EN - 9
E N
TECHNICAL DATA
Air flow rates
39HXC
Operating limit temperature: -20°C/+ 60°C with preheating coil
39HXE
Operating limit temperature: -30°C/+ 60°C
39HXH
Size
Minimum flow rate
(m³/h)
Nominal Flow
Rate
m³/h
Maximum flow
rate
m³/h
007
300
700
1000
012
500
1200
1400
016
600
1600
1900
Operating limit temperature: -20°C/+ 60°C with preheating coil
39HXV
Operating limit temperature: -20°C/+ 60°C with preheating coil
Size
39HXC
Minimum flow rate
(m³/h)
Nominal Flow
Rate
m³/h
Maximum flow
rate
m³/h
010
300
1000
1200
020
500
2000
2200
030
700
3000
3700
040
900
4500
5100
060
1400
6000
6600
Size
39HXE
Minimum flow rate
(m³/h)
Nominal Flow
Rate
m³/h
Maximum flow
rate
m³/h
Maximum flow rate
without cooling coil
m³/h
010
300
1000
1200
1450
020
500
2000
2500
2800
030
700
3000
3700
4500
040
900
4500
5700
5700
050
900
5000
5700
7000
060
1400
6000
8500
8500
075
1400
7500
8500
11000
100
2500
10 000
14 000
14000
150
3000
15 000
18 000
18000
Size
Minimum flow rate
(m³/h)
Nominal Flow
Rate
m³/h
Maximum flow
rate
m³/h
007
300
700
1200
015
700
1500
2000
020
700
2000
2600