background image

Page 5 of 8 

  D A T A   S H E E T

 V85005-0135

 

Not to be used for installation purposes.

  Issue 1.1

11-17-16

Single and Dual Loop Controller Cards

The V-SLC2-1 is a single loop controller card that can be used 
with the VS1 as a replacement for the standard 64-point loop, or 
with the VS4 as a 250-point expansion module.

The V-SLC2-2 is a 500-point dual loop controller card for the VS4 
that provides two IDC circuits, each with 125 detector addresses 
and 125 module addresses.

Specifications

V-SLC2-1

V-SLC2-2

Device Addresses

VS4: one loop, 250 

device addresses

VS1: 64 addresses

VS4: two loops, 500 

device addresses

Wiring

Class B or Class A

Operating Voltage

24 VDC

Operating Current 
(fully loaded loop)

Standby: 55 mA

Alarm: 80 mA

Standby: 45 mA

Alarm: 70 mA

Note: These ratings do not include the use of two-wire smoke modules.

Communication Line 
Voltage

Max. 20.6 V peak-to-peak

Terminal Rating

12 to 18 AWG (0.75 to 2.5 mm

2

)

Circuit Current

0.5 A max.

Max total loop 
resistance

66 Ω

Max total loop 
capacitance

0.5 μF

Isolators

64 isolators maximum per loop (total both

isolator bases and modules)

Ground Fault 
Impedance

0 to 5 kΩ

Operating 
Environment

32 to 120°F (0 to 49°C)

0 to 93% noncondensing at 90°F (32°C)

RZI16-2 Remote Zone Interface Module

 

The RZI16-2 Addressable Remote Zone Interface Module is an 
addressable device that provides connections for sixteen Class B 
Initiating Device Circuits and two Class B Supervised Output 
Circuits. The inputs and outputs can be configured individually for 
several device types.

The RZI16-2 requires 18 consecutive addresses on the Signaling 
Line Circuit (SLC). Addresses are assigned electronically. There are 
no address switches to set.

The RZI16-2 incorporates two 8-segment DIP switches that are 
used to select the Alarm or Supervisory default device type for 
each of the 16 IDC circuits. The module also includes one 4-seg-
ment DIP switch used to select the default Relay or NAC output 
device type. Device types other than the default are accomplished 
through programming.

RZI16-2 Specifications

Voltage
   24V/Aux nominal:  
   Supervisory current:
   Alarm current:
   24V/Aux minimum:
   24V/Aux maximum:
   NAC1, NAC2 nominal:

 
24 VDC
250 mA at 24 VDC nominal
1000 mA
18.4 VDC
26.4 VDC
24 VDC

Current  
   Standby current  
   for 4.7 k EOL (U.S.)  
   Standby current for  
   3.9 k EOL (Canada)  
   Alarm current  
   at nominal voltage

 
 
4.8 mA/ circuit  
 
5.7 mA/ circuit  
 
31.1 mA/ circuit

Relay outputs  
   Quantity  
   Type Rating (pilot duty)

 
2  
Programmable 24 VDC at 2.5 A

Input circuit wiring 
resistance

25 Ω per wire

Initiating device circuits 
   Quantity 
   EOL resistor 
   Zone voltage 

   Alarm current 
   Alarm impedance range 
   Trouble impedance range

16 
4.7 kΩ (U.S.); 3.9 kΩ Canada 
22.78 V for 4.7 kΩ (U.S.)  
22.08 V for 3.9 kΩ (Canada)  
31.1 mA/ channel at nominal voltage  
< 680 Ω  
> 5.55 kΩ

Supervised output circuits 
   EOL resistor 
   Quantity 
   Short circuit detection 
   Open circuit detection 
   Contact ratings

15 kΩ 
2
< 2.6 kΩ 
> 61.9 kΩ 
24 VDC at 2.5 A (5 A for two NACs)

Compatible cabinets

MFC(A), VS4, APS

SA-ETH Ethernet Interface Card 

Network cable

Ethernet card

To network

connection

SA-ETH wiring

   The SA-ETH card provides a 

standard 10/100 Base T Ether-
net network connection for 
connecting to an intranet, a local 
network, or the Internet. The 
card can be used to download 
configuration programming from 
the VS-CU to the panel.

The Ethernet card is installed on 
the plastic assembly and con-
nects to the main circuit board 
via a ribbon cable.

SA-ETH specifications

Ethernet

10/100 Base T

Operating environment

Temperature

Humidity

32 to 120°F (0 to 49°C)
0 to 93% RH, noncondensing at 90°F 
(32°C)

Option Cards

Kidde VS Series panels are supported by a complete line of mod-
ules and related equipment that enhance performance and extend 
system capabilities. Option cards plug directly into the control 
panel main circuit board or are connected to it with a ribbon cable. 
After installation, terminals remain accessible. The cabinet pro-
vides ample room for wire routing, keeping wiring neat at all times.

Содержание Kidde VS1

Страница 1: ...and two additional notification appliance circuits This makes them ideal retrofit solu tions that can accommodate new intelligent detectors as well as existing conventional devices VS Series supports...

Страница 2: ...ckly gets the panel operational using factory default settings Basic zone and point settings can be programmed through the front panel interface so the system is up and running in no time For more adv...

Страница 3: ...andby batteries 1 2 3 4 5 6 7 8 9 10 11 12 13 00 00 00 01 01 07 Four Class B or two optional Class A NACs Up to 20 000 feet of wiring per loop Four Class B or two optional Class A NACs Optional 10 A o...

Страница 4: ...individually configured for continuous temporal synchronized and coded output Specifications VS4 VS1 Circuit Type 4 Class B or 2 Class A 2 Class B or 2 Class A with SA CLA module Voltage 24 VFWR Curre...

Страница 5: ...itch used to select the default Relay or NAC output device type Device types other than the default are accomplished through programming RZI16 2 Specifications Voltage 24V Aux nominal Supervisory curr...

Страница 6: ...priority alarm supervisory trouble and monitor Activations are transmitted before restora tions The SA DACT is installed on the plastic assembly and connects to the main circuit board via a ribbon cab...

Страница 7: ...y 500 mA Output 28 3 to 21 9 VDC special application Note For a list of compatible devices see the VS1 and VS4 Series Compatibility List P N 3102354 EN Loop circuit Maximum loop resistance 66 Maximum...

Страница 8: ...One loop system one 64 point loop installed 110v gray door English Canada VS1 GL F One loop system one 64 point loop installed 110v gray door French Canada VS1 G PG One loop system with one 64 point...

Отзывы: