erreur de polarit ou de mise la terre 1 bip 2 secondes Mode Batterie d faut du secteur 1 bip 1 secondes Mode Batterie d faut d...

Страница 7: ...ois en pays chauds 5 R solution de probl me La table de r solution de panne ci dessous couvre la plupart des difficult s que vous pourrez rencontrer lors d une utilisation normale de votre onduleur Si...

Страница 8: ...t be turned on Computer input power cord is loose or not connected Reconnect computer input power cord correctly Battery is not fully charged or battery is dead or weak Recharge the battery for 4 hou...

Страница 9: ...Ah x2 12V 9Ah x2 12V 7Ah x4 12V 9Ah x4 Replacement utilisateur OUI Batterie Temps de recharge 2 4 heures 90 Mode Normal 110 pendant 10 minutes puis arr t Prot contre les surcharges Mode Batterie 110 p...

Страница 10: ...10...

Страница 11: ...as est n apagadas durante la instalaci n Este equipo genera utiliza y puede irradiar energ a en el espectro de radio frecuencia Si no es instalado y utilizado siguiendo las instrucciones este equipo p...

Страница 12: ...ndicaci n nivel de bater a Panel trasero 1 Puerto RJ45 2 Interruptor DIP 3 Puerto de comunicaci n USB 4 Puerto de comunicaci n RS232 5 Bot n de reajuste de CPU Interno Presione para apagar 6 Interrupt...

Страница 13: ...lmente cargadas Tambi n regula el voltaje de salida para que se mantenga en el rango requerido y a su vez a sla la carga de picos de corriente y ruido que pueda venir del AC comercial Modo Bater a El...

Страница 14: ...e los cuales est trabajando y apague el ordenador Despu s apague el SAI para conservar la bater a para su uso posterior y tests adicionales Reponga la energ a el ctrica al equipo conectado reenchufand...

Страница 15: ...r el UPS Para guardar el UPS por largo tiempo en climas moderados cargue las bater as por 12 horas cada tres meses simplemente conectando el UPS y encendiendo el interruptor principal Repita cada dos...

Страница 16: ...9Ah x2 12V 7Ah x4 12V 9Ah x4 Reemplazable por el usuario Yes Bater a Tiempo de recarga 2 4 horas para 90 Modo normal 110 por 10 minutos y apagado Protecci n de sobrecarga Modo bater a 110 por segundos...

Страница 17: ...t installed and used in accordance with the instructions this unit may cause harmful interference to radio communications However there is no guarantee that interference will not occur in a particular...

Страница 18: ...load 15 Load Battery Level 16 Load Battery Level Indication control button Rear panel 1 RJ11 RJ45 Port 2 DIP Switch 3 USB Communication Port 4 RS232 Communication Port 5 Internal CPU Reset Button pres...

Страница 19: ...ught by the mains On Battery Mode The UPS operates on battery when the line voltage or frequency has fallen outside the limits The user is alerted of this mode of operation by visual and audible indic...

Страница 20: ...est 2 6 Audible Visual Indicators Buzzer Operating Status Normal mode Mains normal Polarity Error ground fault 1 beep every 2 seconds Battery mode Mains failure 1 beep every second Battery mode Mains...

Страница 21: ...g the power cord into the wall receptacle and turning on the main switch Repeat every 3 months in high temperature locations more than 30 C 5 Troubleshooting The TROUBLESHOOTING TABLE in the next page...

Страница 22: ...computer can t be turned on Computer input power cord is loose or not connected Reconnect computer input power cord correctly Battery is not fully charged or battery is dead or weak Recharge the batt...

Страница 23: ...ge 12V 7Ah x2 12V 7Ah x2 12V 9Ah x2 12V 7Ah x4 12V 9Ah x4 User s Replacement Yes Battery Recharge time 2 4 hours to 90 Normal mode 110 for 10 minutes then shutdown Overload prot Battery mode 110 for s...

Страница 24: ...24 w w w u n i t e k p o w e r c o m v 2 1 0504...

Отзывы: