United Technologies Edwards 3-ZA20A Скачать руководство пользователя страница 4

4 / 4 

 

P/N 387463-

EN • REV 005 • ISS 18MAR19

 

Specifications 

 

Current

 

 

Standby

 

 

Alarm

 

 

62 

mA 

 

1.12 A (3

-

ZA20A/20B)

 

2.48 A (3

-

ZA40A/40B)

 

Frequency response

 

400 Hz to 4 kHz at ±3 dB

 

Harmonic Distortion

 

< 7% 

Audio circuit

 

Input

 

Wiring 

Output

 

EOL resistor 

 
8-

channel, multiplexed digitized audio: 

 

Class B or Class A 

 

20 or 40 W at 25 or 70 VRMS

 [1] 

15 k

Ω 

(internal on 3

-

ZA20A/40A)

 

24 VDC

 

NAC circuit

 

 

Wiring 

 

Voltage

 

 

Current

 

 

EOL resistor 

 

Special applications

 

 

Class B or Class A 

 

24 

VDC

 

nominal

 

3.5 A

 

15 k

 

(internal on 3

-

ZA20A/40A)

 

Refer to the panel compatibility list.

 

Wire size 

12 to 18 

AWG (4.0

 to 

1.0

 

mm²)

 

Space requirements

 

1 rail space 

Operating environment

 

Temperature

 

Relative humidity

 

 

32 to 120 °F (0 to 49 °C)

 

93% noncondensing 

[1] For Canadian installations, 70 VRMS is nonpower

-

limited.

 

Regulatory information 

 

Environmental 

class 

UL/ULC

: Indoor dry

 

Contact information 

For 

contact information, see www.edwardsfiresafety.com.

 

Содержание Edwards 3-ZA20A

Страница 1: ...lass B 24 VDC outputs 3 ZA40B 40 watt zoned amplifier Class B audio Class B 24 VDC outputs Installation Install and wire this device in accordance with applicable national and local codes ordinances and regulations Caution Operating the amplifier at an output greater than that required by the speaker may overdrive the speaker circuit and result in damage to the equipment To install the amplifier 1...

Страница 2: ...it supervision The polarity reverses in an alarm condition 4 Shield required when audio riser and telephone riser share the same conduit 5 Twisted pair not required only when audio circuit riser shares conduit exclusively with 24 VDC riser or in conduit by itself 6 A maximum of 10 Signature Series CC1 or CC2 modules may be installed on the speaker circuit 7 For maximum wire resistance refer to the...

Страница 3: ...closure 3 Backup amplifier wiring must be rated greater than or equal to the field wiring used on amplifiers connected to the backup amplifier Figure 5 Typical wiring connecting to SIGA AAxx audio amplifier Notes 1 Configure the zone audio amplifiers for 25 VRMS 2 A maximum of 16 SIGA AAxx audio amplifiers may be connected to the output of a single zone audio amplifier 3 Shield required when the a...

Страница 4: ...0A 40A 24 VDC NAC circuit Wiring Voltage Current EOL resistor Special applications Class B or Class A 24 VDC nominal 3 5 A 15 kΩ internal on 3 ZA20A 40A Refer to the panel compatibility list Wire size 12 to 18 AWG 4 0 to 1 0 mm Space requirements 1 rail space Operating environment Temperature Relative humidity 32 to 120 F 0 to 49 C 93 noncondensing 1 For Canadian installations 70 VRMS is nonpower ...

Отзывы: