Abnormal Situation 

Cause 

Solution 

UPS shutdowns immediately, ON 
switch does not work and there is 
no alarm 

DIP Switch setting error. 

Set correct Voltage and frequency on the 
DIP Switch (2) 

ON button (3) switch was not 
pressed or pressed less than 3 
seconds.  

Press and hold the Main On switch for 
more than 3 seconds. 

Battery voltage is too low 

Recharge the battery for at least 4 hours. 

Battery is not connected 
properly. 

Check that battery connectors are fully 
engaged. 

UPS can not be turned on and 
LCD panel does not light. 

UPS is not connected to AC 
Power supply. 

Check that the power cable from the UPS 
to the utility power supply is securely 
connected. 

Faulty microprocessor 

Unplug power cord and all connected 
equipment from the UPS to let it shut 
down automatically. Replace PCB or 
microprocessor. 

ON button (3) switch on front panel 
doesn’t work. 

ON button (3) was damaged. 

Replace ON button 

UPS input circuit breaker tripped 

Overload 

Remove some load by unplugging non-
critical equipment and press the circuit 
breaker (6) to reset it. 

UPS starts up normally but there is 
no output. 

Output breaker or output relay is 
damaged. 

Check and Replace output breaker or 
output relay. 

Power cord is loose 

Re-plug the power cord firmly. 

Blown Input fuse (or breaker) / 
Line voltage is too high or too 
low / Line frequency is over 
range. 

Remove load and replace fuse (or 
resetting the input breaker) with the same 
rating and check input voltage and 
frequency. 

UPS is always at battery mode. 

Input relay damaged. 

Replace Input relay. 

UPS is normal but the computer 
can’t be turned on. 

Computer input power cord is 
loose or not connected. 

Reconnect computer input power cord 
correctly. 

Battery is not fully charged or 
battery is dead or weak. 

Recharge the battery for 4 hours and re-
test the backup time. If problem remains, 
Replace batteries 

Backup time is less than the rating. 

UPS is slightly overloaded. 

Remove the least critical load 

Communication function is not 
working. 

Wrong interface cable. 

Use the communication cable included in 
UPS box 

Battery is weak. 

Allow the battery to recharge for at least 4 
hours. Then, perform a self-test. If the 
problem persists after recharging, replace 
the battery. 

The replace battery icon (

) is lit. 

Battery Replacement connector 
is not connected properly. 

Check that the battery connector is fully 
engaged. 

The overload icon (

) is lit and 

power output is normal, UPS emits 
continuous beep, and fault LED (2) 
is lit. 

UPS is overloaded. 

Remove some load by unplugging non-
critical equipment 

The fault icon (

) is lit and the 

alarm beeps continuously in backup 
mode. 

UPS Fault including overload, 
short circuit, or output voltage, 
and other abnormal conditions. 

1. Check output circuit 
2. Call for service 

 The site wiring fault icon (

) is lit. 

Site wiring problem. 

Call an electrician to check your wiring. 

Power cord plug is loose 

Check the power cord plug  

Input breaker on rear panel 
blown or Input Fuse blown 

Reset the input breaker or replace fuse 

UPS stays idle while AC is 
connected. 

Wall socket is damaged 

Check wall socket with a table lamp. 

Battery is not fully charged or 
battery is dead. 

Recharge the battery for 4 hours and re-
test the backup time. If problem remains, 
replace batteries 

During power failures, the UPS 
automatic turns off 

UPS is faulty. 

Call for service. 

 
 

Содержание DELTA 1100 TR

Страница 1: ...anuel de l utilisateur Manual del usuario User s manual DELTA TR 1100 1400 2200 3000 Onduleur Online System 1100 3000 VA SAI Online System 1100 3000 VA 1100 3000 VA Online System UPS www unitek power com ...

Страница 2: ...2 ...

Страница 3: ...areil génère utilise et peut émettre des fréquences radio S il n est pas installé conformément aux instructions il peut provoquer des interférences au niveau des communications radio Toutefois il n existe pas de garantie que ces interférences ne se produiront pas Si cet appareil causait des interférences dans la réception de la radio ou de la télévision ce qui peut être déterminé en allumant et ét...

Страница 4: ...onduleur des batteries 16 Affichage taux de charge de l onduleur des batteries Panneau arrière 1 Port RJ11 RJ45 2 DIP boîtier à double rangée de connexion 3 Port de Communication USB 4 Port de Communication RS232 5 N A 6 Disjoncteur d entrée 7 Sorties électriques 8 Identification 9 Disjoncteur de sortie 10 Prise d entrée secteur 11 Connecteur batteries externes 12 Emplacement SNMP 2 3 Installation...

Страница 5: ...ulé grâce à ses batteries Redémarrage automatique l onduleur redémarrera automatiquement si le secteur redevient normal dans les 24 heures après un arrêt automatique L icône de la batterie clignotera pendant toue cette période Si le secteur n est pas rétablit dans les 24 heures la fonction de redémarrage automatiquement ne fonctionnera pas Un démarrage manuel sera alors nécessaire Pour empêcher un...

Страница 6: ...ent 2 6 Indicateurs visuels et sonores bips Etat Mode Normal secteur normal Erreur de polarité ou de mise à la terre 1 bip 2 secondes Mode Batterie défaut du secteur 1 bip 1 secondes Mode Batterie défaut du secteur arrêt imminent Batterie faible En attente du retour de secteur pour un redémarrage automatique Bip continu Surcharge court circuit ou anomalie du voltage en sortie Remplacement des batt...

Страница 7: ...hé à une prise qui fonctionne 2 Le voltage du secteur correspond il aux spécifications de l onduleur 3 Le fusible à l arrière de l onduleur doit il être remplacé N ouvrez pas votre onduleur Il ne contient pas de pièces interchangeables Les batteries utilisées par cet onduleur sont recyclables Elles contiennent du plomb métal dangereux pour la santé Elles doivent donc être confiées à un service com...

Страница 8: ... computer can t be turned on Computer input power cord is loose or not connected Reconnect computer input power cord correctly Battery is not fully charged or battery is dead or weak Recharge the battery for 4 hours and re test the backup time If problem remains Replace batteries Backup time is less than the rating UPS is slightly overloaded Remove the least critical load Communication function is...

Страница 9: ...2V 7Ah x4 12V 9Ah x4 12V 7Ah x8 12V 9Ah x8 Replacement utilisateur OUI Batterie Temps de recharge 4 heures à 90 Mode Normal 110 pendant 10 minutes puis arrêt Prot contre les surcharges Mode Batterie 120 pendant 10 secondes puis arrêt Mode Normal Fusible en entrée circuit électronique Prot contre les courts circuits Mode Batterie Circuit électronique Interface USB PNP RS232c auto sélection Communic...

Страница 10: ...éro de série aurait été endommagé changé ou retiré 2 Les dégâts détériorations ou mauvais fonctionnements dus à a un accident une mauvaise utilisation la négligence le feu l eau la foudre ou toute autre cause naturelle des modifications du produit sans notre autorisation ou le non suivi des instructions données du manuel fourni avec l appareil b Des réparations ou tentatives de réparation effectué...

Страница 11: ...11 ...

Страница 12: ...e la instalación Este equipo genera utiliza y puede irradiar energía en el espectro de radio frecuencia Si no es instalado y utilizado siguiendo las instrucciones este equipo podría causar interferencia a las comunicaciones por radio Sin embargo no hay garantía de que dicha interferencia no ocurra en una instalación particular Si este equipo llegase a causar interferencia en la recepción de radio ...

Страница 13: ... Carga Botón de control de indicación nivel de batería Panel trasero 1 Puerto RJ45 2 Interruptor DIP 3 Puerto de comunicación USB 4 Puerto de comunicación RS232 5 N A 6 Disyuntor de entrada 7 Tomas de salida 8 Etiqueta de características 9 Disyuntor de salida 10 Toma de entrada 11 Conector para baterías externas 12 Alojamiento SNMP 2 3 Instalación Antes de realizar la instalación por favor lea y e...

Страница 14: ...el voltaje de salida para que se mantenga en el rango requerido y a su vez aísla la carga de picos de corriente y ruido que pueda venir del AC comercial Modo Batería El UPS opera en este modo cuando el voltaje o la frecuencia de entrad han caído fuera de los límites permitidos Los usuarios son alertados de este hecho a través de indicadores visuales y alarmas El UPS alimenta la carga utilizando la...

Страница 15: ...sobre los cuales está trabajando y apague el ordenador Después apague el SAI para conservar la batería para su uso posterior y tests adicionales Reponga la energía eléctrica al equipo conectado reenchufando el SAI a la red eléctrica Respalde todos los archivos no guardados antes de realizar la simulación 2 6 Indicadores Audible Visuales Alarma Estado operativo Modo normal alimentación normal Error...

Страница 16: ...contrarse cuando el UPS este trabajando bajo condiciones normales Si el UPS no funciona adecuadamente por favor siga los siguientes pasos antes de llamar al centro de servicio 1 El UPS esta conectado a un toma corriente adecuado 2 El voltaje del toma corriente donde está conectado el UPS esta dentro del rango especificado 3 El fusible o el interruptor de circuito ambos del panel trasero necesitan ...

Страница 17: ...je DC 12V 7Ah x4 12V 9Ah x4 12V 7Ah x8 12V 9Ah x8 Reemplazable por el usuario Si Batería Tiempo de recarga 4 horas para 90 Modo normal 110 por 10 minutos y apagado Protección de sobrecarga Modo batería 120 por segundos y apagado Modo normal Fusible de entrada y circuito electrónico Protección de corto circuito Modo batería Circuito electrónico Interfaz inteligente USB PNP RS232c auto switch Comuni...

Страница 18: ...NO CUBRE LA GARANTÍA 1 Cualquier equipo cuyo número de serial haya sido dañado modificado o removido 2 Daño deterioro o malfuncionamiento provocado por a Accidente mal uso negligencia fuego agua tormenta o cualquier otro acto de la naturaleza modificación no autorizada del producto o falla por no seguir las instrucciones dadas en este manual b Reparación o intento de reparación por personas no aut...

Страница 19: ...19 ...

Страница 20: ...th the instructions this unit may cause harmful interference to radio communications However there is no guarantee that interference will not occur in a particular installation If this equipment does cause harmful interference to radio or television reception which can be determined by turning the equipment off and on the user is encouraged to try to correct the interference by one or more of the ...

Страница 21: ...ault 14 Overload 15 Load Battery Level 16 Load Battery Level Indication control button Rear panel 1 RJ11 RJ45 Port 2 DIP Switch 3 USB Communication Port 4 RS232 Communication Port 5 N A 6 Input Breaker 7 Output sockets Outlet 8 Rating Label 9 Output breaker 10 Input socket Inlet 11 external batteries connector 12 SNMP slot 2 3 Installation Before installation please read carefully the following in...

Страница 22: ...tery when the line voltage or frequency has fallen outside the limits The user is alerted of this mode of operation by visual and audible indicators The UPS provides power to the load from the battery and through its inverter and the output voltage and frequency of the UPS are regulated within a narrow band Function Panel Indicator Switch On Press and hold the ON switch 3 on the front panel Wait u...

Страница 23: ...ndicators Buzzer Operating Status Normal mode Mains normal Polarity Error ground fault 1 beep every 2 seconds Battery mode Mains failure 1 beep every second Battery mode Mains failure imminent cutoff Battery low Stand by waiting for mains return for auto restart Continuous beep Overload short circuit or abnormal output voltage Battery replacement needed Weak battery recharge needed ON Blinking OFF...

Страница 24: ...fore calling the repair center 1 Is the UPS plugged into a proper working outlet 2 Is the line voltage within the specified rating 3 Does the fuse on the rear panel need to be replaced Please do not open the metal cover There are no user serviceable parts inside The batteries contained in this UPS are recyclable The batteries contain lead and pose a hazard to the environment and human health if no...

Страница 25: ...e computer can t be turned on Computer input power cord is loose or not connected Reconnect computer input power cord correctly Battery is not fully charged or battery is dead or weak Recharge the battery for 4 hours and re test the backup time If problem remains Replace batteries Backup time is less than the rating UPS is slightly overloaded Remove the least critical load Communication function i...

Страница 26: ...e Lead Acid DC Voltage 12V 7Ah x4 12V 9Ah x4 12V 7Ah x8 12V 9Ah x8 User s Replacement Yes Battery Recharge time 4 hours to 90 Normal mode 110 for 10 minutes then shutdown Overload prot Battery mode 110 for seconds then shutdown Normal mode Input fuse Electronic circuit Short circuit prot Battery mode Electronic circuit Intelligent Interface USB PNP RS232c auto switch Communication Compatible O S W...

Страница 27: ...valid only for the first consumer purchaser IV WHAT THE WARRANTY DOES NOT COVER 1 Any product on which the serial number has been defaced modified or removed 2 Damage deterioration or malfunction resulting from a Accident misuse neglect fire water lightning or other acts of nature unauthorized product modification or failure to follow instructions supplied with the product b Repair or attempted re...