EN - 18
ELECTRICAL CONNECTIONS
39HX models E and C
39HXH
39HXV
SIZE
007
015
020
Voltage (V)
230 V 1-Ph
400 V 3-Ph
Current (A) without electric
heater
6.2
3.6
3.6
Current (A) with internal
electric heater
26.6
16.2
20.2
Additional box
Size
1
2
2
2
3
3
4
4
5
5
Associat
ed model
39HXC/E 010
39HXV 007 and 010
39HXH 007
39HXH
012
39HXV 015
39HXH 016
39HXC/E 020
39HXV 020
39HXE
2500
39HXC/
E
030
39HXC/
E
040
39HXC/
E
050
39HXC/
E
060
39HXE
075
Voltage
230 V 1-Ph
400 V 3-Ph
Current
20
11
16
16
19
25
29
34
46
Connect the unit's electrics to the power network as per the tables above.
Connection to the machine's general switch located inside it (Ø 22.2 blanking cover provided).
If there is an electric heater in the additional box, make provision for the electrical connections.
SIZE
010
020
030
040
050
060
075
100
150
Voltage (V)
230 V 1-Ph
400 V 3-Ph
Current (A) without electric
heater
6.2
3.6
5.5
6.1
6.1
8.7
8.7
17.1
21.9
Current (A) with internal
electric heater
26.6
19.7
24.2
31
35.4
42.5
54.7
89.3
115.7
SIZE
010
012
016
Voltage (V)
230 V 1-Ph
400 V 3-
Ph
Current (A)
6.2
6.2
3.6