-9-

METHOD A -

 12” (304.8 mm) Clearance to Combustible Wall 

Member:  Using  a  minimum  thickness  3.5”  (89  mm)  brick 

and  a  5/8”  (15.9  mm)  minimum  wall  thickness  clay  liner, 

construct a wall pass-through. The clay liner must conform 

to ASTM C315 (Standard Specification for Clay Fire Linings) 

or its equivalent. Keep a minimum of 12” (304.8 mm) of brick 

masonry between the clay liner and wall combustibles. The 

clay liner shall run from the brick masonry outer surface to 

the inner surface of the chimney flue liner but not past the 

inner surface. Firmly grout or cement the clay liner in place 

to the chimney flue liner.

METHOD B - 

9” (228.6 mm) Clearance to Combustible Wall 

Member:  Using  a  6”  (152.4  mm)  inside  diameter,  listed, 

factory-built  Solid-Pak  chimney  section  with  insulation 

of  1”  (25.4  mm)  or  more,  build  a  wall  pass-through  with  a 

minimum 9” (228.6 mm) air space between the outer wall of 

the chimney length and wall combustibles. Use sheet metal 

supports  fastened  securely  to  wall  surfaces  on  all  sides, 

to  maintain  the  9”  (228.6  mm)  air  space.  When  fastening 

supports to chimney length, do not penetrate the chimney 

liner (the inside wall of the Solid-Pak chimney). The inner end 

of the Solid-Pak chimney section shall be flush with the inside 

of the masonry chimney flue, and sealed with a non-water 

soluble refractory cement. Use this cement to also seal to 

the brick masonry penetration.

METHOD C - 

6” (152.4 mm) Clearance to Combustible Wall 

Member: Starting with a minimum 24 gage (.024” [.61 mm]) 

6” (152.4 mm) metal chimney connector, and a minimum 

24 gage ventilated wall thimble which has two air channels 

of  1”  (25.4  mm)  each,  construct  a  wall  pass-through. 

There  shall  be  a  minimum  6”  (152.4  mm)  separation  area 

containing fiberglass insulation, from the outer surface of the 

wall thimble to wall combustibles. Support the wall thimble, 

and cover its opening with a 24-gage minimum sheet metal 

support.  Maintain  the  6”  (152.4  mm)  space.  There  should 

also be a support sized to fit and hold the metal chimney 

connector. See that the supports are fastened securely to 

wall surfaces on all sides. Make sure fasteners used to secure 

the  metal  chimney  connector  do  not  penetrate  chimney 

flue liner.

METHOD D - 

2” (50.8 mm) Clearance to Combustible Wall 

Member: Start with a solid-pak listed factory built chimney 

section at least 12” (304 mm) long, with insulation of 1” (25.4 

mm) or more, and an inside diameter of 8” (2 inches [51 mm] 

larger than the 6” [152.4 mm] chimney connector). Use this 

as a pass-through for a minimum 24-gauge single wall steel 

chimney connector. Keep solid-pak section concentric with 

and  spaced  1”  (25.4  mm)  off  the  chimney  connector  by 

way of sheet metal support plates at both ends of chimney 

section. Cover opening with and support chimney section 

on both sides with 24 gage minimum sheet metal supports. 

See that the supports are fastened securely to wall surfaces on all sides. Make sure fasteners used to secure 

chimney flue line do not penetrate the inner liner.

NOTES:

1.  Connectors to a masonry chimney, excepting method B, shall extend in one continuous section through the 

wall pass-through system and the chimney wall, to but not past the inner flue liner face.

2.  A chimney connector shall not pass through an attic or roof space, closet or similar concealed space, or a 

floor, or ceiling.

COMBUSTIBLE WALL CHIMNEY CONNECTOR PASS-THROUGHS

Le dégagement minimum de la cheminée à la brique et les

matériaux combustibles est de 5 cm (2 po) (50,8 mm)

Le dégagement minimum de la cheminée à la brique et les

matériaux combustibles est de 5 cm (2 po) (50,8 mm)

30 cm (304,8 mm, 12 po)

minimum aux matériaux

combustibles

Cheminée en

maçonnerie

Conduit de cheminée

Doublage en

argile réfractaire

Conduit de

raccordement

Dégagement minimum

de 30 cm (12 po, 

304,8 mm)

des briques 

Conduit de cheminée

Conduit de

raccordement

Dégagement minimum

de 5 cm (9 po)

(228,6 mm)

Nonsoluble

refractory

cement

Supports de

tôle d'acier

Cheminée en maçonnerie

Longueur de cheminée

à égalité avec le conduit

de fumée intérieur

Utiliser des pièces

de cheminée

fabriquées pour

le fixer solidement

au raccordement.

Vide d’air

Longueur de

cheminée

préfabriquée et

répertoriée, à

isolant solide.

Minimum Vide d’air

de 5 cm (9 po)

(228,6 mm)

Longueur de

cheminée préfabriquée

Cheminée en maçonnerie

Supports de

tôle d'acier

Conduit de cheminée

Conduit de

raccordement

Le dégagement minimum de la cheminée aux

supports en tôle d’acier et aux matériaux

combustibles est de 5 cm (2 po). (50,8 mm)

Deux canaux d’aération

de 2,5 cm (1 po)

chacun. (25,4 mm)

Deux canaux d’aération

de 2,5 cm (1 po)

chacun. (25,4 mm)

Fabriqués en

tôle d’acier

Le dégagement minimum de la cheminée

aux supports en tôle d’acier et aux matériaux

combustibles est de 5 cm (2 po). (50,8 mm)

Isolant de fibre de

verre d’un minimum

de 152,4 mm (6 po).

Conduit de

raccordement

Conduit de cheminée

Cheminée

en maçonnerie

Supports de

tôle d'acier

Conduit de

raccordement

Supports de

tôle d'acier

Vide d’air de 5 cm

(2 po) (50,8 mm)

Longueur de

la cheminée

Section de

cheminée

1 po. Vide d’air

de (25,4 mm) à

la longueur de

cheminée

Dégagement minimum

de 5 cm (2 po)

(50,8 mm)

Содержание VOGELZANG VG2520

Страница 1: ...veuillez consulter le site www P65warnings ca gov Report Number F19 487 United States Stove Company PO Box 151 227 Industrial Park Rd South Pittsburg TN 37380 PH 800 750 2723 www usstove com SAFETY NO...

Страница 2: ...ack or Blued Steel 2100 F 650 C Minimum Chimney Height 12 3 7m Maximum Log Length 21 534mm Dimensions Overall Depth x Width x Height VG2520 BL 25 x 27 x 31 25 635 mm x 686 mm x 794 mm VG2520 BP 25 47...

Страница 3: ...shown using the 3 5 16 18 x 1 1 2 bolts 3 washers and 3 weld tabs provided in the parts box FIREBRICK CONFIGURATION Replace the Firebrick as shown in the illustration Assembly Instructions TOOLS AND M...

Страница 4: ...E IN THIS HEATER KEEP ALL SUCH LIQUIDS WELL AWAY FROM THE HEATER WHILE IT IS IN USE IN THE EVENT OF A CHIMNEY FIRE PUSH THE AIR CONTROL FULL CLOSED TO DEPRIVE THE FIRE OF OXYGEN CALL THE FIRE DEPARTME...

Страница 5: ...3 13 331 331 D 30 29 762 737 E 10 10 254 254 F 20 20 508 508 OUTSIDE COMBUSTION AIR Your wood stove is approved to be installed with an outside air intake 4FAK which is necessary for a mobile home Thi...

Страница 6: ...MUST BE ATTACHED TO THE STRUCTURE OF THE MOBILE HOME SECURING APPLIANCE S ON A PEDESTAL TO THE FLOOR Use the designated holes to secure the unit to the floor SECURING APPLIANCE S WITH LEGS TO THE FLOO...

Страница 7: ...o the room through appliance and chimney connector joints An uncontrollable burn or excessive temperature indicates an excessive draft CHIMNEY Your wood stove may be hooked up with a 6 factory built o...

Страница 8: ...as recommended by the manufacturer The chimney must be the required height above the roof or other obstructions for safety and proper draft operation MASONRY CHIMNEY Ensure that a masonry chimney meet...

Страница 9: ...connector Use this as a pass through for a minimum 24 gauge single wall steel chimney connector Keep solid pak section concentric with and spaced 1 25 4 mm off the chimney connector by way of sheet me...

Страница 10: ...rain or snow also accelerates the drying time A good indicator of if the wood is ready to burn is to check the piece ends If cracks are radiating in all directions from the center then the wood shoul...

Страница 11: ...ling on it and close the door If the piece ignites within 90 seconds from the time it was placed into the stove your wood is correctly dried If ignition takes longer your wood is damp If your wood his...

Страница 12: ...oom temperature when leaving the system and therefore calculations using this heating value consider the heat going up the chimney as lost energy Therefore efficiency calculated using the lower heatin...

Страница 13: ...these gases is somewhere between 275 F and 500 F Below these temperatures the build up of creosote is promoted Above 500 F heat is wasted since a too large quantity is lost into the atmosphere TO PREV...

Страница 14: ...e sold The glass should be washed only when cold PAINT Only clean your stove with a dry soft cloth that will not harm the paint finish If the paint becomes scratched or damaged it is possible to give...

Страница 15: ...6 Flue Collar 1 2 88042 1 4 Rope Gasket 1 3 25845 Air Deflector 1 4 891492 Blower Assembly B36 1 5 26060 Rear Shield 1 6 610926 Rear Ashpan VG2520 BP 1 7 29243 Pedestal VG2520 BP 1 8 29065 Pedestal Fr...

Страница 16: ...ndary Air Tube 7 32 2 6 29248 Left Brick Panel 1 7 24103A Half Firebrick Pumice 4 1 2 X 4 1 2 1 8 40561 Ash Plug 1 9 891530A Firebrick 4 5 X 7 5 X 1 25 1 10 89066A Firebrick Pumice 4 1 2 X 9 18 11 891...

Страница 17: ...17 Notes...

Страница 18: ...18 Notes...

Страница 19: ...7 Date _____________________ Engineer Name ________________________________ License No ____________________________________ Company _____________________________________ Telephone No _________________...

Страница 20: ...ECHANGE VEUILLEZ CONSERVER CE GUIDE DANS UN ENDROIT S R DES FINS DE R F RENCE LORSQUE VOUS NOUS CRIVEZ VEUILLEZ INDIQUER LE NUM RO COMPLET DU MOD LE QUI FIGURE SUR LA PLAQUE SIGNAL TIQUE DE L APPAREIL...

Страница 21: ...____________________________ Service de 07 Date _____________________ Nom de l ing nieur ____________________________ N de licence _________________________________ Compagnie _________________________...

Страница 22: ...cription Qt 1 893156 Poign e en bois 1 2 893164 Poign e de porte 1 3 893062 Manchon rouleau 1 4 83788 Vis t te creuse 1 5 891373 Patin de charni re de porte filet 2 6 40880 grande porte en fonte carr...

Страница 23: ...destal VG2520 BP 1 10 610968 Logement en cendrier VG2520 BL 1 11 610883 Soudure de jambe VG2520 BL 4 12 25826 Plaque de foyer 1 13 29216 Cendrier 1 14 610068 Soudure de glissi re d amortisseur 1 15 61...

Страница 24: ...retiennent les moulures de la vitre l int rieur de la porte Retirez les moulures et remplacez la pi ce endommag e par une neuve Effectuez la proc dure en sens inverse apr s remplacement Lors du rempla...

Страница 25: ...ontinuez en ouvrant la porte tr s lentement ouvrez d un ou deux pouces pendant 5 10 secondes avant de l ouvrir compl tement pour augmenter le tirage et liminer ainsi les fum es qui sont stagnantes dan...

Страница 26: ...premi res heures de fonctionnement N ouvrez jamais la commande d air plus que n cessaire afin d obtenir une vitesse de combustion moyenne Assurez vous que la circulation d air soit suffisante lors du...

Страница 27: ...b ches br l es la fois pour vous assurer que la temp rature ne d passe jamais 246 C 475 F sur un thermom tre magn tique pour une installation sur des tuyaux de po le paroi simple ou 482 C 900 F sur s...

Страница 28: ...z avec une partie de chemin e Solid Pak fabriqu e en usine agr e d au moins 12 304 mm de diam tre int rieur avec une isolation de 1 25 4 mm ou plus et un raccord de chemin e de 8 de diam tre int rieur...

Страница 29: ...n bon tirage CHEMIN E EN MA ONNERIE Assurez vous qu une chemin e en ma onnerie r ponde aux standards minimum de l Association nationale de protection contre les incendies NFPA en la faisant inspecter...

Страница 30: ...p rature excessive indique un tirage excessif Pente de po par pied Partie m le vers le bas 3 vis Vers l appareil Installer l extr mit sertie vers le po le Direction de la circulation des gaz de condui...

Страница 31: ...LE PO LE DOIT TRE FIX LA STRUCTURE DE LA MAISON MOBILE UTILISEZ LES DEUX 2 TROUS AU FOND DU PI DESTAL DE LA RADIATEUR POUR FIXER L APPAREIL AU SOL Illustration Fixation Du R chauffeur Au Plancher Util...

Страница 32: ...des mati res combustibles 2 Les appareils foyer existants au sein du domicile tels que des chemin es ou d autres appareils de chauffage mettent des odeurs ne fonctionnent pas correctement mettent des...

Страница 33: ...l avant de l unit Le d gagement entre le tuyau de carneau et un mur est valable uniquement pour les murs verticaux et pour un tuyau de carneau vertical S il y a un conduit de chemin e horizontal il do...

Страница 34: ...LIQUIDE D ALLUMAGE DE CHARBON OU DE LIQUIDES SIMILAIRES POUR D MARRER OU RAVIVER UN FEU DANS CE PO LE MAINTENEZ TOUS CES LIQUIDES LOIGN S DU PO LE EN CAS D INCENDIE DE CHEMIN E FERMEZ COMPL TEMENT LA...

Страница 35: ...Visualisation Largeur x Hauteur 16 po x 10 26 po 407 mm x 261 mm ACCESSOIRES EN OPTION DESCRIPTION N PI CE Kit d admission d air ext rieur 4FAK AVERTISSEMENTS CHAUD DURANT LE FONCTIONNEMENT MAINTENEZ...

Страница 36: ...issions de particules de 2020 AVERTISSEMENT CONCERNANT LA PROPOSITION 65 DE L TAT DE LA CALIFORNIE Ce produit peut vous exposer des agents chimiques y compris au monoxyde de carbone lesquels sont reco...

Отзывы: