CHIMNEY MAINTENANCE

CAUTION:

DO NOT OVERFIRE APPLIANCE. YOU ARE 

OVERFIRING IF ANY PART OF THE APPLIANCE 

GLOWS RED. CLOSE THE DOOR AND SHUT DAMPER 

IMMEDIATELY TO REDUCE THE AIR SUPPLY AND 

SLOW DOWN THE FIRE.

CAUTION:

SLOW BURNING FIRES FOR EXTENDED USE OR 

BURNING GREEN WOOD MAY CAUSE EXCESSIVE 

CREOSOTE BUILD-UP. IGNITION OF CREOSOTE 

OR OVERFIRING COULD CAUSE A CHIMNEY 

FIRE. CHIMNEY FIRES BURN EXTREMELY HOT 

AND MAY IGNITE SURROUNDING COMBUSTIBLE 

MATERIALS. IN CASE OF A CHIMNEY FIRE, CALL 

THE FIRE DEPARTMENT IMMEDIATELY! 

CREOSOTE FORMATION AND NEED FOR 

REMOVAL

When wood is burned slowly, it produces tar and other 

organic vapors, which combine with expelled moisture 

to form creosote. The creosote vapors condense in the 

relatively cool chimney flue of a slow-burning fire. As a 

result, creosote residue accumulates on the flue lining. 

When ignited this creosote makes an extremely high 

temper fire. The chimney connector and chimney should 

be inspected at least once every two months during the 

heating season to determine if a creosote build-up has 

occurred. If creosote has accumulated (3 mm or more), 

it should be removed to reduce the risk of a chimney fire.
We strongly recommend that you install a magnetic 

thermometer on your smoke exhaust pipe, approximately 

18” above the stove. This thermometer will indicate the 

temperature of your gas exhaust fumes within the smoke 

exhaust system. The ideal temperature for these gases 

is somewhere between 275°F and 500°F. Below these 

temperatures, the build-up of creosote is promoted. 

Above 500°F, heat is wasted since a too large quantity is 

lost into the atmosphere.

TO PREVENT CREOSOTE BUILD UP

•  Always burn dry wood. This allows clean burns and 

higher chimney temperatures, therefore less creosote 

deposit.

•  Leave the air control fully open for about 5 min. every 

time you reload the stove to bring it back to proper 

operating temperatures. The secondary combustion 

can only take place if the firebox is hot enough.

•  Always check for creosote deposit once every two 

months and have your chimney cleaned at least once 

a year.

•  If a chimney or creosote fire occurs, close all dampers 

immediately. Wait for the fire to go out and the heater 

to cool, then inspect the chimney for damage. If no 

damage results, perform a chimney cleaning to ensure 

no more creosote deposits is remaining in the chimney.

CAUTION:

A CHIMNEY FIRE MAY CAUSE IGNITION OF WALL 

STUDS OR RAFTERS WHICH WERE ASSUMED TO 

BE A SAFE DISTANCE AWAY FROM THE CHIMNEY. 

IF A CHIMNEY FIRE OCCURS, HAVE YOUR 

CHIMNEY INSPECTED BY A QUALIFIED EXPERT 

BEFORE USING AGAIN.

ASH REMOVAL & DISPOSAL

Whenever ashes get 3 to 4 inches deep in your firebox or 

ash pan, and when the fire has burned down and cooled, 

remove excess ashes. Leave an ash bed approximately 

1 inch deep on the firebox bottom to help maintain a 

hot charcoal bed. Ashes should be placed in a metal 

container with a tight-fitting lid. The closed container of 

ashes should be placed on a non-combustible floor or the 

ground, away from all combustible materials, pending 

final disposal. The ashes should be retained in the closed 

container until all cinders have thoroughly cooled.

CAUTIONS:

•  ASHES COULD CONTAIN HOT EMBERS EVEN 

AFTER TWO DAYS WITHOUT OPERATING THE 

STOVE.

•  THE ASH PAN CAN BECOME VERY HOT. WEAR 

GLOVES TO PREVENT INJURY.

•  NEVER BURN THE STOVE WITH THE ASH TRAP 

OPEN. THIS WOULD RESULT IN OVER FIRING 

THE STOVE. DAMAGE TO THE STOVE AND EVEN 

HOUSE FIRE MAY RESULT.

SMOKE & CO MONITORS

Burning wood naturally produces smoke and carbon 

monoxide(CO) emissions. CO is a poisonous gas when 

exposed to elevated concentrations for extended 

periods. While the modern combustion systems in 

heaters drastically reduce the amount of CO emitted 

NEVER OPERATE THIS PRODUCT WHILE UNATTENDED

Содержание US1100E-P

Страница 1: ...e shift compromises during the installation of this heater Contact local building or fire officials about permits restrictions and installation requirements in your area NEVER OPERATE THIS PRODUCT WHI...

Страница 2: ...ght US1100E Leg 21 3 542 mm 24 5 623 mm 30 9 785 mm US1100E Pedestal 21 1 536 mm 22 5 572 mm 31 7 806 mm Combustion Chamber Width x Depth 18 25 x 11 5 464 mm X 293 mm Firebox Volume Cubic Feet 1 31 cu...

Страница 3: ..._________________________________________ If no Date of inspection of the existing chimney system ___________________________________________________________ COMMISSIONING Confirm Hearth Pad Installat...

Страница 4: ...BLOWER ASSEMBLY The blower assembly must be disconnected from the source of electrical supply before attempting the installation The blower assembly is intended for use only with a stove that is marke...

Страница 5: ...SOURCE OF FRESH AIR INTO THE ROOM OR SPACE HEATED SHALL BE PROVIDED WHEN REQUIRED US Stove highly recommends your stove be installed by a qualified NFI US or WETT Canada technician To find the nearest...

Страница 6: ...on of combustible construction is desired the installation must conform to CAN CSA B365 A flue pipe crossing a combustible wall must have a minimum clearance of 18 457 2 mm To reduce flue clearances f...

Страница 7: ...ed for your specific flooring 3 Install one bracket per leg or consult your local authority having jurisdiction to determine how many points of attachment are required In addition to the previously de...

Страница 8: ...ctor joints An uncontrollable burn or excessive temperature indicates an excessive draft CHIMNEY Your wood stove may be hooked up with a 6 factory built or masonry chimney If you are using a factory b...

Страница 9: ...ction Association NFPA by having it inspected by a professional Make sure there are no cracks loose mortar or other signs of deterioration and blockage Be sure to the chimney cleaned before the stove...

Страница 10: ...nd cover its opening with a 24 gage minimum sheet metal support Maintain the 6 152 4 mm space There should also be a support sized to fit and hold the metal chimney connector See that the supports are...

Страница 11: ...ific varieties have better energy yields than others Higher efficiencies and lower emissions generally result when burning air dried seasoned hardwoods as compared to softwoods or too green or freshly...

Страница 12: ...ced in the stove your wood is correctly dried If ignition takes longer your wood is damp If your wood hisses and water or vapor escapes at the ends of the piece your wood is soaked or freshly cut gree...

Страница 13: ...f wood during start up and a high burn rate to increase the stove temperature 3 5 4 lbs Pull the air control out fully in the HI position Light the newspaper and leave the door slightly open for about...

Страница 14: ...rly and has a high wood moisture content will produce excess visible smoke and burn poorly AIR TUBES The air tubes assembled in this unit are designed to provide an accurate mix of secondary air to en...

Страница 15: ...Leave the air control fully open for about 5 min every time you reload the stove to bring it back to proper operating temperatures The secondary combustion can only take place if the firebox is hot e...

Страница 16: ...r uses a 1 diameter rope gasket It is recommended that you change the door gasket which makes your stove door air tight once a year in order to ensure good control over the combustion maximum efficien...

Страница 17: ...D TAILS TECHNIQUES 120VAC 60 Hz CA 0 55AMP BLACK NOIR BLACK NOIR NOTICE DO NOT ALLOW THE POWER CORD TO TOUCH HOT SURFACES KEEP THE POWER CORD AT LEAST 12 30 5CM FROM THE STOVE OR PIPE SURFACES DANGER...

Страница 18: ...E BL 4 IN ORDER TO MAINTAIN WARRANTY COMPONENTS MUST BE REPLACED USING ORIGINAL MANUFACTURERS PARTS PURCHASED THROUGH YOUR DEALER OR DIRECTLY FROM THE APPLIANCE MANUFACTURER USE OF THIRD PARTY COMPONE...

Страница 19: ...ption Qty 1 893241 US Complete Door Handle 1 2 40887 Medium Arched Door 1 3 88324 1 Rope Gasket 1 4 893159 Clear Glass 1 5 29229 Glass Retainer Sides 2 6 29227 Glass Retainer Top 1 7 29230 Gasket Clam...

Страница 20: ...____________________ Engineer Name _____________________________________ License No _________________________________________ Company ___________________________________________ Telephone No _________...

Страница 21: ...____________________ Service de 07 Date ______________________ Nom de l ing nieur _________________________________ N de licence ______________________________________ Compagnie ______________________...

Страница 22: ...secondaire 1 6 891414 Demi brique r fractaire 4 7 89066 Brique r fractaire 4 1 2 X 9 4 8 891095 Brique r fractaire 6 X 8 1 4 3 9 23783 Brique r fractaire 1 1 4 X 2 9 16 X 9 4 10 86903 Tube secondaire...

Страница 23: ...8 Soudure d amortisseur 1 8 86709 Tige amortisseur 1 9 891987 Bouton en plastique 1 10 610918 Panneau d acc s US1100E BP 1 11 610944 Soudure de logement en cendrier US1100E BL 1 12 40566 Pied en fonte...

Страница 24: ...R BLACK NOIR AVIS NE PERMETTEZ PAS AU CORDON D ALIMENTATION DE TOUCHER LES SURFACES CHAUDES GARDER LE CORDON D ALIMENTATION AU MOINS 12 po 30 5CM DES SURFACES DU PO LE OU DU TUYAU DANGER RISQUE D LECT...

Страница 25: ...cet appareil utilise un joint de corde de 1 po de diam tre Il est recommand de changer le joint de porte qui rend la porte de votre po le tanche l air une fois par an afin d assurer un bon contr le d...

Страница 26: ...contr le d air compl tement ouvert pendant environ 5 min chaque fois que vous rechargez le po le pour le ramener des temp ratures de fonctionnement appropri es La combustion secondaire ne peut avoir...

Страница 27: ...air assembl s dans cette unit sont con us pour offrir un m lange pr cis d air secondaire et assurer une plus grande efficacit Tout dommage ou d t rioration de ces conduits peuvent r duire l efficacit...

Страница 28: ...et un taux de combustion lev pour augmenter la temp rature du po le 3 5 4 lbs Tirez compl tement la commande d air en position HI Allumez le journal et laissez la porte l g rement ouverte pendant envi...

Страница 29: ...xtr mit s de la pi ce votre bois est tremp ou fra chement coup vert N utilisez pas ce bois dans votre po le De grandes quantit s de cr osote pourraient se d poser dans votre chemin e cr ant des condit...

Страница 30: ...ts nerg tiques que d autres Des rendements plus lev s et des missions plus faibles r sultent g n ralement de la combustion de bois durs s ch s l air par rapport aux r sineux ou aux feuillus trop verts...

Страница 31: ...ord de chemin e m tallique V rifiez que les supports soient fix s de fa on s re aux surfaces de la paroi sur tous les c t s Assurez vous que les l ments de fixation utilis s pour maintenir le raccord...

Страница 32: ...as de fissures de mortiers perdus ou d autres signes de d t rioration et de blocage Faites nettoyer la chemin e avant d installer et de faire fonctionner le po le Lors du raccordement du po le travers...

Страница 33: ...nad quat causera des fuites de fum e par l appareil dans la pi ce s infiltrant par l appareil et les joints du conduit de raccordement Un br lage incontr lable ou une temp rature excessive indique un...

Страница 34: ...n de nivellement ins r dans le pied 2 Une fois l appareil nivel positionnez le support et fixez le au sol l aide du mat riel appropri n cessaire pour votre rev tement de sol sp cifique 3 Installez un...

Страница 35: ...lations canadiennes o le passage travers un mur ou une cloison de construction combustible est souhait l installation doit tre conforme la norme CAN CSA B365 Un conduit de fum e traversant un mur comb...

Страница 36: ...SI N CESSAIRE US Stove recommande fortement que votre po le soit install par un technicien qualifi NFI US ou WETT Canada Pour trouver l installateur qualifi le plus proche acc dez https nficertified o...

Страница 37: ...urce d alimentation lectrique avant de tenter l installation L ensemble sou eur est destin tre utilis uniquement avec un po le qui est marqu pour indiquer une telle utilisation Ne faites pas passer le...

Страница 38: ...ion du syst me de chemin e existant ____________________________________________________________________ MISE EN SERVICE Confirmer l installation du tapis de foyer conform ment aux instructions d inst...

Страница 39: ...po 785 mm US1100E pi destal 21 1 po 536 mm 22 5 po 572 mm 31 7 po 806 mm Chambre de combustion Largeur x profondeur 18 25 po X 11 5 po 464 mm X 293 mm Volume Firebox Pieds cubes 1 31 pieds cubes Ouve...

Страница 40: ...S UTILISER CE PRODUIT SANS SURVEILLANCE MISE EN GARDE Veuillez lire l int gralit de ce manuel avant d installer ou d utiliser votre nouveau radiateur Le non respect des instructions peut entra ner des...

Отзывы: