Wiring diagrams
Figure 2: Typical 25 or 70 VRMS notification appliance circuit wiring
Figure 3: Typical 24 VDC notification appliance circuit wiring
Notes for Figure 2 and Figure 3
1
.
All wiring is supervised and power
-
limited.
2
.
Install listed 15
k
Ω
resistor on last device only when wired as Class B riser.
3
.
Pola
rity designations on connector indicate output signal polarity for circuit supervision. The polarity reverses in an alarm condition.
4
.
Shield required when audio riser and telephone riser share the same conduit.
5.
Twisted
pair not required only when audio circuit riser shares conduit exclusively with 24 VDC
riser or in conduit by itself.
6
.
A maximum of 10 Signature Series CC1 or CC2 modules may be installed on the speaker circuit.
7
.
For maximum wire resistance, refer to the panel installation and service manual or technical reference manual.
8
.
Synchronization of Genesis strobes is accomplished through the use of G1M, G1M
-
RM, SIGA
-
CC1S, and SIGA
-
MCC1S modules. Refer to
the
panel compatibility list.