Series
TFH
Series
TFH
Option -
Fresh Water Backwash
from Municipal Water Supply
INSTALLATION SEQUENCE - FRESH WATER BACKWASH FROM MUNICIPAL SUPPLY
This option changes the facepiping from the standard configuration (as shown in drawings elsewhere) to the con-
figuration shown above. Included with this option is a flow control valve for field installation.
The end-user is respon-
sible for the addition of a pressure-controlling device in the municipal water supply line set to a maximum
30 psi.
Local code may also require the addition of a back flow preventer in the municipal water supply line.
Municipal water supply is connected to the top port of the bottom valve. The additional equipment required to control
the pressure and flow of municipal water supply to the filter system should be installed in the following sequence
from source toward the filter’s bottom valve: 1) back flow preventer (by others); 2) pressure controlling device set to
maximum 30 psi (by others); 3) flow control valve 2” (provided by TF) set at either • 28% for TFH-24 at 65 gpm, •
20% for TFH-30 at 100 gpm. • or 13% for TFH-36 at 141 gpm.