United Technologies Carrier TRANSICOLD 68RM35-604-20 Скачать руководство пользователя страница 15

1-8

T-288

rises, the switch will re-open. Refer to Table 1-2 for
switch settings.

Unloader pressure switch UPS3 closes on
pressure rise to energize unloader valve UV2.
Energizing UV2 will place the compressor in four
cylinder operation. As pressure drops, the switch
will re-open. Refer to Table 1-2 for switch settings.

Energizing of unloader valve UV1 can also be
accomplished

through

the

controller

LOAD/UNLOAD switch.

e. Relays

Fault Relay (FR)

The fault relay (FR) is plugged into the relay board
on the electrical control panel located in the rear
compartment of the unit. (See Figure 1-3.) The FR
relay is energized during initial start-up of the unit.
If the high or low pressure switch (HPS or LPS)
opens due to unsafe operating conditions, the
fault relay (FR) de-energizes and closes an
internal set of FR contacts to energize the ACSR.

A/C Stop Relays (ACSR1 and ACSR2)

The A/C stop relays (ACSR1 and ACSR2) are
plugged into the relay board on the electrical
control panel located in the rear compartment of
the unit. (See Figure 1-3.). The ACSR relay
energizes the A/C stop light when activated by the
fault relay (FR).

To restart the unit and turn the A/C stop light off,
the A/C switch must be toggled off and on.

Clutch Relay (CR)

The clutch relay (CR) is plugged into the relay
board on the electrical control panel located in the
rear compartment of the unit. (See Figure 1-3.)
When the CR relay is energized, a set of internal
contacts will close to activate the compressor
clutch (CL) to start the refrigerant cycle.

Cool Disable Relay (CDR)

The cool disable relay (CDR) coil is de-energized
opening a set of normally open CR contacts in the
clutch relay circuit whenever the evaporator fans
are shut down; this prevents the compressor from
operating when the fans are not operating.

Evaporator Fan Relays (EFR1 and EFR2)

Evaporator fan relays (EFR1 and EFR2) are
installed on the electrical control panel located in
the rear compartment of the unit. (See Figure 1-3.)
When the A/C Mode Switch (ACMS) is placed in

the ON position, EFR1 and EFR2 relays are
energized. When energized, a set of internal
EFR1 and EFR2 contacts are closed to start the
evaporator fan motors.

Evaporator Overload Relays (OR1 and OR2)

Evaporator overload relays (OR1 and OR2) are
plugged into the relay board on the electrical
control panel located in the rear compartment of
the unit. (See Figure 1-3.) These relays are
energized at the same moment the evaporator fan
relays are. The OR1 and OR2 relays, when
energized, will close a set of internal contacts to
energize the evaporator speed relay (ESR).

Evaporator Speed Relay (ESR)

The evaporator speed relay (ESR) is installed on
the electrical control panel located in the rear
compartment of the unit. (See Figure 1-3.) This
relay will energize when the thermostat calls for
low speed evaporator fan operation. When
energized,

the

internal

contacts

will

open

removing a third ground path, which puts the fans
in low speed operation. When the ESR coil is
de-energized, the internal contacts close, which
adds the third ground path and puts the fans in
high speed operation.

Condenser Fan Relays (CFR1 and CFR2)

The condenser fan relays (CFR1 and CFR2) are
installed on the electrical control panel located in
the rear compartment of the unit. (See Figure 1-3.)
When the A/C Mode Switch (ACMS) is placed in
the ON position and the thermostat is calling for
cooling, CFR1 and CFR2 are energized. When
energized, a set of internal CFR1 and CFR2
contacts are closed to start the condenser fan
motors. The low ambient thermostat (LATH) must
be closed to energize the condenser fan relays.

Condenser Speed Relay (CSR1)

The condenser speed relay (CSR1) is installed on
the electrical control panel located in the rear
compartment of the unit. (See Figure 1-3.) This
relay is energized at the same moment that the
A/C Mode Switch (ACMS) is placed in the ON
position, provided that the condenser fan switch
(CFS) is in the closed position and the thermostat
is calling for cooling. If the condenser coil pressure
reaches the CFS switch cutout setting, the CFS
switch will open to de-energize condenser speed
relay CSR1. (Refer to section 1.2 for switch
settings.); this will cause the condenser fan motors
(CM1 and CM2) to run at high speed.

Содержание Carrier TRANSICOLD 68RM35-604-20

Страница 1: ...T 288 Rearmount 68RM35 604 20 R 134a NYCDOT...

Страница 2: ...MANUAL OPERATION AND BUS AIR CONDITIONING UNIT Rearmount 68RM35 604 20 R 134a Carrier Transicold Division Carrier Corporation P O Box 4805 Syracuse N Y 13221 Carrier Corporation 1999 D Printed in U S...

Страница 3: ...r supply is disconnected Always work in pairs Never work on the equipment alone In case of severe vibration or unusual noise stop the unit and investigate MAINTENANCE PRECAUTIONS Beware of unannounced...

Страница 4: ...rosive and toxic compounds WARNING Be sure to avoid refrigerant coming in contact with the eyes Should refrigerant come in contact with the eyes wash eyes for minimum of 15 minutes with potable water...

Страница 5: ...1 3 TROUBLESHOOTING 3 1 3 1 UNIT WILL NOT COOL 3 1 3 2 SYSTEM RUNS BUT HAS INSUFFICIENT COOLING 3 1 3 3 ABNORMAL PRESSURES 3 1 3 4 ABNORMAL NOISES OR VIBRATIONS 3 2 3 5 TEMPERATURE CONTROLLER MALFUNC...

Страница 6: ...r 4 13 4 18 5 Removing Oil from the Compressor 4 13 5 ELECTRICAL SCHEMATIC WIRING DIAGRAM 5 1 5 1 INTRODUCTION 5 1 LIST OF ILLUSTRATIONS Figure Page 1 1 Unit Assembly Back View 1 2 1 2 Unit Assembly I...

Страница 7: ...l 05G Compressor 4 12 4 12 Compressor Oil Charge Connections 4 13 5 1 Electrical Schematic Diagram Legend and Symbols 5 2 5 2 Electrical Schematic Diagram 5 3 LIST OF TABLES Table Page 1 1 Model Chart...

Страница 8: ...of the bus These units interface with the bus driver switches and pump to provide a complete air conditioning system All control systems are powered by 24 vdc supplied by the bus battery and alternato...

Страница 9: ...11 Discharge Line Isolation Valve 12 Receiver Sight Glass Upper 13 Moisture Liquid Indicator 14 Unloader Pressure Switch UPS3 Upper 15 Condenser Fan Switch CFS Lower 16 Evaporator Fan Housing Curbsid...

Страница 10: ...CS 1 Electrical Control Panel See Figure 1 3 2 Liquid Line Solenoid Valve 3 Thermostatic Expansion Valve TXV 4 Roadside Blower Housing 5 Air Filter 6 Evaporator Coil 7 Curbside Blower Housing 1 CDR 6...

Страница 11: ...14 Cool Disable Relay CDR 15 Evaporator Speed Relay ESR 16 Power Terminal Block PTB 17 Return Air Probe 18 Air Conditioning Stop Relay No 2 ACSR2 19 Heat Relay HR 20 Air Conditioning Stop Relay No 1...

Страница 12: ...k 05G Compressor Electric Unloader Pressure Switches UPS1 UPS2 UPS3 See Table 1 2 for settings 1 3 ELECTRICAL SPECIFICATIONS a Evaporator Blower Motor Bearing Lubrication Factory Lubricated additional...

Страница 13: ...r no 2 Circuit Breaker CB2 Manual Reset Opens at 60 amps Excessive current draw by evaporator fan motor no 1 Circuit Breaker CB3 Manual Reset Opens at 60 amps Excessive current draw by condenser fan m...

Страница 14: ...h set point then the evaporator fan motors will not operate when the thermostat is calling for heat Condenser Motor Overload COL1 and COL2 Each condenser fan motor is equipped with an internal thermal...

Страница 15: ...ON position EFR1 and EFR2 relays are energized When energized a set of internal EFR1 and EFR2 contacts are closed to start the evaporator fan motors Evaporator Overload Relays OR1 and OR2 Evaporator o...

Страница 16: ...nt supply of liquid is available to the evaporator coil as needed and as a storage space when pumping down the system The receiver is equipped with a sight glass to observe correct charge level and a...

Страница 17: ...er Drier Outlet Valve 9 Thermostatic Expansion Valve 10 Evaporator Coil 11 Suction Line 12 Subcooler 13 Liquid Suction Heat Exchanger 14 Condenser Fan Switch CFS 15 Unloader Pressure Switch UPS3 16 Ch...

Страница 18: ...ts to interrupt the compressor clutch circuit when the ambient temperature falls to 45_F 7 2_C Heat is then accomplished by cycling Boost Pump Motor BPM and Reheat Coolant Valve RCV to supply engine c...

Страница 19: ...above the thermostat set point the HEAT COOL switch remains in COOL and the HIGH LOW switch remains in the HIGH position The thermostat discontinues supplying the signal to semi unload the compressor...

Страница 20: ...2 3 T 288 Figure 2 2 Automatic High Speed Cool Mode Operation with Reheat TDR 10 SEC...

Страница 21: ...2 4 T 288 Figure 2 3 Automatic High Speed Cool Mode Operation No Reheat TDR 10 SEC...

Страница 22: ...2 5 T 288 Figure 2 4 Automatic High Speed Heat Mode Operation Below 45_F Ambient TDR 10 SEC...

Страница 23: ...refrigerant flow Low refrigerant charge Service valves partially closed Safety device open Liquid line solenoid valve stuck closed 3 3 3 6 3 7 3 7 and 4 12 4 9 Open 1 4 Check 3 3 ABNORMAL PRESSURES Hi...

Страница 24: ...s defective Motor brushes defective Evaporator fan loose or defective Return air filter dirty Icing of coil dirty coil Fan relays EFR1 OR EFR2 defective Safety device open Check 5 1 4 16 4 16 4 16 Cle...

Страница 25: ...refrigerant lines Turning the valve stem counterclockwise all the way out willbackseat the valve to open the suction or discharge line to the compressor and close off the gauge connection In normal op...

Страница 26: ...h O Ring Hose Fitting with O Ring Figure 4 2 R 134a Manifold Gauge Set Connections To service the refrigerant system the manifold gauge set is connected to the compressor suction low side service valv...

Страница 27: ...d always be used whenever removing contaminated refrigerant from the system If a recovery system is not available proceed as follows a Equipment Required 1 Appropriate evacuated returnable refrigerant...

Страница 28: ...the system prior to leak repair 8 Charge the unit as outlined in section 4 8 4 7 EVACUATION AND DEHYDRATION Proper evacuation and dehydration procedures are imperative when service repairs or compone...

Страница 29: ...ifold vacuum pump vacuum gauge reclaimer and hoses as shown in Figure 4 4 All hand valves on manifold should be closed The compressor service valves should be midseated if used with service valve caps...

Страница 30: ...Open filter drier inlet valve half way and allow the liquid refrigerant to flow into the unit Monitor weight of refrigerant cylinder to determine how much refrigerant is entering the system The corre...

Страница 31: ...ight as viewed Finger tighten flare nuts h Tighten filter drier flare nuts using two open end wrenches i Install vacuum pump on filter drier inlet valve Evacuate to 500 microns and disconnect vacuum p...

Страница 32: ...s No Continuity Switch Opens Continuity Switch Closes High Press ure HPS 300 10 psig 200 10 psig Low Press ure LPS 6 3 psig 25 3 psig Condenser Fan Speed CFS 250 10 psig 190 15 psig Unloader Pressure...

Страница 33: ...firmly secured to suction line as shown in Figure 4 8 Place insulation around TXV bulb and thermocouple 4 Connect suction gauge to the service port on the compressor suction service valve 5 Set tempe...

Страница 34: ...unger or deformed valve body assembly Failure to close may be caused by the following a Defective plunger or deformed valve body assembly b Foreign material in the valve It is not necessary to drain t...

Страница 35: ...Clip Bolt 5 Venturi 6 Evaporator Motor 7 Hub Set Screw 7 Figure 4 10 Evaporator Fan Blower Assembly 4 16 1 Routine Examination and Cleaning a At regular maintenance periods remove brush covers and cl...

Страница 36: ...second filter past the holding channel to the center position and remove e Repeat the above step with the third filter f Reverse the procedure for installing the new filters 4 18 COMPRESSOR 4 18 1 Rep...

Страница 37: ...4 18 2 Checking the Compressor Oil Level NOTE It may be necessary to preheat the coach and or operate the system in the Reheat Mode to keep the compressor fully loaded throughout this procedure a Ope...

Страница 38: ...n oil at all times Otherwise air and moisture will be drawn into the compressor 1 Connect manifold gauge set Place center charging line into compressor oil container as shown in Figure 4 12 Slowly ope...

Страница 39: ...is no pressure at the oil drain plug d Remove the oil drain plug on the bottom plate of the compressor and drain the proper amount of oil from the compressor Replace the plug securely back into the c...

Страница 40: ...5 0 26 0 26 70 21 71 1 490 2 5 00 4 90 4 20 4 6 31 7 0 32 0 32 75 24 78 7 542 6 5 53 5 43 2 19 5 6 36 6 0 39 0 39 80 27 86 7 597 8 6 10 5 98 0 18 6 5 44 8 0 46 0 45 85 29 95 3 657 1 6 70 6 57 2 17 7...

Страница 41: ...5 1 INTRODUCTION This section contains Electrical Schematic Wiring Diagrams covering the Models listed in Table 1 1 Before performing operation and maintenance on the equipment ensure that precaution...

Страница 42: ...HIGH PRESSURE SWITCH HR HEAT RELAY HR2 HEAT RELAY 2 LATH LOW AMBIENT THERMOSTAT LPS LOW PRESSURE SWITCH LSV LIQUID SOLENOID VALVE OR1 EVAPORATOR OVERLOAD RELAY 1 OR2 EVAPORATOR OVERLOAD RELAY 2 PTB P...

Страница 43: ...5 3 T 288 Figure 5 2 Electrical Schematic Diagam Based on Drawing 68RM35 1038 12 TDR 10 SEC...

Страница 44: ...1 4 7 4 8 Condenser Motor Overload 1 7 Condenser Speed Relay 1 4 1 7 1 8 Cool Disable Relay 1 4 1 8 Coolant Valve 3 2 D Description 1 1 3 1 Discharge Line Check Valve 1 2 Discharge Line Isolation Valv...

Страница 45: ...Glass 1 2 Refrigerant Charge 1 5 Reheat Coolant Valve 1 5 2 1 3 2 4 9 Relay Board 1 1 1 4 1 8 Return Air Probe 1 4 S Safety Devices 1 5 1 6 3 1 3 2 Schematic Wiring Diagrams 5 1 Service Valves 3 1 Sub...

Отзывы: