EN - 8
Par
Description
Factory setting
Setting 1:
Speed from
potentiometer
Setting 2:
Speed from
contact
Setting 3:
Speed on the
keypad
Eur
Level 1 parameters
1
Minimum speed (Hz)
0
20
2
Maximum speed (Hz)
50
0.55 kW motor:
97
, 1.1 kW motor:
60
, 1.4 kW motor:
65
3
Acceleration ramp-up (s / 100 Hz)
5
5
4
Deceleration ramp-down (s / 100 Hz)
10
10
5
Inverter configuration
AI.AV
AI.AV
Pr
Pad
6
Nominal motor current (A)
Inverter rating
230 V /
: 1 motor: 0.55 kW:
2.4
; 1.1 kW:
4.2
; 1.4 kW:
5
2
motors:
0.55
kW:
4.8
; 1.1 kW:
8.4
; 1.4 kW:
10
400 V / Y: 1 motor: 0.55 kW:
1.4
; 1.1 kW:
2.4
; 1.4 kW:
2.9
2
motors:
0.55
kW:
2.8
; 1.1 kW:
4.8
; 1.4 kW:
5.8
7
Nominal speed (rpm)
1500
0.55 kW motor:
1390
; 1.1 kW motor:
2880
; 1.4 kW motor:
2839
8
Nominal motor voltage (V)
230/400
230/400
230/400
230/400
9
Motor output factor (cos φ)
0.85
0.55 kW motor:
0.8
; 1.1 kW motor:
0.81
; 1.4 kW motor:
0.88
10
Access to the parameters
L1
L2
Level 2 parameters
11
On/Off logic selection
0
0
12
Validation of the brake control
diS
diS
13
Not used
14
Not used
15
Pulse mode reference (Hz)
1.5
1.5
16
Analogue input mode 1 (mA)
4-.20
Volt
4-.20
4-.20
17
Validation of negative preset speeds
OFF
OFF
18
Preset speed 1 (Hz)
0
Speed 1
19
Preset speed 2 (Hz)
0
Speed 2
20
Preset speed 3 (Hz)
0
Speed 3
21
Preset speed 4 (Hz)
0
Speed 4
22
Load display unit
Ld
A
A
A
23
Speed display unit
Fr
Fr
Fr
Fr
24
User scale setting
1
1
1
1
25
User security code
0
3-digit code
3-digit code
3-digit code
26
Not used
27
Keypad reference when powering on
0
0
Last
0
28
Copying parameters
no
No
29
Loading of default settings
no
No
30
Selection of soft start mode
1
1
31
Selection of stop mode
1
0
32
Dynamic U/f selection
OFF
ON
33
Flying restart selection
0
2
34
Mode selection (terminal B7)
dig
Dig
35
Logic output control (terminal B3)
n=0
n=0
36
Analogue output control (terminal B1)
Fr
Fr
37
Maximum switching frequency (kHz)
12-18
12 - 18 (max)
38
Auto calibration
0
0
39
Nominal motor frequency (Hz)
50
50
40
Number of motor poles
Auto
Auto
41
Voltage mode selection
Ur l
Ur I
42
Voltage boost at low frequency (%)
3
3
43
Transmission speed by serial link
19.2
19.2
44
Serial link address
1
1
45
Software version
46
Brake opening current threshold (%)
50
50
47
Brake opening current threshold (%)
10
10
48
Brake opening frequency (Hz)
1
1
49
Brake closing frequency (Hz)
2
2
50
Time delay before brake opening (s)
1
1
51
Brake opening time delay (s)
1
1
52
Fieldbus node address
0
0
53
Fieldbus transmission speed
0
0
54
Fieldbus diagnostics
0
0
55
Last switch to safety mode
0
0