  D A T A   S H E E T

 V85005-0135

 

Not to be used for installation purposes.

  Issue 1.1

11-17-16

SA-232 RS-232 interface 

GND (black wire)

TXD (white wire)

RXD (red wire)

SA-232 wiring

The SA-232 card provides an RS-232 in-
terface with VS panels. It can be used for 
connecting a printer to the control panel 
to print system events. The card also 
can be used for connecting a computer 
to download a configuration program 
from the VS-CU to the control panel.

The RS-232 card is installed on the plas-
tic assembly and connects to the main circuit board via a ribbon 
cable.

SA-232 specifications

Operating voltage

Standard EIA-232

Terminal rating

12 to18 AWG (0.75 to 2.5 sq mm)

Operating environment

Temperature

Humidity

32 to 120°F (0 to 49°C)
0 to 93% RH, noncondensing at 90°F (32°C)

SA-DACT Dialer

The SA-DACT provides communications between the control 
panel and the central station over a telephone line system. It 
transmits system status changes (events) to a compatible digital 
alarm communicator receiver over the public switched telephone 
network. The dialer is capable of single, dual, or split reporting 
of events to two different account and telephone numbers. The 
modem feature of the SA-DACT can also be used for uploading 
and downloading panel configuration, history, and current status 
to a PC running the VS-CU.

Phone line 1

Phone line 2

To wall

phone jack

Phone cables

(supplied)

RJ31 jacks

SA-DACT

wiring

   The dialer phone lines connect to 

connectors on the dialer’s main 
circuit board. Phone line 1 connects 
to connector J4 and phone line 2 
connects to connector J1.

The SA-DACT queues mes-

sages and transmits them based on priority (alarm, supervisory, 
trouble, and monitor). Activations are transmitted before restora-
tions. 

The SA-DACT is installed on the plastic assembly and connects to 
the main circuit board via a ribbon cable.

SA-DACT specifications

Phone line type

One or two loop-start lines on a public, 
switched network

Phone line connector

RJ-31/38X (C31/38X)

Communication formats

Contact ID (SIA DC-05)

Operating environment

Temperature

Humidity

32 to 120°F (0 to 49°C)
0 to 93% RH, noncondensing at 90°F 
(32°C)

Compatible DACRs
Receiver

Models

Formats

Ademco

685

Contact ID

FBII

CP220

Contact ID

Osborne-Hoffman

OH 2000

Contact ID

Bosch

D6600

Contact ID

Silent Knight

9800

Contact ID

Sur-Gard

SG-MLR1, MLR2

Contact ID

SA-CLA Class A Module (VS1 only)

The SA-CLA card provides Class A capability for NAC wiring. 
Its terminal block provides the wiring connection for NAC return 
wiring. The card is required for annunciator Class A wiring even 
though this wiring does not return to the SA-CLA card. The SA-
CLA is compatible with VS1 control panels only. VS4 panels are 
Class A Ready. The SA-CLA is installed directly to the control 
panel circuit board using its plastic standoffs and plug connection.

SA-CLA specifications

Operating voltage

24 VFWR

Operating current

3.75 A FWR total at 120/230 VAC 60 Hz
3.0 A FWR total at 230 VAC 50 Hz 
2.5 A max per circuit

Circuit impedance

26 ohms, 0.35uF

Terminal rating

12 to18 AWG (0.75 to 2.5 sq mm)

Operating environment

Temperature

Humidity

32 to 120°F (0 to 49°C)
0 to 93% RH, noncondensing at 90°F 
(32°C)

D16L-VS LED Display Expander (VS4 only)

The D16L-VS LED Display Expanders provide LED annuncia-
tion for up to 16 zones. It provides two LEDs for each zone. Two 
D16L-VS LED display expanders can be installed in each VS4 
panel.

(1) LED 1
(2) LED 2
(3) LED Expander 1
(4) LED Expander 2
(5) Alarm/non-alarm  
    and trouble zone LEDs 

Содержание Kidde VS1

Страница 1: ...and two additional notification appliance circuits This makes them ideal retrofit solu tions that can accommodate new intelligent detectors as well as existing conventional devices VS Series supports...

Страница 2: ...ckly gets the panel operational using factory default settings Basic zone and point settings can be programmed through the front panel interface so the system is up and running in no time For more adv...

Страница 3: ...andby batteries 1 2 3 4 5 6 7 8 9 10 11 12 13 00 00 00 01 01 07 Four Class B or two optional Class A NACs Up to 20 000 feet of wiring per loop Four Class B or two optional Class A NACs Optional 10 A o...

Страница 4: ...individually configured for continuous temporal synchronized and coded output Specifications VS4 VS1 Circuit Type 4 Class B or 2 Class A 2 Class B or 2 Class A with SA CLA module Voltage 24 VFWR Curre...

Страница 5: ...itch used to select the default Relay or NAC output device type Device types other than the default are accomplished through programming RZI16 2 Specifications Voltage 24V Aux nominal Supervisory curr...

Страница 6: ...priority alarm supervisory trouble and monitor Activations are transmitted before restora tions The SA DACT is installed on the plastic assembly and connects to the main circuit board via a ribbon cab...

Страница 7: ...y 500 mA Output 28 3 to 21 9 VDC special application Note For a list of compatible devices see the VS1 and VS4 Series Compatibility List P N 3102354 EN Loop circuit Maximum loop resistance 66 Maximum...

Страница 8: ...One loop system one 64 point loop installed 110v gray door English Canada VS1 GL F One loop system one 64 point loop installed 110v gray door French Canada VS1 G PG One loop system with one 64 point...

Отзывы:

Похожие инструкции для Kidde VS1