4-7

T-288

b.

Unit operation in cool mode and the
compressor

fully

loaded

(6-cylinder

operation) for 15 minutes.

c.

Head pressure at least 150 psig (for R-134a
systems). (It may be necessary to block
condenser air flow to raise head pressure.)

Under the above conditions, the system is properly
charged when the bottom receiver sight glass
appears half full with refrigerant. If the bottom sight
glass is not half full, add or delete refrigerant
charge to the proper level.

4.10 FILTER-DRIER REMOVAL

If a pressure drop across the filter-drier is indicated
or the moisture-indicator may show an abnormal
(wet) condition, the filter-drier must be changed.

a. Check for a restricted filter. Backseat the inlet

and outlet valves of the filter-drier and attach
the gauge manifold set. Midseat both valve
and start unit. Observe the pressure reading. If
a pressure drop of more than 10 psig is
indicated the filter is plugged and must be
changed.

b. Pump down the system as outlined in section

4.4.

c. Turn the driver’s A/C switch and rear control

switch to the “OFF” position.

d. Place a new filter-drier near the unit for

immediate installation.

e. Using two open end wrenches, slowly crack

open the flare nuts on each side of the
filter-drier. Remove the filter-drier.

CAUTION

The

filter-drier

may

contain

liquid

refrigerant. Slowly open the flare nuts and
avoid contact with exposed skin or eyes.

f.

Remove seal caps from the new filter-drier.
Apply a light coat of compressor oil to the
O’rings.

g. Assemble the new filter-drier to lines ensuring

that the arrow on the body of the filter-drier
points in the direction of the refrigerant flow
(refrigerant flows from left to right, as viewed).
Finger tighten flare nuts.

h. Tighten filter-drier flare nuts using two open

end wrenches.

i.

Install vacuum pump on filter drier inlet valve.
Evacuate to 500 microns and disconnect
vacuum pump.

j.

Open both inlet and outlet valves.

k. Test filter-drier for leaks.

l.

Check refrigerant level.

1

2

3

4

1. Valve Service Port

2. Filter-Drier Inlet

Liquid Line Valve

3. Flare Nut

4. Filter-Drier

5. Filter-Drier Outlet

Liquid Line Valve

1

3

5

Figure 4-5. Filter-Drier Removal

4.11

CHECKING PRESSURE SWITCHES

The recommended procedure for testing the High
Pressure Switch (HPS), Low Pressure Switch
(LPS),

Condenser

Fan

Switch

(CFS)

and

Unloader Pressure Switches #1, #2 & #3 (UPS1,
UPS2 & UPS3) is to remove the switch from the
unit and bench test it as described in the following
procedure.

All pressure switches are threaded into positive
shut off valve connections (schrader valves) to
allow easy removal and installation without
pumping down or removing refrigerant from the
unit. All wire leads to the switches are quick
disconnects.

The High Pressure Switch (black wire leads) and
Low Pressure Switch (red wire leads) are located
on the compressor. The Condenser Fan Speed
Switch (gray wire leads) and the Unloader
Pressure Switch #3 (white wire leads) are located
on the discharge line above the curbside
evaporator fan blower assembly. The Unloader
Pressure Switches #1 and #2 are located on the
suction line near the curbside evaporator motor.

If the switch does not function as described below,
the switch is defective and should be replaced.

a. Remove switch from the unit.

b. Connect an ohmmeter across switch leads

(with no pressure applied to the switch) and
check for continuity. Low Pressure Switch
(LPS) and Unloader Pressure Switch (UPS3)
will show no continuity (switches will be open).
(See Table 4-1.)

c. Connect switch to a cylinder of dry nitrogen as

shown inFigure 4-6.

Содержание Carrier TRANSICOLD 68RM35-604-20

Страница 1: ...T 288 Rearmount 68RM35 604 20 R 134a NYCDOT...

Страница 2: ...MANUAL OPERATION AND BUS AIR CONDITIONING UNIT Rearmount 68RM35 604 20 R 134a Carrier Transicold Division Carrier Corporation P O Box 4805 Syracuse N Y 13221 Carrier Corporation 1999 D Printed in U S...

Страница 3: ...r supply is disconnected Always work in pairs Never work on the equipment alone In case of severe vibration or unusual noise stop the unit and investigate MAINTENANCE PRECAUTIONS Beware of unannounced...

Страница 4: ...rosive and toxic compounds WARNING Be sure to avoid refrigerant coming in contact with the eyes Should refrigerant come in contact with the eyes wash eyes for minimum of 15 minutes with potable water...

Страница 5: ...1 3 TROUBLESHOOTING 3 1 3 1 UNIT WILL NOT COOL 3 1 3 2 SYSTEM RUNS BUT HAS INSUFFICIENT COOLING 3 1 3 3 ABNORMAL PRESSURES 3 1 3 4 ABNORMAL NOISES OR VIBRATIONS 3 2 3 5 TEMPERATURE CONTROLLER MALFUNC...

Страница 6: ...r 4 13 4 18 5 Removing Oil from the Compressor 4 13 5 ELECTRICAL SCHEMATIC WIRING DIAGRAM 5 1 5 1 INTRODUCTION 5 1 LIST OF ILLUSTRATIONS Figure Page 1 1 Unit Assembly Back View 1 2 1 2 Unit Assembly I...

Страница 7: ...l 05G Compressor 4 12 4 12 Compressor Oil Charge Connections 4 13 5 1 Electrical Schematic Diagram Legend and Symbols 5 2 5 2 Electrical Schematic Diagram 5 3 LIST OF TABLES Table Page 1 1 Model Chart...

Страница 8: ...of the bus These units interface with the bus driver switches and pump to provide a complete air conditioning system All control systems are powered by 24 vdc supplied by the bus battery and alternato...

Страница 9: ...11 Discharge Line Isolation Valve 12 Receiver Sight Glass Upper 13 Moisture Liquid Indicator 14 Unloader Pressure Switch UPS3 Upper 15 Condenser Fan Switch CFS Lower 16 Evaporator Fan Housing Curbsid...

Страница 10: ...CS 1 Electrical Control Panel See Figure 1 3 2 Liquid Line Solenoid Valve 3 Thermostatic Expansion Valve TXV 4 Roadside Blower Housing 5 Air Filter 6 Evaporator Coil 7 Curbside Blower Housing 1 CDR 6...

Страница 11: ...14 Cool Disable Relay CDR 15 Evaporator Speed Relay ESR 16 Power Terminal Block PTB 17 Return Air Probe 18 Air Conditioning Stop Relay No 2 ACSR2 19 Heat Relay HR 20 Air Conditioning Stop Relay No 1...

Страница 12: ...k 05G Compressor Electric Unloader Pressure Switches UPS1 UPS2 UPS3 See Table 1 2 for settings 1 3 ELECTRICAL SPECIFICATIONS a Evaporator Blower Motor Bearing Lubrication Factory Lubricated additional...

Страница 13: ...r no 2 Circuit Breaker CB2 Manual Reset Opens at 60 amps Excessive current draw by evaporator fan motor no 1 Circuit Breaker CB3 Manual Reset Opens at 60 amps Excessive current draw by condenser fan m...

Страница 14: ...h set point then the evaporator fan motors will not operate when the thermostat is calling for heat Condenser Motor Overload COL1 and COL2 Each condenser fan motor is equipped with an internal thermal...

Страница 15: ...ON position EFR1 and EFR2 relays are energized When energized a set of internal EFR1 and EFR2 contacts are closed to start the evaporator fan motors Evaporator Overload Relays OR1 and OR2 Evaporator o...

Страница 16: ...nt supply of liquid is available to the evaporator coil as needed and as a storage space when pumping down the system The receiver is equipped with a sight glass to observe correct charge level and a...

Страница 17: ...er Drier Outlet Valve 9 Thermostatic Expansion Valve 10 Evaporator Coil 11 Suction Line 12 Subcooler 13 Liquid Suction Heat Exchanger 14 Condenser Fan Switch CFS 15 Unloader Pressure Switch UPS3 16 Ch...

Страница 18: ...ts to interrupt the compressor clutch circuit when the ambient temperature falls to 45_F 7 2_C Heat is then accomplished by cycling Boost Pump Motor BPM and Reheat Coolant Valve RCV to supply engine c...

Страница 19: ...above the thermostat set point the HEAT COOL switch remains in COOL and the HIGH LOW switch remains in the HIGH position The thermostat discontinues supplying the signal to semi unload the compressor...

Страница 20: ...2 3 T 288 Figure 2 2 Automatic High Speed Cool Mode Operation with Reheat TDR 10 SEC...

Страница 21: ...2 4 T 288 Figure 2 3 Automatic High Speed Cool Mode Operation No Reheat TDR 10 SEC...

Страница 22: ...2 5 T 288 Figure 2 4 Automatic High Speed Heat Mode Operation Below 45_F Ambient TDR 10 SEC...

Страница 23: ...refrigerant flow Low refrigerant charge Service valves partially closed Safety device open Liquid line solenoid valve stuck closed 3 3 3 6 3 7 3 7 and 4 12 4 9 Open 1 4 Check 3 3 ABNORMAL PRESSURES Hi...

Страница 24: ...s defective Motor brushes defective Evaporator fan loose or defective Return air filter dirty Icing of coil dirty coil Fan relays EFR1 OR EFR2 defective Safety device open Check 5 1 4 16 4 16 4 16 Cle...

Страница 25: ...refrigerant lines Turning the valve stem counterclockwise all the way out willbackseat the valve to open the suction or discharge line to the compressor and close off the gauge connection In normal op...

Страница 26: ...h O Ring Hose Fitting with O Ring Figure 4 2 R 134a Manifold Gauge Set Connections To service the refrigerant system the manifold gauge set is connected to the compressor suction low side service valv...

Страница 27: ...d always be used whenever removing contaminated refrigerant from the system If a recovery system is not available proceed as follows a Equipment Required 1 Appropriate evacuated returnable refrigerant...

Страница 28: ...the system prior to leak repair 8 Charge the unit as outlined in section 4 8 4 7 EVACUATION AND DEHYDRATION Proper evacuation and dehydration procedures are imperative when service repairs or compone...

Страница 29: ...ifold vacuum pump vacuum gauge reclaimer and hoses as shown in Figure 4 4 All hand valves on manifold should be closed The compressor service valves should be midseated if used with service valve caps...

Страница 30: ...Open filter drier inlet valve half way and allow the liquid refrigerant to flow into the unit Monitor weight of refrigerant cylinder to determine how much refrigerant is entering the system The corre...

Страница 31: ...ight as viewed Finger tighten flare nuts h Tighten filter drier flare nuts using two open end wrenches i Install vacuum pump on filter drier inlet valve Evacuate to 500 microns and disconnect vacuum p...

Страница 32: ...s No Continuity Switch Opens Continuity Switch Closes High Press ure HPS 300 10 psig 200 10 psig Low Press ure LPS 6 3 psig 25 3 psig Condenser Fan Speed CFS 250 10 psig 190 15 psig Unloader Pressure...

Страница 33: ...firmly secured to suction line as shown in Figure 4 8 Place insulation around TXV bulb and thermocouple 4 Connect suction gauge to the service port on the compressor suction service valve 5 Set tempe...

Страница 34: ...unger or deformed valve body assembly Failure to close may be caused by the following a Defective plunger or deformed valve body assembly b Foreign material in the valve It is not necessary to drain t...

Страница 35: ...Clip Bolt 5 Venturi 6 Evaporator Motor 7 Hub Set Screw 7 Figure 4 10 Evaporator Fan Blower Assembly 4 16 1 Routine Examination and Cleaning a At regular maintenance periods remove brush covers and cl...

Страница 36: ...second filter past the holding channel to the center position and remove e Repeat the above step with the third filter f Reverse the procedure for installing the new filters 4 18 COMPRESSOR 4 18 1 Rep...

Страница 37: ...4 18 2 Checking the Compressor Oil Level NOTE It may be necessary to preheat the coach and or operate the system in the Reheat Mode to keep the compressor fully loaded throughout this procedure a Ope...

Страница 38: ...n oil at all times Otherwise air and moisture will be drawn into the compressor 1 Connect manifold gauge set Place center charging line into compressor oil container as shown in Figure 4 12 Slowly ope...

Страница 39: ...is no pressure at the oil drain plug d Remove the oil drain plug on the bottom plate of the compressor and drain the proper amount of oil from the compressor Replace the plug securely back into the c...

Страница 40: ...5 0 26 0 26 70 21 71 1 490 2 5 00 4 90 4 20 4 6 31 7 0 32 0 32 75 24 78 7 542 6 5 53 5 43 2 19 5 6 36 6 0 39 0 39 80 27 86 7 597 8 6 10 5 98 0 18 6 5 44 8 0 46 0 45 85 29 95 3 657 1 6 70 6 57 2 17 7...

Страница 41: ...5 1 INTRODUCTION This section contains Electrical Schematic Wiring Diagrams covering the Models listed in Table 1 1 Before performing operation and maintenance on the equipment ensure that precaution...

Страница 42: ...HIGH PRESSURE SWITCH HR HEAT RELAY HR2 HEAT RELAY 2 LATH LOW AMBIENT THERMOSTAT LPS LOW PRESSURE SWITCH LSV LIQUID SOLENOID VALVE OR1 EVAPORATOR OVERLOAD RELAY 1 OR2 EVAPORATOR OVERLOAD RELAY 2 PTB P...

Страница 43: ...5 3 T 288 Figure 5 2 Electrical Schematic Diagam Based on Drawing 68RM35 1038 12 TDR 10 SEC...

Страница 44: ...1 4 7 4 8 Condenser Motor Overload 1 7 Condenser Speed Relay 1 4 1 7 1 8 Cool Disable Relay 1 4 1 8 Coolant Valve 3 2 D Description 1 1 3 1 Discharge Line Check Valve 1 2 Discharge Line Isolation Valv...

Страница 45: ...Glass 1 2 Refrigerant Charge 1 5 Reheat Coolant Valve 1 5 2 1 3 2 4 9 Relay Board 1 1 1 4 1 8 Return Air Probe 1 4 S Safety Devices 1 5 1 6 3 1 3 2 Schematic Wiring Diagrams 5 1 Service Valves 3 1 Sub...

Отзывы: